DOE G 441.1-1C Chg 1 (Admin Chg), Radiation Protection Programs Guide for Use with Title 10, Code of Federal Regulations, Part 835, Occupational Radiation Protection
Functional areas: Administrative Change, Defense Nuclear Facility Safety and Health Requirement, Packaging and Transportation, Radiation Protection
Provides guidance for implementing the provisions of the functional areas contained in 10 CFR 835. The revision to the guide reflects changes in the June 2007 amendment to 10 CFR 835, Worker Safety and Health Program.
Admin Chg 1, dated 7-8-11, cancels DOE G 441.1-1C.
Version history and related documents
Supersedes
Earlier documents this one replaced.
Document text
Text extracted from the attached file. Refer to the original document for the authoritative version.
Section 1
AVAILABLE ONLINE AT: INITIATED BY:
www.directives.doe.gov Office of Health, Safety and Security
DOE G 441.1-1C
05-19-08
Chg 1
07-08-11
RADIATION PROTECTION PROGRAMS GUIDE
for Use with
Title 10, Code of Federal Regulations, Part 835,
Occupational Radiation Protection
[This Guide describes nonmandatory approaches for meeting requirements. Guides are not
requirements documents and are not to be construed as requirements in any audit or appraisal for
compliance with the parent Rule, Policy, Order, Notice, or Manual.]
Department of Energy
Office of Health, Safety and Security
DOE G 441.1-1C i
5-19-08
TABLE OF CONTENTS
RADIATION PROTECTION PROGRAMS .............................................................. 1
1.0 PURPOSE AND APPLICABILITY ...................................................................... 1
1.1 USE OF CONSENSUS STANDARDS ...................................................... 2
1.2 ACRONYMS .............................................................................................. 3
2.0 DEFINITIONS ......................................................................................................... 6
3.0 RADIATION PROTECTION PROGRAMS ...................................................... 16
3.1 Implementation Guidance ......................................................................... 17
3.2 Organization and Administration .............................................................. 18
3.2.0 Administrative Processes .............................................................. 19
3.2.1 Radiological Control Organization ............................................... 20
3.2.2 Education, Training, and Skills ..................................................... 20
3.2.3 Internal Audit and Self Assessment .............................................. 22
3.2.4Radioactive Material Transportation Exclusion................................23
3.3 RPP Functional Elements ......................................................................... 24
Appendix 3.A Preparation, Review, and Approval of RPPs.................................. 26
4.0 ALARA ................................................................................................................... 39
4.1 Implementation Guidance ......................................................................... 39
4.2 ALARA Programs .................................................................................... 40
4.2.0 Formal Plans and Measures .......................................................... 40
4.2.1 Policy and Management Commitment.......................................... 41
4.2.2 ALARA Training .......................................................................... 41
4.2.3 Plans and Procedures .................................................................... 42
4.2.4 Internal Assessments/Audits ......................................................... 42
4.2.5 ALARA Design Review ............................................................... 42
4.2.6 Radiological Work/Experiment Administration and Planning ..... 46
4.2.6.0 Job/Task/Experiment Reviews....................................... 46
4.2.6.1 Consideration of Non-radiological Hazards .................. 47
4.3 Records ..................................................................................................... 48
Section 2
5.0 INTERNAL DOSIMETRY PROGRAM ............................................................. 49
5.1 Implementation Guidance ......................................................................... 50
5.2 Program Management and Administration ............................................... 51
5.2.0 General Requirements ................................................................... 52
5.2.1 Organization, Staffing, and Facilities ........................................... 52
5.2.1.0 Organization ................................................................... 52
5.2.1.1 Staffing ........................................................................... 53
5.2.1.2 Facilities and Resources ................................................. 53
5.2.2 Technical Basis Document ............................................................ 53
5.2.3 Internal Dosimetry Procedures Manual ........................................ 54
5.2.4 Quality Assurance ......................................................................... 54
5.3 Air Monitoring and Contamination Control Programs ............................. 54
5.3.0 Air Monitoring When There
Is No Practical Radiobioassay Method... ...................................... 55
5.3.1 Recourse for Technology Shortfall (DIL<MDA) ......................... 55
DOE G 441.1-1C ii
5-19-08
5.4 Individual Monitoring Program ................................................................ 56
5.4.0 Establishing the Need for Individual Monitoring ......................... 56
5.4.1 Investigation Levels/Derived Investigation Levels ...................... 57
5.4.2 Minimum Detectable Amount (MDA).......................................... 57
5.4.3 Frequency of Measurement........................................................... 58
5.4.4 Detection and Confirmation of Intakes ......................................... 58
5.4.5 Internal Dose Management ........................................................... 59
5.4.6 Planned Special Exposures ........................................................... 59
5.4.7 Medical Response ......................................................................... 60
5.5 Internal Dose Evaluation........................................................................... 60
5.5.0 Required Dose Calculations .......................................................... 60
5.5.1 Interpretation of Radiobioassay Data ............................................ 61
5.5.2 Evaluation of Internal Dose from Radiobioassay and Air
Monitoring Data ............................................................................ 61
5.5.3 Periodic Reevaluation of Internal Dose ........................................ 61
5.6 Recordkeeping and Reporting................................................................... 62
6.0 EXTERNAL DOSIMETRY PROGRAM............................................................ 65
6.1 Implementation Guidance ......................................................................... 67
6.2 Program Management and Administration ............................................... 68
6.2.0 General Requirements ................................................................... 68
6.2.1 Organization, Staffing, And Facilities .......................................... 69
6.2.1.0 Organization ................................................................... 69
6.2.1.1 Staffing ........................................................................... 69
Section 3
6.2.1.2 Facilities and Resources ................................................. 70
6.2.2 Technical Basis Document ............................................................ 70
6.2.3 Procedures ..................................................................................... 71
6.2.4 Quality Assurance ......................................................................... 71
6.3 Area Monitoring Program ......................................................................... 71
6.3.0 Monitoring Instruments and Devices ............................................ 72
6.3.1 Performance of Area Radiation Monitoring ................................. 72
6.3.2 Allowance for Physical Characteristics ........................................ 73
6.3.3 Recourse for Technology Shortfall ............................................... 73
6.4 Individual Monitoring Program ................................................................ 73
6.4.0 Establishing the Need for Individual Monitoring ......................... 73
6.4.1 Routine Monitoring of Individual External Doses........................ 75
6.4.1.0 Whole Body Monitoring ................................................... 76
6.4.1.1 Lens of the Eye Monitoring .............................................. 76
6.4.1.2 Skin and Extremity Monitoring ....................................... 77
6.4.1.3 Embryo/Fetal Monitoring ................................................. 77
6.4.1.4 Non-Uniform Radiation Fields ......................................... 77
6.4.1.5 Supplemental Dosimeters ................................................. 78
6.4.2 Lost, Damaged, or Contaminated Dosimeters .............................. 79
6.4.3 Nuclear Accident Dosimetry ......................................................... 79
6.4.4 Planned Special Exposures ........................................................... 80
6.4.5 Personal Protective Equipment ..................................................... 80
DOE G 441.1-1C iii
5-19-08
6.5 External Dose Evaluation ......................................................................... 80
6.5.0 Required Dose Calculations .......................................................... 80
6.5.1 Special Considerations .................................................................. 82
6.6 Recordkeeping and Reporting................................................................... 83
7.0 RADIATION GENERATING DEVICES ........................................................... 85
7.1 Implementation Guidance ......................................................................... 85
7.2 Administrative Organization and Controls ............................................... 86
7.2.0 Contractor Management................................................................ 86
7.2.1 RGD Custodian ............................................................................. 86
7.2.2 RGD Operator ............................................................................... 87
7.2.3 Qualified Expert ............................................................................ 87
7.2.4 Radiological Control Manager ...................................................... 88
7.2.5 Radiological Control Organization ............................................... 88
7.3 Development of Site-Specific Documents ................................................ 89
7.3.0 Radiological Monitoring ............................................................... 89
Section 4
7.3.1 Sealed Radioactive Source Leak Testing ...................................... 90
7.3.2 Area Posting .................................................................................. 90
7.3.2.0 Radiological Conditions................................................. 90
7.3.2.1 Operational Status .......................................................... 90
7.3.2.2 Maintenance Status ........................................................... 91
7.3.3 Training .........................................................................................92
7.3.4 Records 92
7.4 Engineered Safety Controls ...................................................................... 92
7.4.0 Shielding, Controls, & Safety Devices ......................................... 92
7.4.0.0 Shielding ........................................................................... 93
7.4.0.1 Access Control and Safety Devices ............................... 93
7.4.0.2 Interlocks........................................................................... 94
7.4.0.3 Device Controls ................................................................ 95
7.4.0.4 Run-Safe and Emergency Shutdown Devices ............... 95
7.4.0.5 Monitoring Instruments .................................................... 96
7.4.1 Guidance for Specific RGD Installations ..................................... 96
7.4.1.0 Accelerators ................................................................... 96
7.4.1.1 Electron Devices that Generate X-Rays Incidentally ....... 96
7.4.1.2 Cabinet X-Ray Systems ................................................. 97
8.0 EVALUATION AND CONTROL OF RADIATION DOSE TO THE
EMBRYO/FETUS.................................................................................................. 98
8.1 Implementation Guidance ......................................................................... 98
8.2 Declaration of Pregnancy/Withdrawal of Declaration .............................. 98
8.3 Work Restrictions Following Declarations of Pregnancy ........................ 99
8.4 Counseling .............................................................................................. 101
8.5 Dose Determination and Monitoring Methods ....................................... 101
8.5.0 Dose Determination .................................................................... 101
8.5.1 Monitoring Methods ................................................................... 103
8.6 Training ................................................................................................... 103
8.7 Record -Keeping and Reporting ............................................................. 103
DOE G 441.1-1C iv
5-19-08
Appendix 8.A Declaration of Pregnancy Form ............... ……………………….104
Appendix 8.B Withdrawal of Pregnancy Declaration Form .................................. 105
Appendix 8.C Embryo/Fetal Equivalent Dose Record Form ................................ 106
9.0 PORTABLE MONITORING INSTRUMENT CALIBRATION ................... 107
9.1 Implementation Guidance ....................................................................... 108
9.2 Instrument Selection ............................................................................... 108
9.2.0 Type Testing ............................................................................... 109
9.2.1 Acceptance Testing ..................................................................... 109
Section 5
9.3 Instrument Calibration ............................................................................ 109
9.4 Operability Tests ..................................................................................... 110
9.5 Maintenance ............................................................................................ 110
9.6 Calibration Equipment/Calibration Quality ............................................ 110
9.7 Laboratory Documentation ..................................................................... 111
9.7.0 Laboratory Protocol .................................................................... 111
9.7.1 Laboratory Records ..................................................................... 111
9.7.2 Instrument Calibration Records .................................................. 111
9.7.3 Instrument Location .................................................................... 112
9.8 Laboratory and Staff ............................................................................... 112
9.8.0 Laboratory ................................................................................... 112
98.1 Calibration Staff Qualifications .................................................. 112
9.8.2 Calibration Staff Training ........................................................... 113
9.9 Assessments ............................................................................................ 113
10.0 AIR MONITORING ............................................................................................ 114
10.1 Implementation Guidance ....................................................................... 114
10.2 Determining the Needs for Air Monitoring ............................................ 115
10.2.0 Exposure Assessment.................................................................. 116
10.2.0.0 Type and Frequency of Bioassay ............................. 116
10.2.0.1 Estimation of Dose ................................................... 117
10.2.1 Personnel Protection ................................................................... 118
10.2.1.0 Need for Posting .......................................................... 118
10.2.1.1 Effectiveness of Engineered Controls ...................... 118
10.2.1.2 Proper Respiratory Protective Equipment ............... 118
10.2.2 Early Warning ............................................................................. 119
10.3 Placement of Air Sampling and Real-Time
Air Monitoring Equipment ..................................................................... 120
10.3.0 Locations of Release Points and Individuals .............................. 120
10.3.1 Purpose of Sample ...................................................................... 121
10.3.2 Room Air Flow Patterns ............................................................. 121
10.4 Air Sampling Equipment……………… ....... ………………………… 122
10.4.0 Breathing Zone Air Monitoring .................................................. 122
10.4.1 Source-Specific Air Sampling .................................................... 122
10.4.2 Grab Sampling ............................................................................ 123
10.4.3 Operability Checks...................................................................... 123
10.5 Real-Time Air Monitoring Equipment ................................................... 123
Section 6
10.5.0 Instrument Selection ................................................................... 123
DOE G 441.1-1C v
5-19-08
10.5.1 Alarm Set Points ......................................................................... 124
10.5.2 Alarm Capabilities ...................................................................... 124
10.5.3 Operability Checks...................................................................... 124
10.6 Sample Analysis and Data Review ......................................................... 125
10.7 Quality Control and Quality Assurance .................................................. 125
10.7.0 Sample Identification, Handling, and Storage ............................ 126
10.7.1 Air Sampling and Real-Time Air Monitoring Equipment .......... 126
10.7.2 Counting Room Equipment ........................................................ 127
10.7.3 Audits.... ………………………....... …………………………...127
10.7.4 Recordkeeping ............................................................................ 127
10.8 Administrative Controls .......................................................................... 127
10.8.0 Technical Basis Document ......................................................... 127
10.8.1 Written Procedures...................................................................... 128
11.0 RADIOACTIVE CONTAMINATION CONTROL ......................................... 129
11.1 Implementation Guidance ....................................................................... 130
11.2 Contamination Control Program Management ....................................... 130
11.3 Engineered Controls................................................................................ 131
11.4 Administrative Control ........................................................................... 133
11.4.0 Work Authorizations ................................................................... 133
11.4.1 Access Control ............................................................................ 134
11.4.1.0 Entry Controls .......................................................... 134
11.4.1.1 Egress Controls ........................................................ 135
11.4.1.2 Posting and Labeling................................................ 136
11.4.2 Areas of Fixed Contamination .................................................... 136
11.4.3 Conduct of Radiological Work ................................................... 137
11.4.4 Personnel and Material Decontamination ................................... 137
11.4.4.0 Skin and Clothing Contamination ............................ 137
11.4.4.1 Wound Contamination ............................................. 138
11.4.4.2 Material and Area Decontamination ........................ 138
11.5 Contamination Monitoring...................................................................... 138
11.5.0 Contamination Control Values ................................................... 139
11.5.1 Monitoring .................................................................................. 140
11.5.2 Control of Material and Equipment ............................................ 142
11.5.3 Portal Monitors, Laundry Monitors, and Tool Monitors ............ 145
12.0 POSTING AND LABELING FOR RADIOLOGICAL CONTROL .............. 146
12.1 Implementation Guidance ....................................................................... 146
Section 7
12.2 General .................................................................................................... 146
12.2.0 Design...... ................ ...................................................................148
12.2.1 Content.. ...... ……………………………………………………148
12.2.2 Visibility ..................................................................................... 149
12.2.3 Conditions ................................................................................... 150
12.2.4 Accessibility ................................................................................ 150
12.2.5 Boundaries and Barriers .............................................................. 152
12.3 Controlled Areas ..................................................................................... 152
12.4 Posting for Control of Exposure to External Radiation .......................... 152
DOE G 441.1-1C vi
5-19-08
12.5 Posting for Control of Contamination..................................................... 153
12.5.0 Removable and Airborne Radioactive Contamination ............... 153
12.5.1 Areas of Fixed Contamination .................................................... 154
