Section 1
DOE O 420.1
U.S. Department of Energy ORDER
Washington, D.C.
Approved: 10-13-95
Review Date: 10-13-97
SUBJECT: FACILITY SAFETY Chg 1: 11-16-95
DISTRIBUTION: INITIATED BY:
All Departmental Elements The Office of Human Resources
and Administration
1. OBJECTIVE. The objective of this Order is to establish facility safety requirements related
to: nuclear safety design, criticality safety, fire protection and natural phenomena hazards
mitigation.
2. CANCELLATION. The Orders listed below are canceled. Cancellation of an Order does not,
by itself, modify or otherwise affect any contractual obligation to comply with such an Order.
Canceled Orders which are incorporated by reference in a contract shall remain in effect until
the contract is modified to delete the reference to the requirements in the canceled Orders.
a. DOE 5480.28, NATURAL PHENOMENA HAZARDS MITIGATION
b. DOE 5480.7A, FIRE PROTECTION
c. DOE 6430.1A, GENERAL DESIGN CRITERIA (NUCLEAR AND EXPLOSIVES
SAFETY REQUIREMENTS)
d. DOE 5480.24, CRITICALITY SAFETY
3. APPLICABILITY.
a. DOE Elements. Except for the exclusions in paragraph 3c, this Order applies to DOE
Elements with responsibility for DOE-owned or leased facilities as follows (see
Attachment 1, Table 1, "Facility and Activity Applicability"):
(1) 4.2, 4.4 All DOE nuclear and non-nuclear facilities.
(2) 4.1, 4.3 All DOE non-reactor nuclear facilities which are classified as
Hazard Categories 1, 2, or 3; and explosives facilities.
b. Contractors. Except for the exclusions in paragraph 3c, the Contractor Requirements
Document (CRD), Attachment 2, sets forth requirements that are to be applied to the
universe of contractors awarded contracts for management and operating contracts.
Contractor compliance with the CRD will be required to the extent set forth in a
contract. Contractors shall be directed to continue to comply with the requirements of
Orders canceled by this Order until their contracts are modified to delete the reference
to the requirements of the canceled Orders.
Vertical line denotes change.
CANCELE
D
2 DOE O 420.1
10-13-95
c. Exclusions.
(1) Activities that are regulated through a license by the Nuclear Regulatory
Commission (NRC) or a State under an Agreement with the NRC,
including activities certified by the NRC under section 1701 of the
Atomic Energy Act;
(2) Activities conducted under the authority of the Director, Naval Nuclear
Propulsion Program, as described in Public Law 98-525;
(3) Activities conducted under the Nuclear Explosives and Weapons Safety
Program relating to the prevention of accidental or unauthorized nuclear
detonations to the extent a requirement under this part cannot be
implemented for a particular facility in a manner that does not
compromise the effectiveness of such activities;
(4) Activities that are regulated by the Department of Transportation or
pursuant to 49 CFR 173.7(b);
(5) Accelerator facilities that are covered by DOE Order 5480.25 (excluded
from §§4.1 and 4.3 but not from §§4.2 and 4.4.);
(6) Fusion facilities (excluded from §§4.1 and 4.3 but not from §§4.2 and
4.4.).
4. REQUIREMENTS. Each section of this Order has specific requirements, and where
appropriate schedules for implementing requirements and specific exemptions, which
are provided in the following corresponding sections of this Order. In complying with
the provisions of this Order, determinations regarding the acceptability of design
should include comparison with existing safety basis information, if available. All
new construction shall, as a minimum, conform to the Model Building Codes
applicable for the state or region, supplemented with additional safety requirements
associated with the hazards in the facility in a graded manner.
Section 2
Guidance associated with this Order are not mandatory requirements. The guidance
provided in implementation guides and standards referenced therein are acceptable
methods to satisfy the requirements of this Order. Alternative methods that satisfy the
requirements of this Order are also acceptable. Any implementation method selected
must be justified to ensure that an adequate level of safety commensurate with the
identified hazards is achieved.
CANCELE
D
DOE O 420.1 3
10-13-95
4.1. Nuclear and Explosives Safety Design Criteria
Nuclear Safety
The objectives of section 4.1 for nuclear safety are to ensure that Department of Energy
(DOE) non-reactor nuclear facilities are designed and constructed so as to assure adequate
protection for the public, workers, and the environment from nuclear hazards. The
requirements of this section apply to the activities of design and construction of new Hazard
Category 1, 2, and 3 DOE non-reactor nuclear facilities and to the design and construction of
modifications to existing DOE Hazard Category 1, 2, and 3 non-reactor nuclear facilities
when the proposed modifications significantly degrades the approved safety basis for the
facility. Modifications to facility design and construction during the design and construction
phase shall conform to the requirements for new facilities. Section 4.1 does not apply to the
decision process to modify a facility, except to serve as a standard of comparison for safety
requirements. Activities associated with facility deactivation at end of life are exempt if
justified by a safety analysis.
Explosives Safety
The objective of section 4.1 for explosives safety is to establish mandatory standards for
explosives safety in the design and construction of DOE explosives facilities or modifications
thereof. Explosives facilities are those facilities or locations used for storage or operations
with explosives or ammunition. When these facilities are also non-reactor nuclear facilities,
the requirements for nuclear safety design also apply.
4.1.1 Nuclear Safety
4.1.1.1 General Requirements
Detailed application of these requirements shall be guided by safety analyses that establish the
identification and functions of safety (safety class and safety significant) Structures, Systems,
and Components (SSCs) for a facility and establish the significance to safety of functions
performed by those SSCs. Safety analyses shall consider facility hazards, natural phenomena
hazards, and external man-induced hazards. Factors such as proximity to nearby facilities
such as airports, pipelines, and barge traffic peculiar to the site shall be considered. A safety
analysis shall be performed at the earliest practical point in conceptual or preliminary design,
so that required functional attributes of safety SSCs can be specified in the detailed design.
Safety analyses shall be performed in accordance with Safety Analysis Report (SAR)
guidance for safety analysis, as described in DOE guidance documents.
4.1.1.2 Design Requirements
Non-reactor nuclear facilities shall be designed with the objective of providing multiple layers
of protection to prevent or mitigate the unintended release of radioactive materials to the
environment. Defense in depth shall include: siting, minimization of material at risk, the use
of conservative
CANCELE
D
4 DOE O 420.1
10-13-95
Section 3
design margins and quality assurance; the use of successive physical barriers for protection
against the release of radioactivity; the provision of multiple means to ensure critical safety
functions (those basic safety functions needed to control the processes, maintain them in a
safe state, and to confine and mitigate radioactivity associated with the potential for accidents
with significant public radiological impact); the use of equipment and administrative controls
which restrict deviations from normal operations and provide for recovery from accidents to
achieve a safe condition; means to monitor accident releases required for emergency
responses; and the provision of emergency plans for minimizing the effects of an accident.
Facilities shall be sited and designed in such a manner that gives adequate protection for the
health and safety of the public and for workers, including those at adjacent facilities, from the
effects of potential facility accidents involving the release of radioactive materials.
Facilities shall be designed to facilitate safe deactivation, decommissioning and
decontamination at end of life.
Facilities shall be designed to facilitate inspections, testing, maintenance, repair and
replacement of safety SSCs as part of an overall reliability, availability, and maintainability
program. The objective is that the facility can be maintained in a safe state, including during
these operations, and in keeping with the as low as is reasonably achievable (ALARA)
principle for occupational radiation exposure.
Facilities shall be designed to keep occupational radiation exposure within statutory limits and
incorporate ALARA principles in design, including design provisions to facilitate
decontamination during the operational period.
Facility process systems shall be designed to minimize the production of wastes and minimize
the mixing of radioactive and non radioactive wastes.
Safety SSCs identified in accordance with this section shall, commensurate with the
importance of the safety functions performed, be designed: (1) so that they can perform their
safety functions when called upon to operate, and (2) under a quality assurance program that
satisfies 10 CFR 830.120.
4.1.2 Explosives Safety
The safety design of all new DOE explosives facilities and all modifications to existing
explosives facilities shall conform to the DOE explosives safety requirements established in
the DOE Explosives Safety Manual, DOE M 440.1-1. Facility structural design and
construction shall comply with the requirements of TM5-1300, Structures to Resist the Effects
of Accidental Explosions, and DOE/TIC-11268, A Manual for the Prediction of Blast and
Fragment Loading of Structures. Blast-resistant design for personnel and facility protection
shall be based on the TNT equivalency of the maximum quantity of explosives and
propellants permitted. In accordance with TM5-1300, the TNT equivalency shall be
increased by 20% for design purposes.
CANCELE
D
DOE O 420.1 5
10-13-95
4.1.3 Implementation
An Implementation Plan describing the process that will ensure that the requirements of this
section will be invoked during the design and construction shall be submitted to the DOE
Cognizant Secretarial Officer or his designee in accordance with section 5. Deviations from
applicable requirements shall be appropriately documented and justified.
4.2. Fire Protection
Section 4
1. The objectives of section 4.2 are to establish requirements for a comprehensive fire and
related hazards protection program for facilities sufficient to minimize the potential for:
(1) the occurrence of a fire or related event; (2) a fire that causes an unacceptable on-site
or off-site release of hazardous or radiological material that will threaten the health and
safety of employees, the public or the environment; (3) vital DOE programs suffering
unacceptable interruptions as a result of fire and related hazards; (4) property losses
from a fire and related events exceeding defined limits established by DOE; and (5)
critical process controls and safety class systems being damaged as a result of a fire and
related events.