12.6 Radioactive Material Posting .................................................................. 154
12.7 Exceptions from Posting Requirements .................................................. 156
12.8 Radioactive Material Labeling ................................................................ 157
12.8.0 Radioactive Material Labeling .................................................... 157
12.8.1 Exceptions from Labeling Requirements .................................... 158
Appendix 12.A – Standard Radiation Warning Trefoil ......................................... 160
13.0 OCCUPATIONAL RADIATION PROTECTION
RECORD-KEEPING AND REPORTING....................................................... 161
13.1 Implementation Guidance ....................................................................... 161
13.2 Records to be Generated and Maintained ............................................... 162
13.2.0 Individual Monitoring and Dose Records ................................... 162
13.2.0.0 Internal Doses .......................................................... 163
13.2.0.1 External Doses ......................................................... 165
13.2.0.2 Summation of Internal and External Doses ............. 165
13.2.0.3 Lifetime Occupational Dose .................................... 166
13.2.0.4 Non-Uniform Exposure to the Skin ......................... 167
13.2.0.5 Planned Special Exposures (PSEs) .......................... 168
13.2.0.6 Doses Resulting from Emergency
or Accidental Exposures .......................................... 168
13.2.0.7 Records of Embryo/Fetus Dose
and Declared Pregnant Workers .............................. 169
13.2.0.8 Individual Monitoring Program Records ................. 169
13.2.0.9 Equipment Capabilities ............................................ 170
13.2.1 Monitoring and Workplace Records ........................................... 170
13.2.1.1 Work Authorizations ................................................ 172
13.2.1.2 Area and Material/Equipment
Monitoring Records ................................................. 172
13.2.1.3 Airborne Radioactivity Monitoring Records ........... 173
13.2.1.4 Records of Releases of Materials
Section 8
and Equipment from Radiological Areas ................. 174
13.2.2 Administrative Records .............................................................. 174
13.2.2.0 Radiation Safety Training ........................................ 174
13.2.2.1 ALARA Records ...................................................... 176
13.2.2.2 Facility Design ......................................................... 177
13.2.2.3 Entry and Access Control Records .......................... 177
13.2.2.4 Sealed Radioactive Sources ..................................... 177
13.2.2.5 Radiation Protection Program, Policies and
Procedures.. .................................................. ............178
13.2.2.6 Audits and Programmatic Reviews .......................... 178
13.2.2.7 Posting and Labeling................................................ 178
DOE G 441.1-1C vii
5-19-08
13.2.2.8 Calibration, Functional Tests, and Maintenance
Records .................................................................... 179
13.3 Reports .................................................................................................... 179
13.3.0 Reports to Individuals ................................................................. 179
13.3.0.0 Records Requested by Monitored Individuals ......... 180
13.3.0.1 Termination Dose Reports ....................................... 180
13.3.0.2 Reports to DOE ........................................................ 181
13.3.1 Reports of Planned Special Exposures ....................................... 181
13.4 Privacy Act Considerations..................................................................... 181
13.4.0 Informing Individuals ................................................................. 182
13.4.1 Identifying Individuals ................................................................ 182
13.4.2 Requesting Correction or Amendment of a Record .................... 182
13.4.3 Responding to Requests .............................................................. 182
13.4.4 Accounting for Disclosures......................................................... 182
13.5 Record – Keeping Standards ................................................................... 183
14.0 RADIATION SAFETY TRAINING .................................................................. 184
14.1 Implementation Guidance ....................................................................... 184
14.1.0 General Information .................................................................... 184
14.2 Determination of Required Training ....................................................... 185
14.3 Training Course Content ......................................................................... 186
14.4 Facility-Specific Materials ...................................................................... 189
14.5 Conduct of Radiation Safety Training .................................................... 189
14.6 Completion of Radiation Safety Training ............................................... 190
14.7 Periodic Radiation Safety Training ......................................................... 192
14.8 Use of Escorts in Lieu of Training .......................................................... 193
14.9 Refresher Training .................................................................................. 193
14.10 Other Training Programs ........................................................................ 193
Section 9
14.11 Training Effectiveness Evaluations ........................................................ 194
15.0 SEALED RADIOACTIVE SOURCE
ACCOUNTABILITY AND CONTROL........................................................... 195
15.1 Implementation Guidance ....................................................................... 195
15.2 Organization and Responsibilities .......................................................... 196
15.3 Receipt .................................................................................................... 197
15.4 Labeling and Storage .............................................................................. 198
15.5 Inventory ................................................................................................. 199
15.6 Leak Testing............................................................................................ 200
15.7 Handling and Disposal ............................................................................ 202
Appendix 15.A Example Individual Accountable
Sealed Radioactive Source Form ............................................................ 203
Appendix 15.B – Example Sealed Radioactive Source
Accountability Form ............................................................................... 205
16.0 TECHNICAL TABLES FOR OCCUPATIONAL
RADIATION PROTECTION ............................................................................. 206
DOE G 441.1-1C viii
5-19-08
Appendix A ............................................................................................................ 206
Derived Air Concentrations (DAC) For Controlling
Radiation Exposure To Workers At DOE Facilities ................................ 206
Appendix B ............................................................................................................ 263
Reserved .................................................................................................. 263
Appendix C ............................................................................................................ 265
Derived Air Concentration (DAC) For Workers From
External Exposure During Immersion in a Cloud
of Airborne Radioactive Material ............................................... 265
Appendix D ............................................................................................................ 267
Surface Contamination Values ................................................................ 267
Appendix E ............................................................................................................ 269
Values For Establishing Sealed Radioactive Source
Accountability And Radioactive Material Posting
And Labeling Requirements ....................................................... 269
Appendix F............................................................................................................. 272
Radiation Weighting Factors ................................................................... 272
Appendix G ............................................................................................................ 273
Tissue Weighting Factors ........................................................................ 273
REFERENCES ................................................................................................................. 275
DOE G 441.1-1C 1
5-19-08
RADIATION PROTECTION PROGRAMS
1.0 PURPOSE AND APPLICABILITY
Section 10
In March 2007 the U.S. Department of Energy (DOE) published an updated implementation
Guide which discussed acceptable methods for ensuring that the functional elements of
radiological activities will be managed and administered in accordance with Title 10, Code of
Federal Regulations (CFR), Part 835, Occupational Radiation Protection (DOE 2007a), hereinafter
referred to as 10 CFR 835. The March 2007 Guide was part of DOE’s efforts to eliminate
redundant requirements and guidance and compiled the guidance previously provided in a set
of 13 Implementation Guides.
On June 8, 2007, the DOE published an amendment to 10 CFR 835. This Guide reflects the
June 8, 2007, amendment to 10 CFR 835 and continues to provide cross-references to other
Guides, DOE-STD-1098-2008, RADIOLOGICAL CONTROL (DOE 2008a), hereinafter referred to as
the RCS, DOE directives, and industry consensus standards that provide detailed guidance for
implementing specific requirements in 10 CFR 835.
DOE is in the process of updating all of its guidance documents for occupational radiation
protection to reflect the 2007 amendment to 10 CFR 835. This Guide is one of the first
documents to be updated, and as such, the cross-references to other DOE guidance documents
will change as additional updated guidance documents are finalized. The references to other
DOE guidance documents, which are scheduled to be updated, will include the notation “Use
the revised version, reflecting the 2007 amendment to 10 CFR 835, when available.”
This Guide provides guidance with respect to implementing the provisions of all the
functional areas contained in 10 CFR 835. These are listed in Chapter 3 of this Guide. Specific
regulatory citations are provided in the body of the Guide.
This Guide amplifies the regulatory requirements of 10 CFR 835 and provides explanations
and examples of the basic requirements for implementing the requirements of 10 CFR 835. The
requirements of 10 CFR 835 are enforceable under the provisions of Sections 223(c) and 234A of
the Atomic Energy Act of 1954, as amended (AEC 1954).
This Guide was developed consistent with DOE M 251.1C, Departmental Directives Program
Manual, (DOE 2009a) which states that guides: (1) Provide preferred, nonmandatory,
supplemental information about acceptable methods for implementing requirements, including
lessons learned, suggested practices, instructions, and suggested performance measures; (2) Do
not impose requirements but may quote requirements if the sources are adequately cited; and
(3) Provide alternate methods that may be used if it can be demonstrated that they provide an
equivalent or better level of performance.
Except for requirements established by a regulation, contract, or administrative means, the
provisions in this Guide are DOE's views on acceptable methods of program implementation and
are not mandatory. Conformance with this Guide will, however, create an inference of
compliance with the related regulatory requirements. Alternate methods that are
demonstrated to provide an equivalent or better level of protection are acceptable. DOE
DOE G 441.1-1C 2
5-19-08
encourages its contractors to go beyond the minimum regulatory requirements and to pursue
excellence in their programs.
The word "shall" is used in this Guide in reference to requirements from 10 CFR 835.
Compliance with 10 CFR 835 is mandatory except to the extent an exemption has been granted
pursuant to 10 CFR 820, Procedural Rules for DOE Nuclear Activities (DOE 2007b). The words
"should" and "may" are used to denote optional program recommendations and allowable
alternatives, respectively.
Section 11
This Guide may be used by all DOE activities that are subject to the requirements of
10 CFR 835. The Administrator of the National Nuclear Security Administration (NNSA) will
assure that NNSA employees and contractors comply with their respective responsibilities under
this Guide.
1.1 USE OF CONSENSUS STANDARDS
As discussed in the Department of Energy's Radiological Health and Safety Policy DOE P
441.1, (DOE 1996), DOE has established a system of regulatory policy and guidance reflective of
national and international radiation protection standards and recommendations. Consistent
with this policy, this Guide endorses the use of several national and international
recommendations and standards, including several from the International Commission on
Radiological Protection, the National Council on Radiation Protection and Measurements, the
American National Standards Institute. In regards to national consensus standards, to the
extent possible, this guidance document endorses and is written to be consistent with following
non-governmental national consensus standards for radiation protection:
ANSI N13.3, Dosimetry for Criticality Accidents
ANSI N43.3-1993, General Radiation Safety -Installations Using Non-Medical X-Ray and
Sealed Gamma-Ray Sources, Energies up to 10 MeV
ANSI N323A-1997, American National Standard Radiation Protection Instrumentation
Test and Calibration, Portable Survey Instruments
ANSI N13.5-R1989, American National Standard Performance Specifications for Direct
Reading and Indirect Reading Pocket Dosimeters
ANSI N42.17A-1989, Performance Specifications for Health Physics
Instrumentation - Portable Instrumentation for Use in Normal Environmental Conditions
ANSI N42.17C-1989, Performance Specifications for Health Physics
Instrumentation - Portable Instrumentation for Use in Extreme Environmental
Conditions
ANSI N42.17B, Performance Specifications for Health Physics
Instrumentation - Occupational Airborne Radioactivity Monitoring Instrumentation
ANSI N2.1-1971(R1989), Radiation Symbol
DOE G 441.1-1C 3
5-19-08
ANSI N13.27, Performance Specifications for Pocket-sized Alarming
Dosimeter/Ratemeters
ANSI Z88.2-1992, Practices for Respiratory Protection
ANSI/HPS N13.30-1996, Performance Criteria for Radiobioassay
ANSI/HPS N13.41-1997, Criteria for Performing Multiple Dosimetry
ANSI/HPS N43.6-1997, Sealed Radioactive Sources Classification
ANSI /HPS N13.6-1999, Practice for Occupational Radiation Exposure Records Systems
ANSI/HPS N43.2-2001, Radiation Safety for X-Ray Diffraction and Fluorescence Analysis
Equipment
ANSI/HPS N13.49-2001, Performance and Documentation of Radiological Surveys
ANSI/HPS N43.5-2005, Radiological Safety Standard for the Design of Radiographic and
Fluoroscopic Industrial X-Ray Equipment
ANSI/NCSL Z540-1-1994, American National Standard for Calibration - Calibration
Laboratories and Measuring and Test Equipment -General Requirements
ANSI N322, American National Standard Inspection, Test, Construction, and
Performance Requirements for Direct Reading Electrostatic/Electroscope Type
Dosimeters
ANSI N320, American National Standard Performance Specifications for Reactor
Emergency Radiological Monitoring Instrumentation
1.2 ACRONYMS
The following are the acronyms frequently used in this document.
AEC U.S. Atomic Energy Commission
ALARA Low As Is Reasonably Achievable
ALI Annual Limit on Intake
ANS American Nuclear Society
ANSI American National Standards Institute
Section 12
BEIR Biological Effects of Ionizing Radiations
BRH Bureau of Radiological Health
BZ Breathing Zone
CAM Continuous Air Monitor
CED Committed Effective Dose
CFR Code of Federal Regulations
http://webstore.ansi.org/ansidocstore/product.asp?sku=N322%2D1997
http://webstore.ansi.org/ansidocstore/product.asp?sku=N322%2D1997
http://webstore.ansi.org/ansidocstore/product.asp?sku=N322%2D1997
DOE G 441.1-1C 4
5-19-08
CSO Cognizant Secretarial Officer
CTED Cumulative Total Effective Dose
DAC Derived Air Concentration
DIL Derived Investigation Level
DL Decision Level
DOE Department of Energy
DOE G DOE Guide
DOE O DOE Order
DOE P DOE Policy
DOELAP Department of Energy Laboratory Accreditation Program
DOE-STD DOE Standard
DPM Disintegrations per Minute
EPA Environmental Protection Agency
FOIA Freedom of Information Act
FR Federal Register
GERT General Employee Radiological Training
HEPA High Efficiency Particulate Air (filter)
HPS Health Physics Society
ICRP International Commission on Radiological Protection
ICRU International Commission on Radiation Units and Measurements
IL Investigation Level
ISO International Organization for Standardization
MDA Minimum Detectable Amount/Activity
NCRP National Council on Radiation Protection and Measurements
NCSL National Conference of Standards Laboratories
NIST National Institute of Standards and Technologies
NRC Nuclear Regulatory Commission
PNL Pacific Northwest Laboratory
PSE Planned Special Exposure
PSO Program Secretarial Office
RCO Radiological Control Organization
RCS DOE-STD-1098-99, RADIOLOGICAL CONTROL
RCT Radiological Control Technician
RGD Radiation-Generating Device
RMA Radioactive Material Area
RPP Radiation Protection Program
RWP Radiological Work Permit
RWT Radiological Worker Training
DOE G 441.1-1C 5
5-19-08
SLAC Stanford Linear Accelerator Center
TED Total Effective Dose
TEDE Total Effective Dose Equivalent
TLD Thermo Luminescent Dosimeter
TWD Technical Work Document
UNSCEAR United Nations Scientific Committee on the Effects of Atomic Radiation
USLW United States Law Week
DOE G 441.1-1C 6
5-19-08
2.0 DEFINITIONS
Terms from 10 CFR 835 are used consistent with their regulatory definition.
Acceptance testing: Evaluation or measurement of performance characteristics to verify
that certain stated specifications and contractual requirements are met.
Air monitoring: Actions to detect and quantify airborne radiological conditions by the
collection of an air sample and the subsequent analysis, either in real-time or offline laboratory
analysis, of the amount and type of radioactive material present in the atmosphere.
Air sampling: A form of air monitoring in which an air sample is collected and analyzed at a
later time, sometimes referred to as retrospective air monitoring.
ALARA committee: The multi-disciplined forum that reviews and advises management on
improving progress towards minimizing radiation dose and radiological releases.
ALARA design review: A systematic review to ensure that ALARA considerations are
evaluated, incorporated if reasonable, and documented for the design of new facilities and
modifications to existing facilities that involve the potential for exposure to ionizing radiation.
ALARA job/task/experiment review: A systematic pre- and post-job review of high-dose
and potentially high-dose activities to ensure that ALARA controls are planned, evaluated,
implemented where reasonable, and documented.
Section 13
Alarm set point: The count rate or concentration at which a real-time air monitor will
alarm, usually set to correspond to a specific airborne radioactive material concentration
averaged over time (e.g., DAC-hour alarm equivalent) by calculating the sample buildup rate on
the collection medium.
Alpha (α): The probability (not to be confused with an alpha particle) of a Type I error or
false positive. This is also called the false positive probability.
Analyte: The particular radionuclide to be determined in a sample of interest.
Baseline bioassay: An appropriate bioassay measurement obtained from a radiobioassay
program participant prior to beginning or resuming work with radioactive material.
Beta (β): The probability (not to be confused with a beta particle) of a Type II error or false
negative. This is also called the non-detection probability.
Boundary identifier: A hazard identifier that is used to define the boundary of an area.
Boundary: The line that defines the transition from one specified area to another.
Breathing zone air monitoring: A form of air monitoring that is used to detect and quantify
the radiological conditions of air from the general volume of air breathed by the individual,
usually at a height of 1 to 2 meters. See "personal air monitoring."
DOE G 441.1-1C 7
5-19-08
Cabinet X-ray system: An X-ray system with the X-ray tube installed in an enclosure
(hereinafter termed "cabinet") which, independently of existing architectural structures except
the floor on which it may be placed, is intended to contain at least that portion of a material
being irradiated, provide radiation attenuation, and exclude individuals from its interior during
generation of X-radiation. Included are all the X-ray systems designed primarily for inspection of
carry-on baggage at airline, railroad, and bus terminals, and in similar facilities. An X-ray tube
used within a shielded part of a building or X-ray equipment which may temporarily or
occasionally incorporate portable shielding is not considered a cabinet X-ray system.
Challenge examination: An examination administered to ascertain the knowledge of a
worker with respect to radiation safety and provide an exception to the required training.
Check source: A radioactive source, not necessarily calibrated, that is used to confirm the
continuing satisfactory operation of an instrument.
Confirmed intake: An intake confirmed by follow-up radiobioassay, by association with a
known incident, or by investigation.
Contaminated area: Any area meeting the definition of “contamination area,” “high
contamination area,” or “airborne radioactivity area” provided in 10 CFR 835.2(a).
Continuous air monitor (CAM): An instrument that continuously samples and measures the
levels of airborne radioactive material on a "real-time" basis and has alarm capabilities at preset
alarm set points.
Decision level (Lc): The amount of a count (Lc or L c) as final instrument measurement of a
quantity of analyte (Dc or D c) at or above which a decision is made that the analyte is definitely
present.
Derived investigation level (DIL): A value of a radiobioassay or air monitoring measurement
that indicates an intake resulting in a dose exceeding an Investigation Level (IL).
Detector: A device or component designed to produce a quantifiable response to ionizing
radiation, normally measured electronically.
Section 14
Direct (in vivo) radiobioassay: The measurement of radioactive material in the human body
utilizing instrumentation that detects radiation emitted from the radioactive material in the
body.
DOELAP: The Department of Energy Laboratory Accreditation Program. This program
defines a set of reference performance tests and provides a description of the minimum levels of
acceptable performance for personnel dosimetry systems and radiobioassay programs under
either DOE STD-1111-98, THE DEPARTMENT OF ENERGY LABORATORY ACCREDITATION
PROGRAM ADMINISTRATION (DOE 1998A), or DOE STD-1112-98, THE DEPARTMENT OF ENERGY
LABORATORY ACCREDITATION PROGRAM FOR RADIOBIOASSAY (DOE 1998b).
Dose assessment: The process of determining radiological dose and uncertainty included in
the dose estimate, through the use of exposure scenarios, bioassay results, monitoring data,
DOE G 441.1-1C 8
5-19-08
source term information, and pathway analysis.
Elimination: The biological removal of a radionuclide from the body by excretion,
perspiration, exhalation, secretion (e.g., breast milk), exfoliation (sloughing of dead tissue), or
excision.
Embryo/fetus: A developing human organism from conception until birth.
Escort: An individual with the prerequisite training necessary for unescorted access to the
area(s) where the escort activities will be performed and who is authorized to accompany and
ensure the safety of individuals who lack such training.
Evaluation: The process of arriving at a value for intake or dose that uses, among other
inputs, measurement results.
Excretion: The biological removal of a radionuclide from the body via one or more excretion
pathways: urine and feces.
Exempt sealed radioactive source: A sealed radioactive source that does not meet the
accountability criteria established in the definition of the term “accountable sealed radioactive
source” provided in 10 CFR 835.2(a).
Exposure: The general condition of being subjected to ionizing radiation, such as by
proximity to external sources of ionizing radiation or through intake of radioactive material into
the body. In this document, exposure does not refer to the radiological physics concept of
charge liberated per unit mass of air.
False negative: A Type II (β) error, that is, concluding that analyte is not present when in fact
it is.
False positive: A Type I (α) error, that is, concluding that there is analyte present when it is
not.
Fixed contamination: Radioactive material that cannot be readily removed from surfaces
by nondestructive means, such as casual contact, wiping, or brushing.
Fixed-location sampler: An air sampler located at a fixed location in the workplace.
Frisk or frisking: Process of monitoring individuals or surfaces for contamination by directly
scanning the surface with a suitable radiation detector.
Functional tests: Tests (often qualitative) to determine that an instrument is operational
and capable of performing its intended function. Such tests may include, for example, battery
check, zero setting, or source response checks.
Geotropism: A change in an instrument's reading as its orientation changes, due to
gravitational effects.
DOE G 441.1-1C 9
5-19-08
Gestation period: The time from conception to birth; usually 40 weeks or approximately 9
months.
Grab sampling: A single sample removed from the air over a short time interval, typically a
few minutes for high volume air samplers and less than one hour for low volume air samplers.
Section 15
Hot particles: Small, discrete, highly radioactive particles that can cause extremely high
dose rates to a localized area.
Indirect (in vitro) radiobioassay: The measurement or analysis of radionuclides in excreta or
other biological samples removed from the body.
Instrument (radiation detection): A complete system consisting of one or more
subassemblies (e.g., detector, readout, etc.) designed to quantify one or more characteristics of
ionizing radiation or radioactive material.
Intake: The amount of radionuclide taken into the body by inhalation, absorption through
intact skin, injection, ingestion, or through wounds. Depending on the radionuclide involved,
intakes may be reported in mass (e.g., μg, mg), activity (e.g., μCi, Bq), or potential alpha energy
(e.g., MeV, J) units.
Interlock: A device for precluding access to an area of radiation hazard by either preventing
entry or by automatically removing the hazard. One example is an electro-mechanical control
mechanism that interrupts the beam of ionizing radiation or shuts down the radiation
installation whenever the interlock is challenged.
Internal audits: Reviews and evaluations of the content and implementation of the
documented radiation protection program conducted by an organization neither responsible
nor accountable for developing program content or implementing the program.
Investigation level (IL): The value of the committed effective dose from an intake(s) of a
radioactive material by a worker at or above which, for regulatory purposes, is regarded as
sufficiently important to justify further investigation
Irradiator: Any gamma- or neutron-emitting sealed radioactive material that has the
potential to create a radiation level exceeding 500 rads (5 grays) in 1 hour at 1 meter and is
operated within the requirements of an RGD installation.
Minimum detectable amount (MDA): The smallest amount (activity or mass) of an analyte
in a sample that will be detected with a probability, β, of non-detection (Type II error) while
accepting a probability, α, of erroneously deciding that a positive (non-zero) quantity of analyte
is present in an appropriate blank sample (Type I error). The MDA is computed using the same
value of α as used for the Lc. The MDA depends on both α and β. Measurement results are
compared to the Lc, not the MDA; the MDA is used to determine whether a program has
adequate detection capability. The MDA will be greater than or equal to the Lc.
Modification: Any alteration of the shielding configuration, device or installation operating
practices, or the replacement of the original RGD (or component part thereof) with another that
has not been previously evaluated, inspected, monitored, and documented by the radiological
DOE G 441.1-1C 10
5-19-08
control organization. This definition also includes the collocation of additional or multiple
unevaluated RGDs within a previously evaluated installation.
Normal operation: Operation under conditions as recommended by the manufacturer of
the RGD with recommended shielding and barriers in place, and as specified in the operating
procedures and requirements for the RGD installation.
Occupied (occupiable) area: An area or location that may be physically accessible by
individuals (or body parts thereof) while a radiation-generating device is in operation.
Off-normal operation: An event or condition that adversely affects, potentially affects, or
indicates degradation in the safety, security, environmental, or health-protection performance
or operation of an RGD installation.
Section 16
Optimization methodology: A documented methodology which describes how the factors
affecting a protection decision, i.e., social, technical, economic, practical, and public policy, are
assigned values to compare detriment and benefits.
Performance demonstration: A demonstration by a student of the skills required to
perform certain designated activities.
Performance tests: Tests performed periodically over the life of an instrument to verify that
it continues to meet operational requirements. Examples of performance tests are response
time and geotropism.
Personal air monitoring: A form of breathing zone air monitoring that involves the sampling
of air in the immediate vicinity (typically within one foot) of an individual’s nose and mouth,
usually by a portable sampling pump and collection tube (e.g., a lapel sampler) worn on the
body.
Physical barrier: A bounding physical obstruction that prevents unimpeded access to an
area.
Portable air sampler: An air sampler designed to be moved from area to area.
Portable monitoring instrument: An instrument intended to be operated while being
carried by an individual.
Qualified expert: An individual having the knowledge, training, and recognition of such by
management to measure ionizing radiation, to evaluate safety techniques, to design RGD
installations, and to provide advice on radiation protection requirements.
Radiation protection program (RPP): The documented program, approved by DOE,
including, but not limited to, the plans, schedules, and other measures developed and
implemented to achieve and ensure continuing compliance with 10 CFR 835 and to apply the as
low as is reasonably achievable (ALARA) process to occupational dose.
Radiation-generating device (RGD): Collective term for devices which produce ionizing
radiation, including, certain sealed radioactive sources, small particle accelerators used for
DOE G 441.1-1C 11
5-19-08
single purpose applications which produce ionizing radiation (e.g., radiography), and electron
generating devices that produce X-rays incidentally.
Radiography: Examination of the structure of materials by nondestructive methods, using a
RGD.
Radiological control organization (RCO): An organization responsible for radiation
protection activities.
Radiological engineer: An individual who is responsible for providing technical support and
assistance to supervisors, planners, schedulers, principal investigators, and design engineers to
reduce occupational doses and the spread of radioactive materials.
Radiological work permit (RWP): The document that identifies radiological conditions,
establishes worker protection and monitoring requirements, and contains specific approvals for
radiological work activities. The RWP serves as an administrative process for planning and
controlling radiological work and informing the worker of the radiological conditions.
Radon: Unless otherwise specified, the isotope 222Rn.
Real time air monitor: An instrument that measures the levels of airborne radioactive
material on a "real-time" basis.
Refresher training: Periodic (usually annual) training that provides current information on
changes to radiation protection policies and procedures or changes in facility conditions, or to
promote awareness of infrequently encountered radiological safety matters.
Removable contamination: Radioactive material that can be removed from surfaces by
nondestructive means, such as casual contact, wiping, or brushing.
Section 17
Representative air sampling: The sampling of airborne radioactive material in a manner
such that the sample collected closely approximates both the amount of activity and the
physical and chemical properties (e.g., particle size and solubility) of the contaminant to which
the individuals may be exposed.
Retention: The amount of material which, after being taken into the body by inhalation,
ingestion, entry through an open wound, or absorption through the skin, exists in the whole
body, a compartment, an organ, or a tissue at a specified time.
RGD Custodian: An individual who is trained and designated to maintain cognizance over
accountability control of radiation-generating devices assigned to him or her.
RGD installation: The sum of the radiation source (e.g., sealed radioactive material or x-ray
tube), the associated equipment and component items, and the space in which they are
operated.
Five types of installations are defined as follows:
DOE G 441.1-1C 12
5-19-08
(1) Shielded installations are those designed to use the room-within-a-room concept to
limit access to the RGD beam and to place more emphasis on distance as opposed to
shielding for radiation protection and include shielded, exempt shielded, and cabinet
x-ray installations;
(2) Unattended installations are those designed for a specific purpose and that do not
require personnel in attendance for operation and include unattended gauge and other
unattended installations;
(3) Open installations are those designed to accommodate a specimen that is so large as to
make an exempt shielded installation impractical;
(4) X-ray diffraction & fluorescence analysis equipment, including both open and closed
beam installations; and
(5) Incidental, including devices that emit low levels of ionizing radiation as a byproduct of
their normal function, such as electron beam welders, electronic microscopes, and pulse
generators.
RGD Operator: An individual who is trained and deemed qualified to use a
radiation-generating device.
Routine radiobioassay monitoring: Any radiobioassay measurement made on a
predetermined, periodic schedule, to establish whether a worker has had any intake of
radioactive material since previous radiobioassay measurements.
Source custodian: An individual who is trained and designated to maintain cognizance over
accountability and control of assigned sealed radioactive sources.
Source response check: A functional test that includes the observation of the response of
an instrument to a check source.
Source user: An individual who is trained and authorized to use sealed radioactive sources.
Source-specific air sampling: Collection of an air sample near an actual or likely release
point.
Special radiobioassay monitoring: Any radiobioassay measurement that is required for
confirmation of a suspected intake of radionuclides, or is required for follow-up evaluation of
confirmed intakes.
State-of-the-art: The most advanced technology that is commercially available and
successfully field tested.
Technical work document (TWD): A term used to generically identify formally approved
documents that direct work, such as procedures, work packages, or job or research plans. TWDs
provide radiological and ALARA controls applicable to the task.
DOE G 441.1-1C 13
5-19-08
Section 18
Technology shortfall: A technology shortfall for routine radiobioassay exists when the
derived investigation level (DIL) for a well-designed and appropriate routine radiobioassay
program, using current or state-of-the-art methods and equipment, is less than the minimum
detectable amount/activity of the routine monitoring method (e.g., the DIL is less than the
MDA).
Termination radiobioassay: A radiobioassay measurement performed for the purpose of
documenting the retention of radioactive materials in the body due to occupational exposure
either upon termination of employment or upon the cessation of potential exposure to a specific
nuclide.
Test: A procedure whereby an instrument, component, or circuit is evaluated against
certain criteria for satisfactory operation.
Thoron: Unless otherwise specified, the isotope 220Rn.
Traceability: The ability to show, through documentation, that a particular instrument or
radiation source has been calibrated using either the national standard or a transfer standard in
a chain or echelon of calibrations, ultimately leading to a comparison with the national standard.
Type test: An initial test of one or more production instruments made to a specific design to
show that the design meets certain specifications.
Type I error: Incorrectly concluding from a result that there is analyte present; the
probability (α) of a Type I error is usually taken as 0.05. The decision level is determined on the
basis of an acceptable level of Type I errors.
Type II error: Incorrectly concluding from a result that there is no analyte present; its
probability (β) is usually taken as 0.05.
DOE G 441.1-1C 15
5-19-08
Uniform exposure: Hypothetical radiation field in which the fluence and its angular and
energy distributions are the same throughout the volume of interest.
Useful beam: That part of the primary and secondary radiation beam that passes through
the aperture, cone, or other device used for collimation.
DOE G 441.1-1C 16
5-19-08
3.0 RADIATION PROTECTION PROGRAMS
10 CFR 835 establishes specific requirements for the development, content, revision, and
approval of the documented RPP for a DOE activity. These requirements include identifying
existing and/or anticipated operational tasks and formal plans and measures for maintaining
occupational radiation doses ALARA. Guidance provided in this Guide, in combination with the
provisions of site radiological control manuals developed and implemented consistent with
guidance provided by the RCS for those regulatory provisions not addressed by this Guide,
provide reasonable assurance that a site RPP will meet the requirements of 10 CFR 835.
The RPP for a specific DOE activity is approved by the DOE, typically by the cognizant DOE
Headquarters Program Office. The RPP is intended to provide DOE reasonable assurance that
the DOE activity will be conducted in compliance with the provisions of 10 CFR 835. The RPP
also satisfies the requirement for an Implementation Plan found in other DOE directives.
Guidance concerning the specific documentation required for DOE approval of RPPs as required
in 10 CFR 835.101(f), (g), and (h) is provided in Appendix 3.A, PREPARATION, REVIEW AND
APPROVAL OF RADIATION PROTECTION PROGRAMS. Appendix 3.A is based on guidance which
previously was provided in DOE-STD-1082-94, PREPARATION, REVIEW, AND APPROVAL OF
IMPLEMENTATION PLANS FOR NUCLEAR SAFETY REQUIREMENTS. Guidance is also provided by
the cognizant DOE Headquarters Program Office.
Section 19
Program Offices will also provide guidance should DOE need to direct or make modifications
to an RPP as provided under 10 CFR 835.101(b). 10 CFR 835 permits changes, additions, or
updates to an RPP to become effective without prior DOE approval only if the changes do not
decrease the effectiveness of the RPP and the RPP, as changed, continues to meet the
requirements of the rule. Proposed changes that decrease the effectiveness of the RPP shall not
be implemented without submittal to and approval by DOE [10 CFR 835.101(h)]. Guidance
regarding the process for submitting and approving changes will be provided by the appropriate
DOE Headquarters Program Office.
The RPP is the basis for implementing operational radiation protection program
requirements for a DOE activity. A combination of various methods which can be used to
achieve regulatory compliance is discussed in this Guide. DOE recognizes that many of the
requirements of 10 CFR 835 are not new. Equivalent requirements were previously
promulgated in DOE Orders and the DOE Radiological Control Manual, which were implemented
under contractual obligations for most DOE activities involving occupational exposure to ionizing
radiation. Therefore, much of the RPP documentation required to ensure compliance with
10 CFR 835 has already been developed to ensure compliance with contractually-imposed
radiation protection standards. DOE recognizes that significant effort was expended in
upgrading radiation protection of the work force and does not intend for its contractors to
expend significant additional effort to develop and implement a separate, redundant program
to satisfy the RPP requirements of 10 CFR 835. The RPP should rely on existing documents, such
as the site radiological control manual, contractual agreements, procedures, and memoranda, to
effectively administer and manage regulatory commitments. However, the completeness of
these existing documents should be verified to ensure that all 10 CFR 835 requirements are
satisfied. This chapter of this Guide provides guidance on the management and administrative
aspects of the RPP to achieve and maintain compliance with specific requirements in
10 CFR 835.
DOE G 441.1-1C 17
5-19-08
Internal audits of the radiation protection program, including examination of program
content and implementation, shall be conducted through a process that ensures that all
functional elements of the program are reviewed no less frequently than every 36 months
(10 CFR 835.102). This Guide discusses the role of an internal audit program in effectively
managing and administering an RPP that complies with 10 CFR 835. These internal audits may
also be incorporated into quality assurance programs developed under 10 CFR 830 Subpart A,
Quality Assurance Requirements (DOE 2001a) and/or DOE Order 414.1C, Quality Assurance
(DOE 2005a). Functional elements of a comprehensive RPP are identified and discussed
throughout Section 3.2 of this Guide. The specific functional elements for a DOE activity will
depend upon the types of radiological work being performed and the radiological hazards
present. Other functional elements necessary for an integrated worker health and safety
program are not addressed in this Guide, but should be integrated with a radiological control
program. These other functional elements include: respiratory protection, radioactive material
shipment and receipt, radioactive waste management, and emergency response.