2. Section 4.2 of this Order has primacy over all other DOE Orders with respect to matters
concerning fire protection for facilities (refer to DOE 440.1 for worker protection
requirements). To the extent that potential conflicts may arise resulting from the
implementation of these requirements in relation to other DOE Orders or Directives, the
cognizant fire protection Authority Having Jurisdiction (AHJ) within the Office of the
Assistant Secretary for Environment, Safety and Health shall be responsible for
resolving the issue in concert with the other AHJs.
3. DOE facilities, sites and activities (including design and construction) shall be
characterized by a level of fire protection that is sufficient to fulfill the requirements of
the best protected class of industrial risks ("Highly Protected Risk" or "Improved Risk")
and shall be provided protection to achieve "defense-in-depth." This includes meeting
the applicable building code and National Fire Protection Association Codes and
Standards, or exceeding them (when necessary to meet safety objectives), unless an
exemption has been granted. The applicable codes and standards are those in effect
when facility design commences ("code of record"). When significant modifications to
a facility occur, the current edition of the code or standard shall apply to the
modification.
4.2.1 General Programmatic Requirements
DOE Elements and contractors shall develop, implement and maintain an acceptable fire
protection program with the following features:
1. A policy statement that incorporates the requirements of this Section, related DOE
directives, and other applicable Federal, state and local fire protection requirements.
The statement shall affirm management's
CANCELE
D
6 DOE O 420.1
10-13-95
commitment to support a level of fire protection and fire suppression capability
sufficient to minimize losses from fire and related hazards consistent with the best class
of protected property in private industry.
2. Comprehensive, written fire protection criteria that reflect additional site-specific
aspects of the fire protection program, including the organization, training and
responsibilities of the fire protection staff, administrative aspects of the fire protection
program, and requirements for the design, installation, operability, inspection,
maintenance and testing of fire protection systems.
3. Written fire safety procedures governing the use and storage of combustible, flammable,
radioactive, and hazardous materials so as to minimize the risk from fire. Such
procedures shall also exist for fire protection system impairments and for activities such
as smoking, hot work, safe operation of process equipment, and other fire prevention
measures which contribute to the decrease in fire risk.
Section 5
4. A system to ensure that the requirements of the DOE fire protection program are
documented and incorporated in the plans and specifications for all new facilities and
for significant modifications of existing facilities. This includes a documented review
by a qualified fire protection engineer of plans, specifications, procedures, and
acceptance tests.
5. Fire hazards analyses (FHA) for all nuclear facilities, significant new facilities and
facilities that represent unique or significant fire safety risks. The FHA shall be
developed using a graded approach. The conclusions of the FHA shall be incorporated
in the Safety Analysis Report (SAR) Accident Analysis and shall be integrated into
design basis and beyond design basis accident conditions.
6. Access to a qualified and trained fire protection staff, including a fire protection
engineer(s), technicians and fire fighting personnel to implement the requirements of
this Section.
7. A "baseline" needs assessment that establishes the minimum required capabilities of site
fire fighting forces. This includes minimum staffing, apparatus, facilities, equipment,
training, fire pre-plans, off-site assistance requirements, and procedures. Information
from this assessment shall be incorporated into the site Emergency Plan.
8. Written pre-fire strategies, plans, and standard operating procedures to enhance the
effectiveness of site fire fighting forces, where provided. Such procedures include those
governing the use of fire fighting water or other neutron moderating materials to
suppress fire within or adjacent to moderation controlled areas. Restrictions on the use
of water shall be fully justified on the basis of criticality safety.
CANCELE
D
DOE O 420.1 7
10-13-95
9. A comprehensive, documented fire protection self-assessment program, which includes
all aspects (program and facility) of the fire protection program. Assessments shall be
performed on a regular basis at a frequency established by DOE.
10. A program to identify, prioritize and monitor the status of fire protection-related
appraisal findings/recommendations until final resolution is achieved. When final
resolution will be significantly delayed, appropriate interim compensatory measures
shall be implemented to minimize the fire risk.
11. A process for reviewing and recommending approval of fire safety "equivalencies" and
"exemptions" to the DOE Authority Having Jurisdiction for fire safety.
4.2.2 Fire Protection Design Requirements
DOE Elements and contractors shall develop, implement and maintain a comprehensive fire
protection program for facilities that includes:
1. A reliable water supply of adequate capacity for fire suppression.
2. Noncombustible or fire-resistive construction, where appropriate. Complete fire-rated
barriers that are commensurate with the fire hazard to isolate hazardous occupancies and
to minimize fire spread and loss potential consistent with defined limits as established
by DOE.
3. Automatic fire extinguishing systems throughout all significant facilities and in all areas
subject to loss of safety class systems, significant life safety hazards, unacceptable
program interruption, or fire loss potential in excess of defined limits.