3.1 Implementation Guidance
Section 20
The approved RPP details how a DOE activity shall be in compliance with 10 CFR 835 and
should identify the functional elements appropriate for that activity. Additional documentation
should be developed and maintained to supplement the approved RPP to demonstrate that an
RPP can be effectively managed and administered to achieve compliance with 10 CFR 835. This
documentation typically includes a site radiological control manual developed to the guidance
contained in the RCS, as well as detailed implementing procedures, appropriate management
policy statements, and technical basis documentation. While this documentation need not be
part of the RPP, it should be clearly linked to the compliance commitments contained in the
RPP.
DOE has developed technical guidance to support effective implementation of programs to
ensure compliance with 10 CFR 835. The RCS was developed to provide detailed guidance on
and best practices for line management implementation of DOE's radiation protection
requirements. DOE has also developed a set of technical standards and handbooks addressing
radiation protection issues, such as training, internal dosimetry, or plutonium operations.
Additionally, DOE has developed a set of Radiological Control Technical Positions (RCTPs). The
RCTPs provide acceptable approaches to implementing specific provisions, or otherwise address
specific issues, of the Rule (available at
http://www.hss.energy.gov/HealthSafety/WSHP/radiation/tpp.html). In addition, this Guide
provides acceptable methods for achieving compliance with a variety of technical and
administrative requirements.
RPP changes may be implemented without prior DOE approval only if the RPP continues to
meet 10 CFR 835 requirements and the changes do not reduce program effectiveness
[10 CFR 835.101(h)]. Due to the wide range of activities subject to 10 CFR 835 and the variety of
methods used by these activities to ensure compliance, no specific criteria exist by which DOE
may predetermine whether an RPP change results in a reduction in program effectiveness.
Factors that should be considered include the impact of the proposed change(s) on:
radiological conditions in occupied areas;
DOE G 441.1-1C 18
5-19-08
individual and collective doses;
worker awareness of radiological conditions and controls;
management oversight and control of routine and non-routine radiological work
activities;
sufficiency of area and personnel monitoring programs;
completeness and irretrievability of records;
radiological control performance indicators;
adherence to consensus standards; and
other factors that ensure full implementation of the RPP.
Documentation of the rationale applied to RPP changes implemented without prior DOE
approval should be retained for future reference and demonstration of compliance.
The terms "likely" and "potential" have been used judiciously throughout the rule to
allow the use of professional judgment and experience in making decisions in specific
circumstances and provide the flexibility necessary to implement the regulatory
requirements under a broad range of activities. The technical bases and other
considerations should be documented when professional judgment is exercised. This
documentation should provide sufficient detail to permit individuals who are responsible for
implementing and assessing the RPP to clearly understand how regulatory compliance is
achieved and maintained. The RCS, Guides, and other DOE technical standards and
Section 21
handbooks are designed to facilitate development and implementation of a comprehensive
RPP commensurate with the radiological hazards associated with the DOE activity. In
addition, consensus standards, such as those developed by the American National Standards
Institute (ANSI) and the Health Physics Society (HPS), may provide additional guidance
concerning technical issues not specifically addressed by the Guides, RCS, DOE technical
standards, or other DOE guidance documents.
3.2 Organization and Administration
The RPP shall include plans, schedules, and other measures for achieving compliance with
10 CFR 835 [10 CFR 835.101(f)]. Plans should include establishing the organization and
administration of the RPP to ensure that the program is effectively implementing appropriate
measures that ensure regulatory compliance can be achieved and sustained. The authority and
responsibility for radiation protection should originate at the highest levels of line management
and should be emphasized throughout the organization. Ultimately, workers should be aware of
their individual responsibilities for radiation protection. Programmatic documentation should
be developed to document the organizational and administrative aspects of the RPP.
DOE G 441.1-1C 19
5-19-08
3.2.0 Administrative Processes
The degree of formality and scope of the associated administrative processes should be
commensurate with the radiological hazards encountered and complexity of the associated
control measures. More rigorous administrative processes should be implemented for more
complex or hazardous DOE activities. Administrative processes should include a hierarchy of
documents that clearly and unambiguously delineate management policies, requirements,
expectations, and objectives for the RPP. This documentation should typically include the
following:
Policy statement: The policy statement should articulate management’s commitment to
conduct radiological operations in a manner that will ensure the health and safety of all
its employees, contractors, and the general public. This policy statement should be
patterned after DOE P 441.1, Department of Energy Radiological Health and Safety
Policy (DOE 1996).
Site-specific radiological control manual or handbook: This document should be issued
and endorsed by senior management for a DOE activity. This manual or handbook
should address all functional elements of the RPP for the DOE activity.
Procedures: These documents should provide detailed instructions for implementing
various functional elements of the RPP. Responsibilities and actions required of
management and workers should be clearly and unambiguously stated. Written
procedures shall be developed and implemented as necessary to ensure compliance
with 10 CFR 835, commensurate with the radiological hazards created by the activity
and consistent with the education, training, and skills of the individuals exposed to
those hazards (10 CFR 835.104).
It is not necessary for written procedures to be developed and implemented for all
of the requirements of 10 CFR 835. Written procedures should be developed and
employed under the following circumstances:
– worker health and safety are directly affected;
– the expected outcome for the process or operation requires that a specific
method be followed;
– the process or operation is infrequently used and competence training cannot
assure adequate implementation; or
Section 22
– to document the approved method to implement specific processes or
operations. In evaluating the need for written procedures, consideration shall
be given to the level and extent of the radiological hazards, the complexity of
the measures required to achieve compliance, and the education, training and
skills of the individuals who must implement those measures (10 CFR 835.104).
Under such a regimen, a low hazard activity employing a stable staff of highly
educated and skilled workers having demonstrated an advanced knowledge of
radiation protection principles and practices could have fewer and less detailed
DOE G 441.1-1C 20
5-19-08
procedures than a higher hazard activity employing a transient workforce with
less knowledge of radiation protection practices and principles. This Guide
provides additional guidance regarding specific procedural aspects of the RPP.
Technical basis documents: Document decisions and approaches used to achieve
regulatory compliance, such as those decisions where professional judgment has been
exercised. The document should include supporting analyses and justifications
sufficient to demonstrate that regulatory compliance can be achieved and maintained.
This Guide contains specific recommendations for documenting the technical basis for
various RPP functional elements.
10 CFR 835 specifies the frequency for performing certain activities. Internal audits shall be
conducted on a 36 month cycle (10 CFR 835.102); radiation safety training shall be conducted
every twenty four months [10 CFR 835.901(e)]; and accountable sealed radioactive sources shall
be inventoried and leak tested every six months [10 CFR 835.1202(a) and (b)]. DOE expects that
those entities responsible for ensuring compliance with the rule will undertake those measures
necessary to perform the required activities within the prescribed time frame (e.g., if a sealed
radioactive source is leak tested on January 15, DOE would expect the subsequent leak test to
be performed on or before July 15 of the same year). 10 CFR 835.3(e) allows a grace period of
up to 30 days when operational or scheduling considerations preclude adherence to the
required schedule (e.g., the leak test could be performed no later than August 14 of the same
year). If the provisions of 10 CFR 835.3(e) are exercised, documentation of the schedule
deviation should be developed and include a discussion of the specific activity involved and the
reason for the schedule deviation. Schedule extensions beyond the 30 day grace period can
only be granted through the regulatory exemption process under 10 CFR 820.62.
3.2.1 Radiological Control Organization
A radiological control organization should be established to support line managers and
workers. To function effectively and be consistent, as necessary, with the requirements in DOE
O 226.1, Implementation of Department of Energy Oversight Policy (DOE 2005b) the radiological
control organization should be independent of the line organizational element responsible for
production, operation, or research activities, and should have an equivalent reporting level.
Radiological control organization function is discussed in detail in the RCS. Other organizational
schemes that allow effective compliance with the standards set forth in 10 CFR 835 should be
considered to address site- or facility-specific needs.
3.2.2 Education, Training, and Skills
Section 23
Individuals responsible for developing and implementing measures necessary for ensuring
compliance with the requirements of 10 CFR 835 shall have the appropriate education, training
and skills to discharge these responsibilities (10 CFR 835.103). These individuals can include
technical and management personnel within the radiological control organization, independent
assessors, and line managers responsible for radiological work activities. In addition,
10 CFR 830.122(b), Quality Assurance Criteria, specifies that nuclear facility personnel shall be
trained and qualified to ensure they are capable of performing their assigned work.
DOE G 441.1-1C 21
5-19-08
DOE previously issued requirements and guidance with regard to education, training, and
skills for many categories of personnel, including individuals responsible for developing and
implementing measures necessary for ensuring compliance with the requirements of
10 CFR 835. Some of these requirements are addressed in DOE O 426.2, Personnel Selection,
Training, Qualification, and Ceftification Requirements for DOE Nuclear Facilities (DOE 2010a).
This order establishes training and qualification requirements for technical professionals and
management personnel operating defense nuclear facilities. While these requirements are not
mandatory for all DOE facilities, this information may be useful for all DOE facilities in
developing training programs and standards for the education, training, and skills appropriate
for personnel to achieve compliance with the requirements of 10 CFR 835.103 and
10 CFR 830.122(b).
Key radiation protection positions are identified in DOE STD-1107-2007, Chg 1.
KNOWLEDGE, SKILLS AND ABILITIES FOR KEY RADIATION POSITIONS AT DOE FACILITIES (DOE
2007g). This document supplements the requirements discussed above by synthesizing
guidance from several source documents into a single reference. DOE STD-1107-2007 describes
the level of knowledge, skills, and abilities for personnel in key radiation protection involved
with DOE activities. The approach taken in DOE STD-1107-2007 reinforces the DOE’s emphasis
on establishing a system of criteria for key radiation protection positions that reflects the
increasing levels of education, training, and skills needed for positions of increasing
responsibility. The information contained in this standard should be strongly considered when
evaluating the education, training, and skills of personnel in key radiation protection positions.
The standards in DOE O 426.2 and DOE STD-1107-2007 are based on DOE, Nuclear
Regulatory Commission, and related industry standards and provide an acceptable method for
achieving compliance with the requirements of 10 CFR 835.103.
DOE STD-1107-2007 includes radiological control technicians (RCTs) in the list of key
radiation protection positions. While 10 CFR 835 does not establish specific requirements for
RCT training, DOE considers the typical job functions associated with RCTs to be critical in
implementing an acceptable RPP. These typical job functions include: prescribing and
implementing radiological work controls, performing radiological monitoring, responding to
radiological incidents, or evaluating radiological conditions in the workplace. Individuals
performing these functions shall meet the provisions of 10 CFR 835.103. Chapter 6, Part 4, of
the RCS discusses the essential elements of RCT training and qualification, including qualification
standards, oral examination boards, and continuing training. In support of these elements, DOE
has developed and maintains the core course for RCTs. DOE considers the DOE-developed core
course for RCTs, augmented with site specific training, an acceptable level of training for
individuals performing the typical job functions associated with RCTs. As is the case with using
any of the DOE-developed training courses, sites need to evaluate the individual’s job functions
and ensure the adequacy of the training provided.
Section 24
To ensure that the work performed by RCTs receives the appropriate level of review and
evaluation, it is important that RCT Supervisors receive a higher level of training and maintain a
higher level of knowledge than those expected of RCTs. Chapter 6, Part 4 of the RCS also
provides guidance on the essential elements of RCT Supervisor training and qualification,
including continuing training and oral examination boards.
DOE G 441.1-1C 22
5-19-08
DOE developed and implemented core courses to enhance the content of training provided
to general employees, radiological workers, and radiological control technicians across the DOE
complex and bring these core training programs up to a standard consistent with the
commercial industry. The use of the core courses is not mandatory. However, these courses
should strongly be considered as a basis for developing and implementing radiation safety and
radiological control technician training programs. Additional guidance regarding compliance
with the Subpart J requirements is provided in Chapter 14 of this Guide.
DOE has also sponsored development of additional training courses and guidance. DOE
strongly encourages its operating entities to implement these courses and guidance. These
courses and guidance, when augmented with site specific information and appropriately revised
to reflect the most current regulatory requirements, provide acceptable approaches for
providing radiation safety training or training for individuals responsible for developing and
implementing measures necessary for ensuring compliance with the rule. These courses
include:
DOE-HDBK-1130-2008; RADIOLOGICAL WORKER (RW) TRAINING MATERIALS; APPENDIX
A, RADIOLOGICAL CONTROL TRAINING FOR SUPERVISORS. (DOE 2008c)
DOE-HDBK-1145-2008; RADIOLOGICAL SAFETY TRAINING FOR PLUTONIUM FACILITIES
(DOE 2008d)
DOE-HDBK-1141-2008; RADIOLOGICAL ASSESSOR TRAINING (DOE 2008e)
DOE-HDBK-1129-2008; TRITIUM SAFE HANDLING AND STORAGE(DOE 2008f)
DOE-HDBK-1106-2008, RADIOLOGICAL WORKER TRAINING; Appendix B: RADIOLOGICAL
CONTAMINATION CONTROL TRAINING FOR LABORATORY RESEARCH (DOE 2008g)
DOE-HDBK-1108-2002; RADIOLOGICAL SAFETY TRAINING FOR ACCELERATOR FACILITIES
(DOE 20025b)
DOE-HDBK-1130-2008, RADIOLOGICAL WORKER (RW) TRAINING MATERIALS; Appendix
C: RADIOLOGICAL SAFETY TRAINING FOR RADIATION-PRODUCING (X-RAY) DEVICES (DOE
2008h)
DOE-HDBK 1110-2008, ALARA TRAINING FOR TECHNICAL SUPPORT PERSONNEL (DOE
2008b)
DOE-HDBK-1113-2008, RADIOLOGICAL SAFETY TRAINING FOR URANIUM FACILITIES
(DOE 2008i)
DOE-HDBK-1122-2009, RADIOLOGICAL CONTROL TECHNICIAN TRAINING (DOE 2009a)
3.2.3 Internal Audit and Self Assessment
Internal audits and self assessments are two of the numerous checks and balances needed
in an effective RPP. Internal audits of the RPP, including examination of program content and
http://www.eh.doe.gov/radiation/RST/rct3/rct-web-cover.htm
DOE G 441.1-1C 23
5-19-08
implementation, shall be conducted through a process that ensures that all functional elements
of the program are reviewed no less frequently than every 36 months (10 CFR 835.102). The
RCS discusses how assessments, including internal audits, provide independent feedback to
senior line managers concerning the implementation of the RPP.
Section 25
An audit plan or mechanism should be developed that identifies the functional elements of
the RPP and the schedule for review to ensure that over a 36 month period, all of the functional
elements are reviewed. Internal audits should be conducted on a continuing basis. DOE
cautions against conducting a single comprehensive internal audit of the entire RPP once every
three years. DOE does not believe that such an approach is effective in assuring that a DOE
activity will be conducted in conformance with its approved RPP. DOE recommends that, at a
minimum, an annual, broad scope audit of the program be conducted. Under this approach, the
audit plan would identify each functional element to be reviewed during the annual audit and
ensure that all functional elements would be reviewed during a 36 month cycle. Thus, the RPP is
under continuing review and deficiencies can be identified and corrected in a timely manner.
The functional elements of a comprehensive RPP are discussed in this Guide. All of these
functional elements may not be applicable to a specific DOE activity, but should be selected
based upon the type of radiological work being performed and the radiological hazards
encountered.
Internal audits should be conducted by individuals who are organizationally independent
from the organizations responsible for developing and implementing the RPP.
3.2.4 Radioactive Material Transportation Exclusion
10 CFR part 835 excludes radioactive material transportation not performed by DOE or a
DOE contractor (10 CFR 835.1(b)(7)). The intent is to exclude from 10 CFR part 835
transportation by the U. S. Postal Service or a commercial carrier, such as FedEx or UPS, which
transport radioactive material as part of their normal operations. A company or subsidiary of a
corporation that operates a DOE facility would not be considered a commercial carrier - even if
such an organization transports radioactive material as part of its contractual agreement with
DOE. Activities related to transportation such as the preparation of material or packaging for
transportation, storage of material awaiting transportation, or application of markings and
labels required for transportation is not included in the exclusion (See 10 CFR 835.2, Definitions,
Radioactive material transportation).
Subparts F (Entry Control Program) and G (Posting and Labeling) do not apply to radioactive
material transportation conducted by a DOE individual or DOE contractor, when the radioactive
material is under the continuous observation and control of an individual who is knowledgeable
of and implements required exposure control measures or when conducted in accordance with
Department of Transportation regulations or DOE orders that govern such movements (10 CFR
835.1(d)). This does not affect the application of requirements to radioactive material
transportation in the other subparts of 10 CFR part 835. In accordance with the definition of
“radioactive material transportation,” the exclusion applies while the material is in the process
of undergoing movement, including nominal stoppages such as for traffic considerations or
refueling activities.
DOE G 441.1-1C 24
5-19-08
Occupational doses received as a result of radioactive material transportation performed by
other than the DOE or a DOE contractor, shall be considered to the extent practicable when
determining compliance with the occupational dose limits (10 CFR 835.1(c)). Occupational
doses received by DOE or DOE contractor employees while conducting radioactive material
transportation shall be considered when determining compliance with the occupational dose
limits.
Section 26
3.3 RPP Functional Elements
This section identifies the programmatic functional elements of a comprehensive RPP. For
each element, the following table identifies the applicable regulatory provisions, contractual
requirements, and recommended guidance document(s) which are useful in achieving
compliance with these provisions.
DOE G 441.1-1C 25
5-19-08
Functional Element Regulatory Provision Contractual/Guidance
Document
1. Organization and Administration 10 CFR 835, Subpart B Chapter 3.0 of this Guide
2. ALARA Program 10 CFR 835.101(c), Subpart K Chapter 4.0 of this Guide.
3. External Dosimetry Program 10 CFR 835.401 (a), 402(a), (b) Chapter 6.0 of this Guide.
4. Internal Dosimetry Program 10 CFR 835.401(a), 402(c), (d) Chapter 5.0 of this Guide.
5. Area Monitoring and Control
a. Area Radiation Monitoring 10 CFR 835.401(a) Chapter 6.0 of this Guide.
b. Airborne Radioactivity Monitoring 10 CFR 835.209, 401(a), 403 Chapter 10.0 of this Guide.
c. Contamination Monitoring and
Control
10 CFR 835.401(a), Subpart L Chapter 11.0 of this Guide.
d. Instrument Calibration and
Maintenance
10 CFR 835.401(b) Chapter 9.0 of this Guide.
6. Radiological Controls
a. Radiological Work Planning 10 CFR 835.501(d), 1001(b),
1003
DOE-STD-1098-2008,
RADIOLOGICAL CONTROL
b. Entry and Exit Controls 10 CFR 835, Subpart F Chapter 7.0 of this Guide.
c. Radiological Work Controls 10 CFR 835, Subpart F, 1003 Chapter 7.0 of this Guide.
d. Posting and Labeling 10 CFR 835, Subpart G Chapter 12.0 of this Guide.
e. Release of Materials and
Equipment
10 CFR 835.1101 Chapter 11.0 of this Guide.
f. Sealed Radioactive Source
Accountability and Control
10 CFR 835, Subpart M Chapter 15.0 of this Guide.
7. Emergency Exposure Situations 10 CFR 835.1301, 1302 DOE O 151.1-1C,
Comprehensive Emergency
Management System (DOE
2005c)
8. Nuclear Accident Dosimetry 10 CFR 835.1304 Chapter 6.0 of this Guide.
9. Records 10 CFR 835, Subpart H Chapter 13.0 of this Guide.
10. Reports to Individuals 10 CFR 835, Subpart I Chapter 13.0 of this Guide.
11. Radiation Safety Training 10 CFR 835, Subpart J Chapter 14.0 of this Guide.
12. Limits for the Embryo/Fetus 10 CFR 835, Subpart C Chapter 8.0 of this Guide.
DOE G 441.1-1C 26
5-19-08
Appendix 3.A
PREPARATION, REVIEW, AND APPROVAL OF
RADIATION PROTECTION PROGRAMS
3.A 1. PREPARATION OF RPPs
The RPPs detail how the site, facility, or activity has met or will meet the requirements of 10
CFR 835. The format for the RPP is not specified. This flexibility will permit the RPP submitting
organizations to take advantage of pre-existing documents. The following sections describe the
minimum content expected in RPPs.
Note: The term “Operations Office” is used throughout this
document. Where it is used, the term “Field Office,” “Site Office” or the
term “Area Office,” as appropriate, should be substituted where there is
no Operations Office.
3.A 1.1 RPP SUMMARY
Each RPP should contain a summary section in the front to allow DOE management and
reviewers to quickly assess the more significant information contained in the RPP. The summary
should identify the following minimum information:
(1) Any requests for exemptions contained in the RPP;
(2) The total additional funding required to meet the commitments of the RPP and the
expected sources of funding by fiscal year;
(3) Any significant new programs or activities needed to meet the requirements;
(4) Any significant impacts to other programs or activities not included in the RPP;
Section 27
(5) Any constraints to implementing the RPP; and
(6) Those areas where there is currently full compliance with the requirements.
3.A 1.2 GENERAL INFORMATION
The RPP should include general information which: (1) identifies that the RPP addresses the
requirements of 10 CFR 835; (2) identifies whether the RPP is the initial submittal or a revision;
(3) identifies the facilities or activities, missions, and organizations involved; and (4) briefly
discusses the content and format of the RPP.
3.A 1.3 APPLICABILITY OF REGULATORY REQUIREMENTS
The RPP should identify the specific facilities or activities covered by the RPP. Any
determination that a specific requirement is not applicable to the facilities or activities
addressed in the RPP should be documented in the RPP to ensure that the determination
is clearly communicated. DOE approval of the RPP will constitute agreement with
applicability statements contained therein.
DOE G 441.1-1C 27
5-19-08
Applicability statements may not be used to provide relief where the requirements
are clearly stated to be applicable in 10 CFR 835. Relief from 10 CFR 835 can only be
granted by an approved exemption granted in accordance with 10 CFR Part 820, Subpart E
as discussed in Section 3.A 1.8 of this technical document.
The information provided in the plan should clearly identify which of the following
three categories applies to each requirement for a given facility, site, or activity:
(1) The requirement is applicable and the RPP defines the actions and schedules for
compliance;
(2) The requirement is applicable and an exemption is being requested; or
(3) The requirement is not applicable for the reasons documented in the RPP.
The RPP should also identify any requirements that are only partially applicable, the
limits of the applicability, and the reasons for the limitation.
Individuals should contact the appropriate Operations Office to assist with any needed
clarification of applicability statements. The Operations Office should contact the Office
of Health and Safety for any needed technical clarifications or the Office of the General
Counsel for legal interpretations of 10 CFR 835.
For example, the DOE General Counsel responded to a question concerning what
activities are intended to be included within the scope of the 10 CFR 835.1(b)(3) exclusion.
In response, General Counsel Ruling 95-1 stated "This exclusion is drafted narrowly to
cover only those activities necessary to prevent an accidental or unauthorized nuclear
detonation (that is, where the component parts of a nuclear weapon have been
assembled in a manner such that a nuclear detonation could take place)."
There are potential situations where a DOE protective force individual could receive
an exposure to ionizing radiation in excess of the 10 CFR 835 limits (or be in
noncompliance with other 10 CFR 835 provisions) as a result of emergency actions taken
to protect nuclear or other material from theft or diversion. Per General Counsel Ruling
95-1, these situations would not be included within the scope of the 10 CFR 835.1(b)(3)
exclusion. However, these situations, if conducted as part of an emergency response to a
threat to nuclear or other material, would likely fall within the scope of 10 CFR 835.3(d)
which states that "Nothing in this part shall be construed as limiting actions that may be
necessary to protect health and safety."
3.A 1.4 GUIDES AND TECHNICAL STANDARDS
Section 28
The RPP should identify the guides and technical standards that are to be adopted as the
means to meet 10 CFR 835. The use of guides and technical standards is not required; however,
it is encouraged for the following reasons:
DOE G 441.1-1C 28
5-19-08
(1) The use of previously approved methodologies will streamline the review and approval
process; and
(2) The use of guides and technical standards will enhance the consistent and successful
implementation of requirements across the DOE complex.
The implementing organization should consider methods and guidance from guides and
technical standards when developing the RPPs; however, alternative methods that achieve
equivalent or better results are acceptable. When an implementing organization identifies an
alternate way to implement the requirements, a reasonable opportunity will always be provided
to demonstrate compliance with the requirements using the alternate method. Demonstration
of compliance does not require an organization to address the differences between the
alternate method and the method in the guide or technical standard unless the comparison is
necessary to demonstrate acceptability.
When guides or technical standards are used, the RPP should indicate if they are adopted in
their entirety or adopted with exceptions. The exceptions, if any, should be specifically noted.
Methodologies and guidance that are adopted with exceptions will be reviewed on a
case-by-case basis.
The adopted guides and technical standards should be listed either by:
(1) Including a list of applicable guides and technical standards in the RPP, or
(2) Incorporating a list of guides and technical standards by reference.
Commitments in an RPP to meet all or parts of guides and technical standards are
enforceable as part of the RPP.
3.A 1.5 RESOURCE ASSESSMENT
New RPPs should contain an estimate of the additional life cycle costs to implement 10
CFR 835. Revised RPPs may contain an estimate of the change in life cycle costs associated
with the revision, if the change in life cycle cost is significant. The goals of this element of
the RPP are as follows: (1) to communicate the expected new costs of implementation to
DOE management for the purposes of budget planning and prioritization; (2) to identify the
need to explore more cost effective means of achieving compliance; and (3) to identify cases
where exemptions should be requested on the basis of insufficient benefit versus the
expected implementation costs. Identification of required resources should also serve to
open a dialogue between DOE and the RPP submitting organization on adjusting costs and
activities to the available resources.
When performing the assessments, the estimator should consider monetary costs, as well as
non-monetary resource considerations such as the limited availability of special job capabilities
(e.g., health physicists). The assessment should (1) be guided by available quantitative and
qualitative information; (2) reflect the current status of plant conditions, configurations, and
DOE G 441.1-1C 29
5-19-08
processes; (3) consider the availability of materials and resources; and (4) consider any other
information that is relevant to the radiation protection requirements.
Section 29
RPP submitting organizations should seek to achieve the broadest consistency in the
methods used to evaluate the resource requirements so that the assumptions, evaluations, and
results of the assessment can be objectively compared with the equivalent parameters of other
resource assessments. This will assist DOE and RPP activity management to determine priorities
for the use of funding. All assumptions and estimates should be made using the best available
knowledge and information.
After evaluating the resource impacts, consideration should be given if a more cost-effective
means of achieving the intent of the requirement is available. As a minimum, the use of more
cost-effective methods of compliance, or exemptions (see section 3.A 3.1.6.7 of this
attachment), should be considered whenever the resource expenditures necessary to meet a
requirement are not commensurate with the expected safety improvements. One of the criteria
for granting an exemption to a nuclear safety requirements is that the requirement results in
resource impacts which are not justified by safety improvements. In the past DOE has granted
exemptions on this basis for such topics as radiological postings and recording tritium intakes,
see http://www.eh.doe.gov/whs/rhmwp/exemption.html.
There should be limited effort used to develop the resource assessments to only that level
of detail necessary to achieve the goals of the assessment as stated above.
3.A 1.6 PRIORITIZATION
The RPP should include a discussion of the prioritization process used to integrate the
proposed activities into a facility or site schedule of activities. The prioritization process is to be
used to develop the proposed schedules and should be sufficiently flexible to accommodate
changes at later dates.
The prioritization process should consider available information from safety analyses and
other sources and give primary attention to controlling and reducing risks to the public, the
environment, and the workers to an acceptable level. It should also consider other factors such
as mission needs, outage schedules, and external regulations.
The prioritization process should be selected in consultation with the applicable DOE
Operations Office and Program Offices to ensure that the prioritization of efforts meets DOE
expectations. The prioritization schedule should tie budgets to schedules.
3.A 1.7 MILESTONES AND SCHEDULES
Per 10 CFR 835.101(f), the RPP must identify proposed milestones with achievable schedules
developed in accordance with the prioritization process identified in the RPP (see Section 3.A 1.6
above). In developing the schedules, consider the resources available to support the work, as
well as any major work reductions or schedule changes in other areas that will be required in
order to meet the proposed schedules. The RPP should identify major impacts to activities or
commitments outside the scope of the RPP that will be caused by the proposed additional
activities.
DOE G 441.1-1C 30
5-19-08
Schedules should be developed using the best information available with any assumptions
on availability of resources (monetary or non-monetary) clearly stated. The milestones and
schedules will be enforceable commitments upon approval of the RPP. Schedule commitments
should be firm commitments and consequently, should not be listed as contingent on funding.
Thus, it is essential that line program representatives participate in the review and approval of
RPPs that involve additional funding needs. Following approval of the RPPs, DOE has a
responsibility to provide appropriate funding to support the RPP schedules, the RPPs should be
revised to reflect the new schedules supported by funding (provided any schedules specifically
prescribed in the DOE requirements documents are met or schedule exemptions are approved).
Such revisions should be submitted to DOE for review and approval.
Section 30
Alternatively, RPP developers may consider requesting an exemption for unfunded
activities, if the criteria for granting an exemption are met (see Section 3.A 1.8 of this
attachment).
3A 1.8 EXEMPTIONS
Exemptions are to be requested whenever relief is sought from an applicable DOE
requirement. The RPP should clearly identify any exemptions that have been approved or are
being requested from the subject requirements. The organization conducting RPP activities may
submit requests for exemptions as part of the RPP provided that they relate to the same
requirements. Requests for exemption that are submitted as part of the RPP should be
identified in the RPP summary for early recognition. Early identification of exemption requests
is important because they may need to follow a separate review and approval process.
The provisions for requesting and granting exemptions to rules are stated in 10 CFR Part
820, Subpart E, Exemption-Relief.
3.A 2 SUBMITTAL OF RPPS
Per 10 CFR 835.101, RPPs must be submitted to the designated DOE point-of-contact within
the schedule specified in 10 CFR 835.
Normally, the RPP is submitted to a point-of-contact located in a DOE Operations Office.
The Operations Office point-of-contact should date stamp the receipt of the RPP.
Contact the Operations Office point-of-contact in advance of the submittal date to
determine the number of copies to be submitted. Documents that are incorporated by
reference should be submitted with the RPP unless other arrangements are made with the
Operations Office point-of-contact. In addition, if the RPP is not a stand-alone document (able
to be reviewed independent of other documents), contact the Operations Office
point-of-contact prior to submittal of the RPP to discuss which supporting documents are to be
transmitted with the RPP or made available for onsite review.
Also see section 3.A 4 below for additional submittal requirements for final RPPs.
3.A 3. REVIEW AND APPROVAL OF RPPs
DOE G 441.1-1C 31
5-19-08
3.A 3.1 REVIEW AND APPROVAL PROTOCOL
The Department’s protocol for review and approval of RPPs is described below. The
protocol defines the roles, interfaces, and responsibilities of Department organizations with
respect to review and approval of RPPs. Organizations who prepare the RPPs and the DOE
organizations responsible for review and approval of the RPPs should have a shared vision of
what should be in the completed RPPs before submission of the RPP to DOE. In order to ensure
this shared vision and the development of successful RPPs, early and continual dialogue
between the RPP submitting organization and the Review Team is essential. This dialogue
should begin well before the RPP is submitted to DOE. The process described below was built
on the lessons learned in similar efforts and was designed to facilitate that dialogue.
Because review and approval of the RPPs will often involve multiple Departmental
organizations, the review and approval process should provide for coordination, consistency of
review, and resolution of issues among those offices. In addition, the review and approval
process should address both the technical adequacy of the proposed RPPs and the
programmatic responsibilities (i.e., funding and mission). These responsibilities will require
additional coordination within the Department as they may reside in different organizations.
Section 31
The review and approval process should be sufficiently flexible to accommodate the
subjects addressed by 10 CFR 835 and adequately structured to permit efficient completion of
the review and approval within the 180 days [See 10 CFR 835.101(i)]. Table 1, at the end of this
attachment, provides recommended time periods to meet this 180-day requirement.
In the review and approval process, the Operations Office should be responsible for
coordination between the RPP submitting organization and the Department’s Headquarters
staff. This focused interface will ensure consistency in the information provided to the RPP
submitting organization and allow interaction with a single point-of-contact. In addition, the
Operations Office should be responsible for coordinating PSO (Program Secretarial Officer)
approvals. It should be noted that this attachment contains a detailed protocol. However,
individual steps may be modified to or eliminated, based on local conditions, as long as the
process involves appropriate review and approval. For example, approval authority may have
been delegated to the Manager of the Field Element (or lower), which would obviate the need
for specific PSO approval
A RPP Review Team should be formed for each RPP to conduct the review of the RPP. The
Review Team members should include DOE Headquarters and Field Operations personnel with
technical expertise and coordinating responsibility for program decisions (e.g., funding,
schedule). Operations Office personnel should serve as points-of-contact and Review Team
Leaders for RPP reviews applicable to their sites. Individual participation in Review Team
activities will vary in level of effort and time frame based on review and approval needs.