4. Redundant fire protection systems in areas where safety class systems are vulnerable to
fire damage and where no redundant safety capability exists outside of the fire area. In
new facilities, redundant safety class systems shall be in separate fire areas. Redundant
fire protection systems shall also be provided in areas where the maximum possible fire
loss (MPFL) exceeds limits established by DOE.
Section 6
5. A means to summon the fire department in the event of a fire, such as a fire alarm
signalling system.
6. A means to notify and evacuate building occupants in the event of a fire, such as a fire
detection or fire alarm system and illuminated, protected egress paths.
7. Physical access and appropriate equipment to facilitate effective intervention by the fire
department, such as an interior standpipe system(s) in multi-story or large facilities with
complex configurations.
CANCELE
D
8 DOE O 420.1
10-13-95
8. A means to prevent the accidental release of significant quantities of contaminated
products of combustion and fire fighting water to the environment, such as ventilation
control and filter systems and curbs and dikes. Such features would only be necessary
if required by the FHA or SAR in conjunction with other facility or site environmental
protection measures.
9. Fire and related hazards that are unique to DOE and are not addressed by industry codes
and standards shall be protected by isolation, segregation or use of special fire control
systems, such as inert gas or explosion suppression, as determined by the FHA.
10. Fire protection systems shall be designed such that their inadvertent operation,
inactivation or failure of structural stability will not result in the loss of vital safety
functions or inoperability of safety class systems as determined by the SAR.
4.3. Nuclear Criticality Safety
DOE Elements shall ensure that a contractor responsible for a DOE non-reactor nuclear
facility shall establish a nuclear criticality safety program that (i) applies to fissionable
materials that are produced, processed, stored, transferred, disposed, or otherwise handled,
and (ii) includes the following elements in paragraphs 4.3.2 and 4.3.3.
4.3.1 Objectives
The objective shall be to establish nuclear criticality safety program requirements to ensure
that:
1. Criticality safety is comprehensively addressed and receives an objective
review, with all identified risks reduced to acceptably low levels and
management authorization of the operation is documented.
2. The public, workers, property, both government and private, the environment,
and essential operations are protected from the effects of a criticality accident.
4.3.2 General Requirements
Operations with fissionable materials which pose a criticality accident hazard shall be
evaluated and documented to demonstrate that the operation will be subcritical under both
normal and credible abnormal conditions. Fissionable material operations shall be conducted
in such a manner that consequences to personnel and property that result from a criticality
accident will be mitigated. No single credible event or failure shall result in a criticality
accident having unmitigated consequences.
CANCELE
D
DOE O 420.1 9
10-13-95
The nuclear criticality safety program shall be evaluated and documented and shall include:
(i) Nuclear criticality safety evaluations for normal and credible abnormal
conditions that document the parameters, limits, and controls required to ensure
that the analyzed conditions are subcritical.
(ii) Implementation of limits and controls identified by the nuclear criticality safety
evaluations.
(iii) Reviews of operations to ascertain that limits and controls are being followed
and that process conditions have not been altered such that the applicability of
the nuclear criticality safety evaluation has been compromised.
Section 7
(iv) Assessment of the need for criticality accident detection devices and alarm
systems, and installation of such equipment where total risk to personnel will
be reduced.
4.3.3 Specific Requirements
Fissionable materials shall be produced, processed, stored, transferred, disposed, or otherwise
handled in such a manner that the probability of a criticality accident is acceptably low, and,
to the extent practical, all persons, all government, public, and private property, and the
environment are protected from damaging effects and undue hazards that may arise from a
criticality accident.
The Contractor Criticality Safety Program for non-reactor nuclear facilities shall
include the following requirements:
a. Contractor Criticality Safety Programs (CCSPs) shall apply to operations
involving fissionable materials that pose a criticality accident hazard.
Fissionable nuclides of concern to this section are listed in Table 4.3-1. The
assignment of nuclides to the three columns in Table 4.3-1 is based on typical
conditions. DOE Elements shall ensure that each contractor organization shall
determine which column is appropriate to the fissionable nuclides existing in its
inventory, whether listed in this table or not expressly included. Specific
technical information concerning differences in behavior of these nuclides
relevant to their differing abilities to support a self-sustaining nuclear chain
reaction may be found in ANSI/ANS-8.1-1983,R88 and ANSI/ANS-8.15-
1981,R87.