The Operations Office point-of-contact plays a key role in coordinating all RPP review and
approval activities between DOE Headquarters and the RPP submitting organization.
The process for the development, review, and approval of RPPs is discussed below. The
provisions of 10 CFR 835.101(i) state that “an initial RPP or an update shall be considered
DOE G 441.1-1C 32
5-19-08
approved 180 days after its submission unless rejected by DOE at an earlier date.” See Table 1
for a typical schedule of activities to meet this provision.
3.A 3.1.1 Identifications of Responsible Review Staff
3.A 3.1.1.1 Points-of-Contact
Each Operations Office Manager should identify a point-of-contact for the RPP. The
Operations Office point-of-contact should be the primary interface for all activities associated
with the development, submittal, review, and approval of the RPPs. The Operations Office
point-of-contact should also be the Review Team Leader.
The Review Team Leader should coordinate assignment of Review Team members with the
PSOs and the Operations Office.
3.A 3.1.1.2 RPP Review Teams
As discussed in the previous paragraph, the Operations Office point-of-contact should
normally be the Review Team Leader. The Operations Office Manager may provide additional
team members and technical assistance as necessary. In addition, each affected PSO should
identify the Program Office representatives for each Review Team to the Review Team Leaders.
The PSO may assign multiple reviewers to a single site or a single reviewer.
3.A 3.1.2. Review Planning
3.A 3.1.2.1 RPP Guide
Each responsible PSO should prepare an RPP Guide that defines DOE’s specific technical and
programmatic expectations for the RPPs internal to their organization. The guide should include
Section 32
the following types of information: (1) criteria and/or checklists of items to be considered during
the review, (2) approaches to key issues, (3) direction on use of existing RPPs and approvals, (4)
review and approval authorities, and (5) specific issues relating to Headquarters or Operations
Office review responsibilities. The guide should be as brief as possible, should be user friendly,
and should not repeat general guidance available in other guidance documents such as this
attachment. The PSO should provide assistance and/or training to the Review Teams on the use
of the guide.
3.A 3.1.2.2 Implementation Action Plan
For each RPP, the Review Team Group should prepare an Implementation Action Plan that
defines the Review Team activities, priorities, and schedule. A copy of the plan should be
provided for information.
3.A 3.1.2.3 Responsibility and Interface Matrix
The PSO should prepare and maintain a matrix that identifies the Review Team Leader,
Review Team members, and DOE programmatic and technical contacts for each RPP.
DOE G 441.1-1C 33
5-19-08
3.A 3.1.3 Meetings, Conference Calls, and Status Reports
3.A3.1.3.1 Initial Site Meeting
The Review Team should meet with the RPP submitting organization at the earliest
feasible date to discuss the basic expectations for implementation of the DOE requirements
document and to discuss any issues that might impact the timely and acceptable completion
of the RPP. Issues to be discussed should include (1) how to best use existing plans or other
information in developing the RPP; (2) potential exemptions; (3) plans and schedules for
ongoing interactions; and (4) funding sources for new activities identified as necessary to
come into compliance. The Operations Office point-of-contact has primary responsibility for
planning and coordinating this meeting.
3.A 3.1.3.2 Status Meetings
Periodic status meetings should be held with the RPP submitting organization to fully
discuss all elements of the proposed RPPs that could affect the acceptability of the RPPs.
3.A3.1.3.3 Periodic Conference Calls
The Operations Office point-of-contact should coordinate regular conference calls with the
RPP submitting organization and the Program Offices to address and resolve issues as they arise.
As necessary, site or headquarters meetings should be held to resolve difficult issues. The
Operations Office point-of-contact has primary responsibility for coordinating phone
conferences, as well as necessary meetings to resolve issues.
3.A 3.1.4 Submittal and Distribution of RPPs
As discussed in Section3.A 2 of this attachment, RPPs should be submitted directly to the
Operation Office point-of-contact. The Operations Office point-of-contact should transmit a
copy of the RPP to the Review Team members and a copy of the transmittal memorandum to
the affected PSOs within four working days of the receipt of the RPP. The transmittal
memorandum should identify the required date for completing the review.
3.A 3.1.5 Review
3.A 3.1.5.1 Review to Review Teams
RPPs should be reviewed by an integrated Review Team with Program and Operations Office
representatives, as discussed in Section3.A 3.1.1.2 above. Program Office team members and
their contacts should, as a minimum, participate in the review of issues involving funding,
missions, schedules, priorities, and exemptions. The Review Team Leader should facilitate
resolution of unique or difficult issues not addressed in the RPP Guide.
Section 33
Review Team members should assist the RPP submitting organization in clearly
understanding what actions or changes are necessary to result in an acceptable RPP. DOE
comments and feedback should be routed through the Review Team Leader to ensure
consistent feedback. The Review Team Leader should also be responsible for resolving conflicts
prior to communication with the RPP submitter.
DOE G 441.1-1C 34
5-19-08
All reviewers should expedite their reviews to allow closure on an acceptable RPP as early as
possible.
3.A 3.1.5.2 Delegated Approval Authority for RPPs
The PSO may delegate the authority to approve specific RPPs. Any such delegation should
be provided in writing to the designee and documented in the Functions, Responsibilities, and
Authorities (FRA) document for that organization.
Wherever the authority to approve an RPP has been delegated to the Operations Office by
all of the affected PSOs, the Operations Office may choose to have the Review Team consist
entirely of Operations Office personnel provided any technical and programmatic requirements
can be handled by the designated team.
Per 10 CFR Part 820, Subpart E, the authority to approve exemptions to 10 CFR 835 cannot
be delegated.
3.A 3.1.6 Approval
3.A 3.1.6.1 Approval Recommendations by the Review Team
The Review Team Leader is responsible for ensuring that the Operation’s Office Manager
receives the Review Team’s final recommendation for approval within 145 days after receipt of
the RPP. That recommendation should either endorse acceptance of the RPP as submitted (or
changed through negotiations during the review process) or, if issues cannot be resolved,
provide recommendations regarding specific additional commitments or changes to be
incorporated in the RPP.
3.A 3.1.6.2 Operations Office Review of the Review Team Recommendations
The Operations Office Manager, or equivalent, should review the recommendation of the
Review Team and either endorse the recommendation or provide specific recommendations for
an acceptable RPP. The Operations Office Manager is responsible for ensuring that the PSO
receives the recommendations of the Review Team along with any recommendations from the
Operations Office no later than 159 days after receipt of the RPP [with information copy to the
affected CSOs [Cognizant Secretarial Officer)].
In some cases involving multiple PSOs, approval authority may be delegated by one or more
PSOs, but not all PSOs. In such cases, the Operations Office Manager should coordinate the
remaining approvals with the PSOs.
For cases in which the approval authority has been delegated by all affected PSOs to the
Operations Office Manager, the Operations Office Manager should skip to step 3.A 3.1.6.4
Approval Letter, below.
3.A 3.1.6.3 PSO Approval Memorandum
DOE G 441.1-1C 35
5-19-08
In order to ensure the Operations Office has a week to transmit the approval or disapproval
of the RPP before it becomes automatically effective 180 days after receipt of the RPP by DOE,
each affected PSO should indicate approval or disapproval of the RPP in a memorandum to the
Operations Office within 173 days of receipt of the RPP by DOE.
3.A 3.1.6.4 Approval Letter
The Operations Office Manager should transmit the approval memorandum by letter to the
RPP submitting organization no later than 180 days after receipt of the RPP by DOE.
3.A 3.1.6.5 Imposition of RPPs
Section 34
The Review Team will endeavor to resolve any issues identified during the review process. If
conflicts exist which cannot be resolved, the Department may exercise its authority [see 10 CFR
835.101(b)] to modify proposed RPPs to include those actions and schedules that the
Department finds appropriate for achieving full compliance in a reasonable and timely manner.
In such cases, the PSO approval memorandum should be replaced with a memorandum
imposing a revised RPP. The revised RPP should be transmitted to the RPP submitting
organization by the Operations Office Manager. The RPPs may be renegotiated at a later date,
but until it is replaced by another approved RPP, it will be the enforceable basis for
implementation of 10 CFR 835.
3.A 3.1.6.6 RPPs which are not Approved by Final Date
Per 10 CFR 835.101(I), RPPs which are not approved within the approval period specified in
the DOE requirements document should be considered to be approved unless another RPP is
imposed by the Department. These RPPs may be renegotiated at a later date, but until they are
replaced by another approved RPP, they will be the enforceable basis for implementation of 10
CFR 835.
3.A3.1.6.7 Approval of RPPs Containing Exemption Requests
RPPs may contain requests for exemptions. When they do, the requests may be granted in
the approval memorandum for the RPP, provided that all of the requirements for processing
exemptions are met, including the approval of the DOE Headquarters official designated by
10 CFR Part 820 Subpart E. When exemptions are approved as part of an RPP, the approval
document should state how the provisions of 10 CFR Part 820, Subpart E were met.
Alternatively, exemptions may be approved separately and referenced in the RPP approval
letter.
Upon submittal of the RPPs, the Review Team Leader should determine if any exemption
requests submitted in the RPPs need to be reviewed and approved separate from the RPPs.
Where separate review and approval is necessary, the Review Team Leader should alert the PSO
Review Team representatives to initiate a separate and expeditious review of the exemption
requests.
The provision in 10 CFR 835.101(i) that states that RPPs are considered approved 180 days
after submission, does not apply to exemptions.
DOE G 441.1-1C 36
5-19-08
Approval of an RPP pending granting of an exemption does not constitute or imply approval
of the exemptions contained therein.
3.A 3.2 DISTRIBUTION OF COPIES OF THE FINAL RPP
The Operations Office Manager should be responsible for distributing approved RPPs (if
changed from the originally submitted RPP) to the Office of the Docketing Clerk (in the Office of
Price Anderson Enforcement) and to the affected PSOs. Copies of approved RPPs transmitted to
the Office of the Docketing Clerk should include both a hard copy and an electronic copy. As
required by 10 CFR Part 820, the Office of Docketing Clerk will maintain a file of enforceable
actions based upon rule violations and noncompliance with RPPs.
3.A 3.3 REVIEW RESPONSIBILITIES
The Review Team should determine if the RPP provides an acceptable method to meet 10
CFR 835. The Review Team should also determine if the RPP adequately addresses the elements
discussed in Section 3.A 1 of this attachment (Preparation of RPPs). RPP submitting
organizations are encouraged to use the methodologies contained in this Guide for
implementation of 10 CFR 835 where they are reasonable and economical; however, one may
Section 35
elect to propose an alternate way to meet the requirements. In cases where an alternate
method is proposed, the Review Team should evaluate the proposed method to ensure that it
will be adequate to meet the requirements and provide a comparable level of safety.
The Review Team should verify that the RPP provides sufficient detail to permit DOE to
measure the progress towards meeting the DOE requirements.
The Review Team should also ensure that (1) the projected budget and schedule
information contained in the RPP is reasonable and consistent with the funding projects, (2) the
prioritization of efforts meets the DOE expectations, (3) the proposed milestones and schedules
will meet DOE needs, (4) the applicability of the requirements is correctly identified, and (5) the
compensatory actions are acceptable.
The Review Team should expect to see significant variations in the level of detail and size of
individual RPPs because of the diversity of types, sizes, and missions of DOE facilities. In order
to facilitate timely reviews and agreements on complex RPPs, the members of the Review Team
should visit the site and/or facility and have frequent communication during both the
preparation and the review of the RPP.
3.A 3.4 APPROVAL RESPONSIBILITIES
DOE approval of the RPP constitutes acceptance by the PSO that:
(1) The proposed activities represent an acceptable method to meet the requirements;
DOE G 441.1-1C 37
5-19-08
(2) The resources identified in the RPP are necessary and sufficient to ensure completion of
the activities contained in the RPP and are expected to be available to support the
proposed schedules;
(3) The proposed milestones and schedules are acceptable;
(4) The applicability of the requirements is correctly identified; and
(5) The identified compensatory actions are acceptable.
3A 4. REVISIONS TO RPPs
The RPPs will probably need to be revised and updated during the life cycle of the site,
facility, or activity. Approved RPPs should be revised as needed to reflect the addition or
deletion of other work at a facility or other factors that affect the ability to meet the approved
schedule, such as prospective changes in the level of funding or assumptions regarding the
availability of materials and other resources. The provisions in 10 CFR 835.101(h) contain
conditions under which RPPs may be revised without prior approval from DOE. In such cases,
submit the revised RPP to DOE within 30 days of the effective date of the RPP. All other changes
to RPPs should be reviewed and approved by DOE prior to the effective date of the change.
Revised RPPs should be submitted in a timely manner for DOE approval (at least 180 days before
the change is to be effective), along with justification for the revision. As noted previously,
proposed revisions will be considered approved 180 days after submittal to DOE, unless they are
approved or rejected by DOE.
The changes to the RPP should be clearly indicated (e.g., sidebars) to facilitate timely review.
Revised RPPs are to be submitted to DOE in the manner described in this section and reviewed
and approved in the manner described in section 3.A.3 above.
Any changes to RPPs which will result in a requirement not being met, require an approved
exemption.
3.A 5. EXTENSIONS TO THE SUBMITTAL SCHEDULE FOR RPPS
Extensions to the schedule for submitting an RPP will generally require an exemption
processed in accordance with 10 CFR Part 820, Subpart E, and approved by the Secretarial
Section 36
Officer responsible for environment, safety and health matters (i.e., the Chief Health, Safety and
Security Officer).
3.A 6. IMPLEMENTATION TRACKING
Following approval of the RPP and during the implementation process, the DOE Operations
Office should oversee progress in meeting the commitments in the RPP (for example, schedules,
milestones, and costs) and maintain a dialogue on any problems that arise.
3.A 7. INCORPORATION BY REFERENCE
DOE G 441.1-1C 38
5-19-08
The RPP submitting organization may choose to incorporate information into the RPP by
referencing all or selected portions of other documents. In such cases, the portions of the
referenced documents that are incorporated into the RPP are also subject to the provisions of
this Guide and attachment.
However there are situations when a citation or reference is used to indicate the origin of
some of the text in a document. For example, in this Guide, 10 CFR 835 is cited to indicate the
basis for statements containing the word “should” or “shall” (i.e., requirements). Consequently,
the RPP submitting organization should clearly indicate which documents (or portions of
documents) are considered part of the RPP commitments. The RPP submittal should maintain a
file of all documents incorporated by reference and should make non-DOE documents available
to DOE upon their request. See also section 3.A 1.2 above for submittal criteria.
Table 1. TYPICAL SCHEDULE FOR REVIEW AND APPROVAL OF RPPS
Submittal of RPP to Operations Office
0 days
Operations Office send RPP to Review Team/PSOs/Environment, Safety and Health
4 days
Review Team sends recommendation to Operations Office Manager
145 days
Operations Office Manager sends recommendation to PSO*
159 days
PSO Approval to Operations Office*
173 days
Operations Office Manager issues approval/disapproval to RPP submitting organization
180 days
*If approval authority not delegated to the Operations Office by the PSO.
DOE G 441.1-1C 39
5-19-08
4.0 ALARA
In promulgating 10 CFR 835, DOE considered alternatives to reduce the risk from radiation
exposure to workers that included retaining the current occupational dose limits, reducing these
limits, and emphasizing efforts to maintain occupational doses As Low As is Reasonably
Achievable (ALARA). After considering public comments on this issue, DOE elected to emphasize
the ALARA process to maintain occupational dose for DOE and contractor employees as far
below the current regulatory occupational dose limits as reasonably achievable. Adopting the
ALARA process in DOE occupational radiation protection regulations also provides consistency
with recommendations provided in the President’s Radiation Protection Guidance to Federal
Agencies For Occupational Exposure (EPA 1987), which endorsed the ALARA process.
The importance of the ALARA concept was further stressed in DOE P 441.1, DOE
Radiological Health and Safety Policy (DOE 1996), which states:
It is the policy of the Department of Energy to conduct its radiological operations
in a manner that ensures the health and safety of all its employees, contractors, and
the general public. In achieving this objective, the Department shall ensure that
radiation exposures to its workers and the public and releases of radioactivity to the
environment are maintained below regulatory limits and deliberate efforts are taken
to further reduce exposures and releases as low as reasonably achievable. The
Department is fully committed to implementing a radiological control program of
the highest quality that consistently reflects this policy.