CANCELE
D
10 DOE O 420.1
10-13-95
Table 4.3-1. Fissionable Nuclides of Criticality Concern
Nuclide Nuclide Nuclide
92U233* 93Np237 91Pa231**
92U235* 94Pu238 92U232**
94Pu239* 94Pu240 92U234**
94Pu241 96Cm246**
94Pu242 98Cf250**
95Am241 98Cf252**
95Am242m 99Es254**
95Am243
96Cm243
96Cm244
96Cm245
96Cm247
98Cf249
98Cf251
* existing in quantities and forms that lead to the major focus of nuclear
criticality safety
** existing in isolated quantities less than potential minimum critical mass
(per ANSI/ANS-8.15-1981,R87, "Nuclear Criticality Control of Special
Actinide Elements")
b. The basic elements and control parameters of programs for nuclear criticality
safety shall satisfy the requirements of the following American Nuclear
Society's ANSI/ANS nuclear criticality safety standards:
ANSI/ANS-8.1-1983,R88, "Nuclear Criticality Safety in Operations
with Fissionable Materials Outside Reactors," however paragraphs 4.2.2
and 4.2.3, and paragraph 3.3 shall be followed as modified in section
4.3.3.d of this Order;
ANSI/ANS-8.3-1986, "Criticality Accident Alarm System," however
paragraphs 4.1.2, 4.2.1 and 4.2.2 shall be followed as modified in
section 4.3.3.c and e of this Order;
ANSI/ANS-8.5-1986, "Use of Borosilicate-Glass Raschig Rings as a
Neutron Absorber in Solutions of Fissile Material";
ANSI/ANS-8.6-1983,R88, "Safety in Conducting Subcritical Neutron-
Multiplication Measurements in Situ," however paragraph 5.3 shall be
followed as modified in section 4.3.3.f of this Order;
CANCELE
D
DOE O 420.1 11
10-13-95
ANSI/ANS-8.7-1975,R87, "Guide for Nuclear Criticality Safety in the
Storage of Fissile Materials," however paragraph 5.2 shall be followed
as modified by section 4.3.3.c of this Order.
ANSI/ANS-8.9-1987, "Nuclear Criticality Safety Criteria for Steel-Pipe
Intersections Containing Aqueous Solutions of Fissile Materials";
ANSI/ANS-8.10-1983,R88, "Criteria for Nuclear Criticality Safety
Controls in Operations with Shielding and Confinement";
Section 8
ANSI/ANS-8.12-1987,R93, "Nuclear Criticality Control and Safety of
Plutonium-Uranium Fuel Mixtures Outside Reactors";
ANSI/ANS-8.15-1981,R87, "Nuclear Criticality Control of Special
Actinide Elements";
ANSI/ANS-8.17-1984,R89, "Criticality Safety Criteria for the Handling,
Storage, and Transportation of LWR Fuel Outside Reactors," however
paragraph 4.3 shall be followed as modified in section 4.3.3.g of this
Order;
ANSI/ANS-8.19-1984,R89, "Administrative Practices for Nuclear
Criticality Safety;"
ANSI/ANS-8.21-1995, "Use of Fixed Neutron Absorbers in Nuclear
Facilities Outside Reactors."
Revisions to any of the ANSI/ANS standards listed above will place this
Section under immediate review by DOE. Revised ANSI standards shall not be
used unless an exemption is granted or it is incorporated into a DOE Order.
c. All recommendations in the ANSI/ANS standards listed in paragraph 4.3.3.b
shall be addressed. When recommendations are not implemented, justification
shall be documented in a manner described in the Implementation Plan .
Two ANSI/ANS recommendations shall be requirements:
ANSI/ANS-8.3-1986, paragraph 4.1.2, the second sentence of which
becomes, for this Order, "Where alarm systems are installed, emergency
plans shall be maintained."
ANSI/ANS-8.7-1975,R87, paragraph 5.2, the last sentence of which
becomes, for this Order, "The effects of more significant moderation
shall be evaluated."
CANCELE
D
12 DOE O 420.1
10-13-95
d. For DOE application, the following sections of ANSI/ANS-8.1-1983,R88,
"Nuclear Criticality Safety in Operations with Fissionable Materials Outside
Reactors," shall be read as follows:
(1) Application of Double Contingency (paragraph 4.2.2, Double
Contingency). Process designs shall incorporate sufficient factors of
safety to require at least two unlikely, independent, and concurrent
changes in process conditions before a criticality accident is possible.
Protection shall be provided by either (i) the control of two independent
process parameters (which is the preferred approach, when practical, to
prevent common-mode failure), or (ii) a system of multiple controls on
a single process parameter. The number of controls required upon a
single controlled process parameter shall be based upon control
reliability and any features that mitigate the consequences of control
failure. In all cases, no single credible event or failure shall result in the
potential for a criticality accident, except as referenced in the paragraph
that follows.
An exception to the application of double contingency, where single
contingency operations are permissible, is presented in paragraph 5.1 of
ANSI/ANS-8.10-1983,R88. This exception applies to operations with
shielding and confinement (e.g., hot cells or other shielded facilities).
Double contingency shall be demonstrated by documented evaluations.
(2) Application of Geometry Control (paragraph 4.2.3, Geometry Control).
Where a significant quantity of fissionable material is being processed
and criticality safety is a concern, passive engineered controls such as
geometry control shall be considered as a preferred control method.
Where passive engineered control is not feasible, the preferred Order of
controls is: active engineered controls, followed by administrative
controls. The double contingency analysis shall justify the chosen
controls. Full advantage may be taken of any nuclear characteristics of
the process materials and equipment. All dimensions, nuclear
properties, and other features upon which reliance is placed shall be
documented and verified prior to beginning operations, and control shall
be exercised to maintain them.
Section 9
(3) Application of Definition of "Bias" (paragraph 3.3, Glossary of Terms).
The uncertainty in the bias is interpreted as a measure of both the
accuracy of the calculation and the precision of the experimental data.
It is assumed also to include (a) the precision of the calculation if the
calculation is stochastic (notwithstanding that such
CANCELE
D
DOE O 420.1 13
10-13-95
precision often can be made as great as desired), and (b) the accuracy of
the experimental data if the experiment is a mock-up of a referenced
system.
Deterministic computer calculations are assumed to have very high
precision, or should be made to have very high precision. Stochastic
computer calculations should be forced to have appropriately high
precision. An experiment that is not a mock-up is exactly accurate by
definition.
e. The requirements in ANSI/ANS-8.3-1986 relating to the needs for an alarm
system (paragraphs 4.2.1 and 4.2.2), are not applicable to this Order. For the
purpose of this Order, Criticality Accident Alarm Systems (CAS) and
Criticality Detection Systems (CDS) shall be required as follows:
In what follows, 10 per year is used as a measure of credibility, and does not-6
mean that a probabilistic risk assessment (PRA) has to be performed.
Reasonable grounds for incredibility may be presented on the basis of commonly
accepted engineering judgment.
(1) In those facilities where the mass of fissionable material exceeds the
limits established in paragraph 4.2.1 of ANSI/ANS-8.3-1986 and the
probability of a criticality accident is greater than 10 per year (as-6
documented in a DOE-approved Safety Analysis Report (SAR) or in the
supporting analysis for an SAR), a CAS conforming to ANSI/ANS-8.3-
1986 shall be provided to cover occupied areas in which the expected
dose exceeds 12 rads in free air, where a CAS is defined to include a
criticality accident detection device and a personnel evacuation alarm.
(2) In those facilities where the mass of fissionable material exceeds the
limits established in paragraph 4.2.1 of ANSI/ANS-8.3-1986 and the
probability of a criticality accident is greater than 10 per year, (as-6
documented in a DOE-approved SAR or in the supporting analysis for
an SAR), but there are no occupied areas in which the expected dose
exceeds 12 rads in free air, a CDS shall be provided, where a CDS is
defined to be an appropriate criticality accident detection device but
without an immediate evacuation alarm. The CDS response time should
be sufficient to allow for appropriate process-related mitigation and
recovery actions. DOE Elements shall ensure that appropriate response
guidance to minimize personnel exposure shall be provided by the
contractor.
(3) In those facilities where the mass of fissionable material exceeds the
limits established in paragraph 4.2.1 of ANSI/ANS-8.3-1986, but a
criticality accident is determined to be impossible due to the physical
form of the fissionable material, or the probability of occurrence is
determined to
CANCELE
D
14 DOE O 420.1
10-13-95
be less than 10 per year (as documented in a DOE-approved SAR or in-6
the supporting analysis for an SAR, or in other appropriate
documentation), neither a CAS nor a CDS is required.
Neither a CAS nor a CDS is required for fissionable material during
shipment when packaged in approved shipping containers, or when
packaged in approved shipping containers awaiting transport provided
that no other operation involving fissionable material not so packaged is
permitted on the shipping dock or in the shipment area.
Section 10
(4) If a criticality accident is possible wherein a slow (i.e., quasistatic)
increase in reactivity could occur leading from subcriticality to
supercriticality to self-shutdown without setting off emplaced criticality
alarms, then a CAS might not be adequate for protection against the
consequences of such an accident.
To aid in protecting workers against the consequences of slow criticality
accidents in facilities where analysis has shown that slow criticality
accidents are credible, CASs should be supplemented by warning
devices such as audible personnel dosimeters (e.g., pocket
chirpers/flashers, or their equivalents), area radiation monitors, area
dosimeters, or integrating CASs. If these devices are used solely as
criticality warning devices in accordance with this Section, they shall be
exempt from the calibration requirement of DOE Order 5480.11
(Radiation Protection for Occupational Workers, 12-21-88).
(5) Neither a CAS nor a CDS is required to be installed for handling or
storage of fissionable material when sufficient shielding exists that is
adequate to protect personnel (e.g., spent fuel pools, hot cells, or burial
grounds); however a means to detect fission product gasses or other
volatile fission products should be provided in occupied areas
immediately adjacent to such shielded areas, except for systems where
no fission products are likely to be released.
f. For DOE application, in section 5.3 of ANSI/ANS-8.6-1983,R88, "Safety in
Conducting Subcritical Neutron-Multiplication Measurements in Situ," "i.e."
should be read as "e.g."
g. For DOE application, in section 4.3 of ANSI/ANS-8.17-1984,R89, "Criticality
Safety Criteria for the Handling, Storage, and Transportation of LWR Fuel
Outside Reactors," the guidance on alarm systems is specifically modified in
this Order.