Section 37
10 CFR 835 requires formal plans and measures for maintaining occupational exposures
ALARA as part of the documented radiation protection program (RPP). Measures include
incorporating ALARA considerations into the design of new facilities and modifications of
existing facilities, as well as activities that pose the potential for significant occupational dose.
Additionally, administrative controls are addressed as measures which supplement engineered
controls and are integrated into the work planning process. Record keeping and training
requirements related to ALARA are also specified. This chapter of this Guide discusses
acceptable methods for implementing the ALARA process provisions in 10 CFR 835.
Due to the complex nature of many DOE activities, a combination of radiological and
non-radiological hazards may be encountered. Identification of non-radiological hazards is
critical to the ALARA process, because efforts to apply the ALARA process may inadvertently
increase risks from non-radiological hazards. An integrated safety management approach that
optimizes worker protection from all hazards should be considered in the ALARA process for a
given DOE activity.
4.1 Implementation Guidance
Subpart B of 10 CFR 835 requires that a DOE activity shall be conducted in compliance with
an RPP approved by DOE [10 CFR 835.101(a)]. The content of the RPP shall be commensurate
with the nature of the activities performed and shall include formal plans and measures for
applying the ALARA process to occupational exposure [10 CFR 835.101(c)]. Subpart K of the rule
provides requirements for design and control for maintaining radiation exposures ALARA. The
primary methods used for maintaining radiation exposures ALARA in controlled areas shall be
DOE G 441.1-1C 40
5-19-08
engineered controls; administrative controls may be used as supplemental features and for
specific activities where engineered controls are impractical [10 CFR 835.1001(a) and (b)]. The
rule specifies objectives for design of new facilities or modifications to existing facilities
(10 CFR 835.1002) and the integration of work controls during routine operations
(10 CFR 835.1003). Additionally, the rule requires documentation of the actions taken to
maintain occupational exposures ALARA, including actions required by the RPP, as well as facility
design and control actions [10 CFR 835.704(b)].
Guidance on complying with the training requirements of 10 CFR 835.103 and 835.901 is
provided in Chapters 3 and 14 of this Guide.
This chapter provides the basic guidelines for conducting an occupational ALARA program.
It includes the requirements and guidance for developing, implementing, documenting, and
providing feedback and lessons learned for improving the program to reduce individual doses to
levels that are ALARA.
4.2 ALARA Programs
4.2.0 Formal Plans and Measures
The method of implementing an ALARA program is highly dependent on the complexity and
magnitude of potential radiological hazards associated with the DOE activity. The elements of
an effective ALARA program should be identified in a formal ALARA plan or procedure. The RPP
shall clearly identify the ALARA plans and measures employed by the DOE activity
[10 CFR 835.101(c)]. The degree of formality and the level of detail contained in these plans and
measures and other pertinent documentation should be commensurate with the magnitude of
the radiological hazard associated with the DOE activity. A DOE activity with higher collective
dose and/or potential for significant occupational doses should have more detailed ALARA
documentation than an activity with low collective doses and/or potential for significant
occupational doses. ALARA plans and measures should address the following elements at a level
commensurate with the radiological hazards associated with the DOE activity:
Section 38
Policy and Management Commitment: Establish commitment and participation of all
line management and all levels of the work force;
ALARA Training: Require ALARA training for all employees, including managers involved
with any aspect of radiological operations. Guidance is provided in Chapters 4 and 14 of
this Guide and the RCS;
Plans and Procedures: Consider administrative and engineered controls and
optimization methods during work procedure development to assure that the ALARA
process is fully integrated into the development of operational/experimental plans,
procedures, and protocols. Document formal plans and measures for applying the
ALARA process to occupational doses;
Internal Assessments/Audits: Conduct comprehensive internal reviews, audits, and
evaluations periodically and report the results to the highest levels of site management.
Guidance is provided in Chapter 3;
DOE G 441.1-1C 41
5-19-08
ALARA Design Review: Ensure the integration of appropriate methods and
considerations during the design phase to maintain occupational exposures ALARA
during subsequent construction, modification, and operation of the equipment or
facility;
Radiological Work/Experiment Administration and Planning: Implement controls and
use optimization methods to assure that occupational dose is maintained ALARA for
routine and special operations or experiments; and
Records: Maintain documents that demonstrate compliance and that the program is
adequately carried out. Guidance is provided in Chapter 13.
4.2.1 Policy and Management Commitment
Management commitment to ALARA, consistent with the DOE Radiological Health and
Safety Policy (DOE 1996), is a critical element in ensuring a successful ALARA program. This
commitment should take the form of a formal, written, policy statement from a high level of
corporate management, generally the senior site executive or company officer responsible for
radiological activities that cause the exposures. This commitment should hold all levels of
management and individual workers responsible for adhering to the company's ALARA policy. If
appropriate, union leadership endorsement of the ALARA policy should be considered.
Senior site and line management should demonstrate their support of the ALARA program
through direct communication, instruction, inspection of the workplace, and actions including:
management decisions that place ALARA considerations before cost or schedule
considerations (in accordance with numerical criteria; see section 4.2.5 below);
encouragement of and praise for workers who identify ALARA solutions;
support of the ALARA Committee; and
publication of ALARA success stories.
All site personnel should be made aware of management's commitment to ALARA and
radiological workers should be instructed on their responsibility to comply. Management’s
ALARA commitment statement should be periodically updated and reaffirmed.
4.2.2 ALARA Training
Specialized ALARA training should be developed for personnel who plan, prepare,
schedule, estimate, or engineer jobs that have the potential for significant radiological
consequences. The purpose of training these personnel in ALARA concepts and techniques
is to empower them to include ALARA considerations in the early phases of job planning and
engineering. This training should provide the basics of ALARA concepts and the use of
ALARA related equipment such as containment devices, shielding, ventilation, and special
Section 39
DOE G 441.1-1C 42
5-19-08
tools. Topics such as radiological waste minimization, application of decontamination
efforts, and basic contingency planning for mitigation of accidental spills and releases may
also be appropriate. DOE has developed specialized training material for these types of
positions in DOE HDBK 1110-2008, ALARA TRAINING FOR TECHNICAL SUPPORT PERSONNEL
(DOE 2008b).
Discipline-specific ALARA training may be appropriate for some organizations including:
operations, maintenance, engineering, production, and construction (craft workers). Chapter 3
provides additional guidance with respect to training for such individuals under 10 CFR 835.103.
Mock-up training may be appropriate for craft workers and others to prepare them for unique
and/or high dose jobs.
4.2.3 Plans and Procedures
10 CFR 835.101(c) requires that the content of each RPP be commensurate with the nature
of the activities performed and include formal plans and measures for applying the ALARA
process to occupational exposures. The RPP (approved by facility management and DOE) and
supporting procedures (approved by facility management) should describe the organization,
responsibilities, and method of operation of the ALARA program. These documents should be
reviewed and updated according to an established schedule. Chapter 3 provides additional
guidance with respect to procedures required under 10 CFR 835.104.
4.2.4 Internal Assessments/Audits
10 CFR 835.102 requires that internal audits of the RPP be conducted such that all functional
elements are reviewed no less frequently than every 36 months and shall include program
content and implementation. The ALARA program is one of these functional elements. Chapter
3 provides detailed guidance concerning internal audits. Management's responsibilities for
reviewing, auditing, and evaluating the ALARA program should be clearly documented. The
occupational ALARA program should be evaluated by an individual(s) or members of the ALARA
Committee with no direct responsibility for implementing the program.
4.2.5 ALARA Design Review
10 CFR 835.1001 requires that measures be taken to maintain radiation exposures in
controlled areas ALARA. The primary method used shall be engineered controls (e.g.,
confinement, ventilation, remote handling, and shielding); administrative controls shall be
incorporated only as supplemental methods and for specific activities where engineered
controls are demonstrated to be impractical (10 CFR 835.1001). 10 CFR 835.1003 further
requires that during routine operations, the combination of engineered controls and
administrative controls shall provide that the anticipated occupational dose to general
employees does not exceed regulatory limits and that the ALARA process is utilized for
personnel exposures to ionizing radiation. Engineered controls typically include features that
are used to control the work environment, such as permanent structures, systems, and controls,
including shielding, filtered ventilation systems, remote controls, containment devices, and the
DOE G 441.1-1C 43
5-19-08
use of designs and materials that facilitate operations, maintenance, and other activities. They
may also include controls (e.g., temporary shielding, confinement and ventilation systems) that
are typically used to facilitate short-term or emergent operations when the installed engineered
controls do not provide the desired level of protection. In addition to the engineered controls,
Section 40
initial consideration should be given to elimination or substitution of the hazards where feasible
and appropriate. This could include use of non-radioactive material or sources. Administrative
controls typically include controls that are implemented by the individual at the work site,
including written procedures, technical work documents, work authorizations, and other
controls that are used to guide individual actions in a manner that will facilitate implementation
of the ALARA process.
DOE has an approved set of directives concerning radiological design criteria for the design,
construction, operation, and decommissioning phases of its nuclear facilities. (See list below.)
The appropriate ALARA design features should be incorporated into modifications of existing
facilities and/or equipment and designs of new facilities and/or equipment as early as possible
in the engineering and design process. From early in the design phase and throughout the
project, a radiological engineer or representative of the radiation protection staff should be
assigned to the design team. This individual should ensure that reasonable radiological
considerations have been integrated into the design, construction procedures, proposed
operating procedures, and plans for decommissioning. Numerical criteria (e.g., dollars per rem
avoided) developed for site ALARA decisions should be used to determine those design features
that are reasonable. An individual with expertise in radiation protection, preferably from the
site staff, but at least familiar with the site program, should perform an independent ALARA
design review that includes the following elements:
review the general configuration of the facility and/or equipment, considering traffic
patterns, location of radiation areas, location and size of changing rooms, adequacy of
personnel decontamination facilities, location of fixed monitoring equipment, and
adequacy of space for anticipated operations, maintenance, production, research, and
decommissioning. Facility design and selection of materials shall include features that
facilitate operations, maintenance, decontamination, and decommissioning
[10 CFR 835.1002(d)]. The RCS provides additional guidance;
verify that radiological design criteria are consistent with applicable federal/state
regulations, recognized standards and guides, and with the following DOE directives
relating to radiological safety in design:
– 10 CFR 835;
– DOE O 458.1; Radiation Protection of the Public and the Environment (DOE
2011a);
– DOE P 441.1; Department of Energy Radiological Health and Safety Policy (DOE
1996)
DOE G 441.1-1C 44
5-19-08
– DOE O 420.2B, Safety of Accelerator Facilities (DOE 2004a);
– DOE 5480.30, Nuclear Reactor Safety Design Criteria (DOE 1993);
– DOE O 420.1B, Facility Safety (DOE 2005d);
– DOE O 413.3B, Program and Project Management for the Acquisition of Capital
Assets (DOE 2010b);
– DOE O 435.1, Radioactive Waste Management (DOE 2001b); and
– the RCS.
verify that the design of the confinement and ventilation systems provides the required
level of protection from airborne contamination, giving particular attention to patterns
of air flow and to the locations of air inlets, penetrations, and exhausts. Releases of
radioactive material to the workplace atmosphere should be avoided under normal
operating conditions and inhalation of such materials by workers should be controlled
to the extent reasonably achievable;
Section 41
evaluate and confirm the adequacy of specific control devices for reducing occupational
doses, including shielding, hoods, glove boxes, containments, interlocks, barricades,
shielded cells, decontamination features, and remote operations. External sources of
radiation in areas of continuous occupational occupancy (2,000 hours/year) shall be
maintained below an average of 0.5 millirem (0.005 mSv) per hour and as far below this
average as is reasonably achievable. For areas where occupancy differs from the above,
external dose rates should be ALARA and should be maintained at a rate so as not to
exceed 20% of the limits in 10 CFR 835.202;
verify that the design will be able to maintain personnel entry control for each
radiological area, commensurate with existing or potential radiological hazards
within the area, by using one or more of the methods listed in 10 CFR 835.501;
verify that each entrance or each access point to high and very high radiation areas will
have the control features required by 10 CFR 835.502; and
assess the adequacy of planned radiological monitoring and nuclear criticality safety
instrumentation and determine whether the proposed instrumentation is appropriate
for the expected types, levels, and energies of the radiation(s) to be encountered, and
whether it has sufficient redundancy and capability for operation under normal
operating conditions and during emergencies [10 CFR 835.401(b)].
The ALARA design review should have six discrete phases:
dose assessment;
DOE G 441.1-1C 45
5-19-08
review of projected radiological conditions against the trigger points or numerical
criteria established by management to initiate a review (e.g., creation of a new radiation
source or an increase in the dose rates from an existing source that causes increased
projected facility lifetime collective dose of greater than 5,000 millirem (50 mSv) or
annual collective dose of 1,000 millirem (10 mSv), from operations, maintenance,
production, research, inspection and decommissioning activities);
identification of the applicable radiological design criteria;
review of similar facilities, designs, and processes to assist in the selection of optimum
ALARA design features and less costly alternatives using approved numerical criteria;
and,
incorporation and documentation in the design package of features to reduce the:
exposure of personnel; spread of radioactive contamination; release of radioactive
effluent; and creation of radioactive waste; and
post-construction review of effectiveness of ALARA engineering features to provide
feedback to the design engineers and help refine the design process. The ALARA design
review should be conducted and documented in accordance with an approved
procedure and the design review package should be readily retrievable. Detailed
radiological design considerations are discussed in PNL-6577, Health Physics Good
Practices for Reducing Radiation Exposures to as Low as Reasonably Achievable (ALARA)
(PNL 1988a).
Optimization Methodology
Section 42
Optimization methods are required to assure that occupational exposure is maintained
ALARA in developing and justifying facility designs or modifications and physical controls.
Optimization methodology provides the technical and managerial basis for setting numerical
criteria for ALARA decisions in the design of facilities, development or review of work processes,
and the design/purchase of special tools and equipment. Selection of an appropriate cost
benefit factor for reducing occupational dose involves a judgment of the relative value of dose,
normally in terms of dollars per rem avoided. Additionally, guidance on optimization
methodology will also provide the basis for selection of trigger points or collective dose values
(facility lifetime, facility annual, job lifetime, one time job, etc.) above which an ALARA design
review or job review is appropriate. Numerical criteria for ALARA decision making should
include radioactive waste volume, radioactive effluent, contamination levels, and airborne
radioactivity levels. Optimization methodology has led to a multi-attribute analysis technique
which is discussed extensively in ICRP Publication 37, Cost-Benefit Analysis in Optimization of
Radiation Protection (ICRP 1982) and ICRP Publication 55, Optimization and Decision-making in
Radiological Protection (ICRP 1990).
At sites with significant collective dose, formally documented optimization methodologies
should be developed for ALARA reviews and decisions on implementation of ALARA efforts
should be developed. This may be on a site- or facility-specific basis. Application of
DOE G 441.1-1C 46
5-19-08
optimization methodologies to the ALARA process should lead to consistent, rational,
repeatable decisions as to which ALARA efforts are justifiable. The level of effort involved in
documenting ALARA decisions should be commensurate with the potential dose savings to be
realized. A detailed evaluation need not be made if its cost, including the cost of
documentation, outweighs the potential value of the benefits. The procedure used to evaluate
the "appropriateness" of dose-reduction and contamination minimization decisions should be
maintained. The RCS and PNL-6577 provide additional guidance on optimization methodologies.
4.2.6 Radiological Work/Experiment Administration and Planning
10 CFR 835.1003 requires that during routine operations, the combination of engineered
and administrative controls shall provide that the anticipated occupational dose to general
employees shall not exceed the limits established in 10 CFR 835.202 and that the ALARA process
is utilized for personnel exposures to ionizing radiation. Additionally, 10 CFR 835.501(d)
requires written authorizations to control entry into and perform work within radiological areas.
Often, these written authorizations take the form of radiological work permits (RWP) or
technical work documents (TWD) associated with jobs or experiments. These written
authorizations provide a convenient mechanism to integrate ALARA review of work tasks if the
requirement for ALARA review is embodied in the written authorization. Optimization
methodologies and appropriate radiological judgment should be used to develop numerical
criteria and/or trigger points for determining when a formal ALARA review of planned
radiological work activities is required. Once conducted, the completed ALARA review should be
incorporated into the written authorizations for the work activity.
Section 43
4.2.6.0 Job/Task/Experiment Reviews
A formal ALARA job/task/experiment review should be performed for work or experiments
with the potential to exceed the established numerical radiological criteria. The following are
examples of criteria that should trigger a formal ALARA review.
the estimated individual or collective dose is greater than pre-established criteria.
the predicted concentrations of airborne radioactivity could exceed pre-established
criteria (such as 100 times the DAC values provided in 10 CFR 835 Appendices A and C).
there is potential for significant radiological exposures.
the removable contamination in work areas could exceed pre-established criteria (such
as 100 times the values provided in 10 CFR 835 Appendix D).
individuals will enter areas where exposure rates could exceed pre-established criteria
[such as 1 rem/hour (0.01 Sv/hr)].