CANCELE
D
DOE O 420.1 15
10-13-95
h. It is acceptable to DOE to follow DOE-STD-3007-93 (Guidelines for Preparing
Criticality Safety Evaluations at Department of Energy non-Reactor Nuclear
Facilities) when preparing Criticality Safety Evaluations.
For DOE application, the following sections of DOE-STD-3007-93 shall be
read as follows:
(1) II. DEFINITIONS. The definition of "BIAS" should be interpreted as
discussed in paragraph 4.3.3.d.(3).
(2) 4.0 METHODOLOGY. When computer neutronics calculations are
used, the type of computing platform should be stated along with
relevant code configuration control information and code development
and user documentation.
i. DOE Elements shall ensure that the contractor shall have a program to detect
inadvertent accumulation of significant quantities of fissionable material.
j. Transportation Requirements for Fissionable Material.
(1) The requirements of this Section shall apply to all activities where
fissionable material is transferred from one operation to another within a
facility and from one on-site location to another.
(2) The requirements of DOE O 460.1 (Packaging and Transportation
Safety, 9-27-95) shall be complied with regarding off-site shipment of
fissionable material.
DOE O 460.1 (Packaging and Transportation Safety, 9-27-95) shall
apply to the safe transportation of weapon components and special
assemblies shipped in national defense.
k. Guidelines for Fire Fighting
The fire protection program (Section 4.2.1) shall establish guidelines for fire
fighting within, or adjacent to, moderation controlled areas. These guidelines
shall be based on comparisons of risks and consequences of a criticality
accident with the risks and consequences of postulated fires for the respective
area(s). Risk and consequence comparisons may be a qualitative evaluation.
The basis for the guidelines shall be documented.
Section 11
4.4. Natural Phenomena Hazards Mitigation
The objectives of this section are to ensure that all DOE facilities are designed, constructed,
and operated so that the general public, workers, and the environment are protected from the
impact of Natural Phenomena Hazards
CANCELE
D
16 DOE O 420.1
10-13-95
(NPHs).The provisions of this section apply to DOE sites and facilities. The provisions of this
section cover all natural phenomena hazards such as seismic, wind, flood, lightning. Where
no specific requirements are specified, model building codes or national consensus industry
standards shall be used.
4.4.1 General Requirements
For hazardous facilities, safety analyses shall include the ability of Systems, Structures,
Components (SSCs) and personnel to perform their intended safety functions under the effects
of natural phenomena.
4.4.2 Natural Phenomena Mitigation Design Requirements
Systems, structures and components shall be designed, constructed and operated to withstand
the effects of natural phenomena as necessary to ensure the confinement of hazardous
material, the operation of essential facilities, the protection of government property, and the
protection of life safety for occupants of DOE buildings. The design process shall consider
potential damage and failure of systems, structures and components due to both direct and
indirect natural phenomena effects, including common cause effects and interactions from
failures of other systems, structures and components. Furthermore, the seismic requirements
of Executive Order 12699 shall be addressed.
Systems, structures and components for new DOE facilities, and additions or major
modifications to existing systems, structures and components shall be designed, constructed
and operated to meet the requirements in the previous paragraph. Any additions and
modifications to existing DOE facilities shall not degrade the performance of existing
systems, structures and components to the extent that the objectives in this Section cannot be
achieved under the effects of natural phenomena.
4.4.3 Evaluation and Upgrade of Existing DOE Facilities
Systems, structures and components in existing DOE facilities shall be evaluated in
accordance with Section 4.4.2 when there is a significant degradation in the safety basis for
the facility. Furthermore, the seismic requirements of Executive Order 12941 shall be
addressed.
If any of the conditions above are satisfied then the contractor/operator shall establish a plan
for evaluating the affected systems, structures and components. The plan shall incorporate a
schedule for evaluation taking into account programmatic mission considerations and the
safety significance of the potential failure of systems, structures and components due to
natural phenomena.
If the evaluation of existing systems, structures and components identifies natural phenomena
mitigation deficiencies, the contractor/operator shall establish an upgrade plan for the affected
systems, structures and components.
CANCELE
D
DOE O 420.1 17
10-13-95
The upgrade plan shall incorporate a prioritized schedule for upgrading the systems,
structures and components. The upgrade plan shall address possible time or funding
constraints as well as programmatic mission considerations.
4.4.4 Natural Phenomena Hazards Assessment
Section 12
The design and evaluation of facilities to withstand natural phenomena shall be based on an
assessment of the likelihood of future natural phenomena occurrences. The natural
phenomena hazards assessment shall be conducted commensurate with a graded approach and
commensurate with the potential hazard of the facility.
For new Sites; natural phenomena hazards assessment shall be conducted commensurate with
a graded approach to the facility. Site planning shall consider the consequences of all types of
natural phenomena hazards.
For existing Sites; if there are significant changes in natural phenomena hazards assessment
methodology or site-specific information, the natural phenomena hazards assessments shall be
reviewed and shall be updated, as necessary. A review of the natural phenomena hazards
assessment shall be conducted at least every 10 years. The review shall include
recommendations to DOE on the need for updating the existing natural phenomena hazards
assessments based on identification of any significant changes in methods or data.
4.4.5 Natural Phenomena Detection
Facilities or sites with hazardous materials shall have instrumentation or other means to detect
and record the occurrence and severity of seismic events.
4.4.6 Post-Natural Phenomena Procedures
Facilities or sites with hazardous materials shall have procedures that include, inspecting the
facility for damage caused by severe natural phenomena, and placing the facility into a safe
configuration when such damage has occurred.
5. RESPONSIBILITIES.
a. Secretary of Energy: The Secretary of Energy retains sole and final authority
to determine what acts are necessary to comply with this Order. Further, the
Secretary retains the authority to suspend any or all requirements under this
Order whenever the Secretary deems it necessary. This authority may be
delegated by the Secretary.
b. Assistant Secretary for Environment, Safety and Health: The Assistant
Secretary for Environment, Safety and Health is responsible for development,
promulgation, and maintaining the
CANCELE
D
18 DOE O 420.1
10-13-95
policy, requirements, guidance, and technical standards, and providing advice
and assistance, as requested, concerning implementation of DOE safety policy
as it relates to this Order at DOE facilities; and for monitoring and reviewing
the implementation of all aspects of this Order, including field organizations
and contractor performance.
c. Cognizant Secretarial Officers: Cognizant Secretarial Officers or designees for
facilities or planned facilities under their programmatic responsibilities shall
ensure that all programs comply with requirements falling within the scope of
this Order, shall review and approve Implementation Plans submitted to
implement the Order, and shall review and approve requests for exemptions.
d. Heads of Field Organizations: As directed by the CSO, shall ensure that the
requirements falling within the scope of this Order are in compliance with this
Order.
Field Elements are responsible for determining whether adequate protection
can most effectively be achieved by continuing to operate under the terms of
existing contracts requiring compliance with old Orders or by modifying the
contract to incorporate the requirements of revised.
Field Elements are responsible for determining that implementation of new rule
or Order requirements will provide adequate protection prior to requesting
contract modification to drop old Order requirements from contract.
Section 13
e. Heads of DOE Elements: Heads of DOE elements shall ensure that initiators of
procurement requests shall identify in procurement requests if the requirements
in the Contractor Requirements Document for this Order are to be applied to
the award or subawards resulting from the procurement request.
f. Contractor Organizations: As directed by the CSO or the Heads of Field
Organizations and as directed by the Contracting Officer, contractors (including
subcontractors) shall develop, implement, and maintain the policies, objectives,
and requirements of the CRD of this Order.
6. CONTACT: Office of Environment, Safety and Health; Office of Nuclear Safety
Policy and Standards; Office of Occupational Safety and Health Policy.
CANCELE
D
DOE O 420.1 19 (and 20)
10-13-95
7. IMPLEMENTATION PLANS. Contractors shall submit an Implementation Plan to
DOE to implement the requirements of this Order. The Implementation Plan shall be
submitted after this Order is incorporated into applicable contracts and shall be
developed with an integrated safety review process commensurate with the hazards.
BY ORDER OF THE SECRETARY OF ENERGY:
ARCHER L. DURHAM
Assistant Secretary for
Human Resources and Administration
CANCELE
D
DOE O 420.1 Attachment 1
10-13-95 Page 1 (and 2)
TABLE 1
FACILITY AND ACTIVITY APPLICABILITY
WEAPONS FACILITIES
Section New
NUC
New
NON
EXISTING
NUC
EXISTING
NON
MODS
NUC
MODS
NON
ACC &
FUSION
NEW EXISTING MODS ACTIVITI
ES (NOTE
3)
4.0 YES YES YES YES YES YES NOTE 2 YES NO YES NO
4.1 YES NOTE 1 NOTE 1 NOTE 1 YES YES YES YES NO YES NO
4.2 YES YES YES YES YES YES YES YES YES YES NO
4.3 YES NO YES NO YES NO NO YES YES YES NO
4.4 YES YES YES YES YES YES YES YES YES YES NO
Note 1: Refer to each section
Note 2: See Orders and Standards on Accelerators and Fusion Facilities
Note 3: Activities within weapons facilities relating to the prevention of accidental or
unauthorized nuclear detonations are subject to the 5600 series of DOE Orders
NUC = Nuclear facility categorized as Hazard Category 1, 2, or 3
NON = All other facilities
CANCELE