The ALARA job/task/experiment review should encompass three discrete phases: (1)
pre-job planning and dose assessment; (2) specification and implementation of ALARA controls
and dose tracking; and (3) post-job review.
Pre-job Planning and Dose Assessment
DOE G 441.1-1C 47
5-19-08
Pre-job planning should include an estimate of the collective dose resulting from the
job/task/experiment and a determination regarding whether the numerical criteria for an
ALARA job/task/experiment review will be exceeded. The estimates may be based on actual or
historical radiological monitoring results. If a review is required, the next step is to identify
appropriate ALARA controls and alternatives. This should include an assessment of the cost of
controls against numerical criteria.
ALARA Controls
During the work or experiment, periodic inspections should be made to ensure that ALARA
controls are being implemented and are effective. Typical ALARA controls implemented in the
field include: appropriate use of shielding and personal protective equipment (including
respiratory protection devices), monitoring of stay times, minimization of time in radiological
areas, maximizing distances from radioactive sources, and effective use of mock-up training and
pre-job briefings. In addition, individual and collective doses should be tracked and periodically
compared to the dose estimates to determine if intervention is needed.
Post-Job Review
Criteria should be established to trigger a formal post-job review. Examples include:
an actual collective dose equivalent of 5 person-rem or greater,
-job estimates,
use of the stop radiological work authority,
issuance of a radiological occurrence/deficiency report, or
identification of significant lessons learned.
The post-job review should compare the actual person-hours and person-rem with the
estimates, evaluate the effectiveness and cost of the ALARA controls, document the lessons
learned, and make recommendations on ways to control dose and contamination for similar
activities. The ALARA review should be documented and records should be readily retrievable.
In the special case of an ALARA review for a planned special exposure, additional
requirements are described under 10 CFR 835.204.
4.2.6.1 Consideration of Non-radiological Hazards
The work planning process should integrate the consideration of other industrial, physical,
and chemical hazards that an individual may encounter. Efforts to maintain worker doses
ALARA should ensure that the risk of personnel injury from other hazards is not
disproportionately increased. The ALARA process should consider the impact of other
occupational hazards when optimizing worker radiation dose. For example:
Section 44
excessive protective clothing to control personnel contamination events may lead to
heat stress situations.
DOE G 441.1-1C 48
5-19-08
respiratory protective devices used to reduce intakes of radionuclides may impair visual
acuity and communications capabilities between workers.
protective clothing to protect workers from chemical hazards may slow work down
leading to increased worker dose.
An integrated approach during the work planning process will ensure that all occupational
hazards are appropriately considered and the ALARA process is followed.
10 CFR 851, Worker Safety and Health Program (DOE 2006) provides requirements for
worker safety and health. The worker safety and health program must integrate the Rule’s
requirements with other site worker protection activities and the integrated safety management
system (ISMS) [851.11(a)(3)(ii)]. Coordination should be established, maintained, and
documented among worker safety and health technical disciplines and other safety and health
organizations (e.g., radiation control) at a site to ensure successful implementation of the
worker safety and health program.
Additional information concerning DOE expectations for integrating safety management can
be found in Department of Energy Acquisition Regulations (DEAR) clause 48 CFR 970.5223-1,
Integration of Environment, Safety and Health into Work Planning and Execution. This states that
“the contractor will manage and perform work in accordance with a documented Safety
Management System (System).”
DOE G 440.1-8, Implementation Guide for Use with Title 10 Code of Federal Regulations Part
851 (DOE 2006d) provides guidance for establishing and implementing an ISMS program.
4.3 Records
Actions taken to maintain occupational exposures ALARA shall be documented and retained
[10 CFR 835.701(a) and 835.704(b)]. Administrative controls discussed in this Guide should
include the systematic generation and retention of those auditable records and reports that
document major actions considered or taken to attain and maintain occupational doses and the
spread of radioactive contamination ALARA. The RCS and Chapter 13 provide detailed guidance
on record-keeping.
All documents and legal records used to demonstrate compliance with ALARA program
requirements should be reviewed and approved by supervisory or line management.
DOE G 441.1-1C 49
5-19-08
5.0 INTERNAL DOSIMETRY PROGRAM
In the 2007 amendment to 10 CFR 835 DOE changed most of the dosimetric terms used in
10 CFR 835 to reflect the recommendations for assessing dose and associated terminology from
ICRP Publication 60, 1990 Recommendations of the ICRP on Radiological Protection (ICRP 1991),
and ICRP Publication 68, Dose Coefficients for Intakes of Radionuclides by Workers (ICRP 1995).
DOE made this change mainly because these recommendations are based on updated scientific
models and more accurately reflect the occupational doses to workers than the models
currently used by DOE.
During the rulemaking process DOE received a comment that, under certain circumstances,
when an individual conducts multiple activities involving both activities under 10 CFR 835.1(b)(1)
and excluded activities (e.g., activities involving NRC licensed activities) it is ambiguous as to how
the rule would be applied when using different dose coefficients and weighting factors to
calculate the total effective dose for the worker from both activities. DOE agreed that guidance
was needed for this provision. In the preamble for the final rule DOE stated that for the purpose
of compliance with 10 CFR 835.1(b)(1) and (c), DOE considers the following terms to be
equivalent:
Section 45
Dosimetric Term as Defined by Excluded
Activity Cognizant Regulator DOE Amended Dosimetric Term
Committed effective dose equivalent
Committed effective dose
Committed dose equivalent
Committed equivalent dose
Cumulative total effective dose equivalent
Cumulative total effective dose
Deep dose equivalent
Equivalent dose to the whole body
Dose equivalent
Equivalent dose
Effective dose equivalent
Effective dose
Lens of the eye dose equivalent
Equivalent dose to the lens of the eye
Quality factor
Radiation weighting factor
Shallow dose equivalent
Equivalent dose to the skin or
Equivalent dose to any extremity
Weighting factor
Tissue weighting factor
Total effective dose equivalent
Total effective dose
DOE G 441.1-1C 50
5-19-08
Accordingly, for the purpose of compliance with the requirement in 10 CFR 835.1(c) for the
inclusion of doses from excluded activities in determining compliance with the limits, DOE
considers it acceptable to sum the equivalent dosimetric terms (per the above table) without
further adjustment. DOE recognizes that, for some situations, such as evaluation of uranium
intakes, this approach will overestimate radiation doses from excluded activities as compared to
those assessed using ICRP 60 values. For other situations, such as the evaluation of certain
neutron exposures or for intakes of selected radionuclides, this approach may underestimate
radiation doses from excluded activities as compared to those assessed using ICRP 60 values.
In cases where doses from excluded activities are expected to have been over estimated, no
additional activities above the standard radiological controls are required because this dose
estimate is unlikely to have resulted in a dose less than that estimated using ICRP 60 methods.
Regarding cases where doses from excluded activities are expected to have been
underestimated, a review of doses over the past several recent years, from both DOE and NRC,
indicated very few examples where individuals had neutron exposures or significant intakes of
those radionuclides which could underestimate radiation doses from excluded activities as
compared to those assessed using ICRP 60 values. Accordingly, the differences in assessing
these intakes or neutron doses between DOE (ICRP 60) and excluded activities would
infrequently result in doses challenging limits had they been entirely assessed using ICRP 60
values. Use of Administrative Control Levels, per the RCS, should be adequate to address
concerns regarding these situations.
See Section 6.0.1, “Protection and Operational Quantities” for a discussion on the use of
protection and operational quantities.
Radiation protection programs for limiting intakes of radioactive material are based on the
DOE policy of controlling radioactive material at the source. It is nonetheless recognized that
low-level, chronic, or intermittent occupational exposures to some materials may be difficult to
avoid due to the types of material handled or processed, their chemical or physical forms, and
the nature of operations, and that incidents may cause unplanned releases of radioactive
material. 10 CFR 835.402(c) requires internal dosimetry programs (including routine
radiobioassay programs) be conducted for radiological workers, declared pregnant workers,
occupationally exposed minors, and members of the public entering controlled areas who are
likely to receive intakes that exceed specified levels for committed effective dose in a year. An
internal dosimetry program generally consists of three elements:
Section 46
An air monitoring program, using a combination of real-time, fixed, and portable
devices, as appropriate;
an individual monitoring program, using direct and/or indirect radiobioassay, and
personal breathing zone (BZ) air monitoring, as appropriate; and
a dose evaluation program that evaluates the data collected by the air and individual
monitoring programs to determine the magnitude of individual doses.
5.1 Implementation Guidance
DOE G 441.1-1C 51
5-19-08
This section provides guidance for establishing and conducting internal dosimetry programs
for individuals who have the potential for intakes of radioactive materials. It includes guidance
for design and implementation of the radiobioassay program, and guidance for evaluating,
recording, reporting, and managing internal doses. Additional technical guidance is provided in
DOE-STD-1121-2008, INTERNAL DOSIMETRY (DOE 2008j) and the National Council on Radiation
Protection and Measurements (NCRP) Report No. 87, Use of Radiobioassay Procedures for
Assessment of Internal Radionuclide Deposition (NCRP 1987a).
An acceptable internal dosimetry program includes the following features:
adequate staff with appropriate technical training;
internal dosimetry technical basis documentation providing scientific information and
other rationale explaining essential elements of the internal dosimetry program to
support dose evaluation methods;
written policies and procedures covering essential steps in the activities used to
determine worker internal dose;
criteria and methods for implementing an appropriate air monitoring program;
defined criteria for identifying workers who need to participate in the individual
monitoring program;
appropriate radiobioassay measurement methods and frequencies;
methods for control, accountability, and safe handling of samples;
appropriate dosimetric models and default parameters for evaluating internal dose;
timely analysis of radiobioassay samples and measurements, transmission of results,
dose evaluation, and recommendations to operations management;
adequate detection capability and quality of radiobioassay measurements;
defined criteria and actions for identifying individuals with suspected intakes, based on
workplace measurements and radiobioassay measurements;
appropriate action level guidelines;
defined program to report internal doses to workers, management, and DOE;
historical records of radiobioassay measurement results and dose evaluations;
historical records of the program, and changes in the program over time; and a quality
assurance program covering essential steps in the activities that determine worker
internal dose.
5.2 Program Management and Administration
DOE G 441.1-1C 52
5-19-08
5.2.0 General Requirements
The internal dosimetry program shall be adequate to demonstrate compliance with the dose
limits established in Subpart C of 10 CFR 835 [10 CFR 835.402(d)]. In addition, radiobioassay
programs implemented to demonstrate compliance with the requirements in 10 CFR 835.402(c)
(individual monitoring thresholds) shall be:
accredited or excepted from accreditation in accordance with the DOELAP for
Radiobioassay [10 CFR 835.402(d)(1)]; or
determined by the Secretarial Officer responsible for environment, safety and health
matters (i.e., the Chief Health, Safety and Security Officer) to have performance
substantially equivalent to that of programs accredited under DOELAP for radiobioassay
[10 CFR 835.402(d)(2)].
Section 47
Guidance for achieving accreditation or exception from accreditation under DOELAP is
provided in DOE-STD-1111-98, DEPARTMENT OF ENERGY LABORATORY ACCREDITATION
PROGRAM ADMINISTRATION (DOE 1998a). Requests for other program determinations
will be considered by DOE on a case-by-case basis.
The provision requiring accreditation for radiobioassay programs implemented to
demonstrate compliance with 10 CFR 835.402(c) does not reflect an intent to provide a
lesser degree of protection to individuals unlikely to receive doses exceeding the regulatory
monitoring thresholds, nor does it express a desire to establish two separate radiobioassay
programs (i.e., an accredited program for individuals likely to exceed the regulatory
monitoring thresholds and a non-accredited program for individuals who are unlikely to
exceed these thresholds). Rather, those individuals who are unlikely to exceed the
regulatory monitoring thresholds are provided an adequate degree of protection by the
various engineering and administrative controls that limit their internal doses.
Implementation of a comprehensive air monitoring program in accordance with
10 CFR 835.401 and 403 verifies the effectiveness of these controls. When an accredited
radiobioassay program already exists and management of any given facility chooses to
provide monitoring for those individuals who are unlikely to exceed the regulatory
monitoring threshold, consideration should be given to using the accredited program. This
will obviate the need to implement two radiobioassay programs, one accredited and the
other not. In addition, it will avoid giving workers who are not required to be monitored the
impression that they are being provided a lesser degree of protection. However, this does
not imply that the monitoring program for those unlikely to exceed the monitoring threshold
must be accredited.
Sections 401 through 403 of 10 CFR 835 establish specific monitoring requirements for areas
and individuals. 10 CFR 835 also establishes requirements for maintaining individual monitoring
records (10 CFR 835.702) and reporting radiation doses to individuals (10 CFR 835.801).
5.2.1 Organization, Staffing, and Facilities
5.2.1.0 Organization
DOE G 441.1-1C 53
5-19-08
The internal dosimetry program should be administered by the radiological control
organization under the leadership of the radiological control manager. The internal dosimetry
program should have a designated leader with demonstrated expertise in internal dose
evaluation. When elements of the internal dosimetry program are performed by one or more
subcontractors, the radiological control organization should establish an arrangement of
contractual standards and assessments that ensure that subcontractors meet all applicable
requirements in 10 CFR 835, the documented Radiation Protection Program (RPP), DOELAP
standards, and the internal dosimetry technical basis document.
5.2.1.1 Staffing
The radiological control organization management should ensure that the internal
dosimetry program is adequately staffed to carry out its functions. The analysis of workplace
and radiobioassay measurement data and the evaluation of internal dose involve complex
evaluation and professional judgment. Personnel with responsibility for internal dose
evaluation should have the necessary expertise and skill, based on appropriate education and
Section 48
training in conjunction with practical experience, to perform their assigned duties. Additional
guidance on education, skills, and training is provided in Chapter 3. It is important that internal
dosimetry specialists be capable of recognizing conditions warranting follow-up radiobioassay
and dose evaluation. Personnel should be familiar with the relevant internal dosimetry
literature and the recommendations of national and international scientific organizations with
regard to internal dose evaluation.
Management of the radiological control organization should establish minimum
requirements for those staff who evaluate internal doses. These requirements should include
both experience and education requirements. Suggested educational background and formal
training needed for internal dosimetry program key positions are listed in DOE-STD-1107-2007,
Chg 1, KNOWLEDGE, SKILLS, AND ABILITIES FOR KEY RADIATION PROTECTION POSITIONS AT DOE
FACILITIES (DOE 2007g). Members of the internal dosimetry staff should meet these
requirements, or the staff should have access to individuals with the required background
(perhaps through interdepartmental agreements or contracted services). It is not necessary for
all personnel on the staff to have expertise in all of the listed subject areas.
5.2.1.2 Facilities and Resources
Computational facilities and software tools used by internal dosimetry personnel
should be adequate for performing calculations required for the evaluation of dose from
radionuclides in the body. A library of handbooks, reference materials, scientific
publications, and other resources pertaining to internal dosimetry should be readily
available. Suggested reference materials are included in the reference chapter of this
Guide. DOE O 414.1D, Quality Assurance (DOE 2011), establishes quality process
requirements to be implemented under a QA program (QAP) for the control of
suspect/counterfeit items (S/CIs), safety issue corrective actions, and safety software.
5.2.2 Technical Basis Document
DOE G 441.1-1C 54
5-19-08
Internal dosimetry technical basis documentation should be developed and should include
technical methods, supporting evidence, and reference information used to provide the
technical foundation for the internal Dosimetry program. The internal dosimetry technical basis
documentation should provide the approach to evaluating internal doses from radiobioassay
data, and for situations in which there is no practical radiobioassay, from representative air
monitoring or other appropriate data. The technical basis documentation should address all of
the topics listed under Section 3.1 of DOE-STD-1121-2003. The technical basis documentation
should be reviewed periodically and updated as necessary to ensure that the scientific bases are
appropriate for current conditions. The technical basis documentation should be controlled and
retained as a radiation protection program record.
5.2.3 Internal Dosimetry Procedures Manual
10 CFR 835 requires that written procedures be developed and implemented as necessary to
ensure compliance, commensurate with the radiological hazards created by the activity and
consistent with the education, training, and skills of the individuals exposed to those hazards
(10 CFR 835.104). Essential elements of the internal dosimetry program should be addressed in
written procedures. These procedures should be consistent with 10 CFR 835, the DOELAP
standard, and technical basis documentation.
Section 49
Detailed guidance on topics that should be addressed in the internal dosimetry procedures
manual are discussed in Section 3.2 of DOE-STD-1121-2008. Additional guidance on written
procedures is provided in Chapter 3 of this Guide.
5.2.4 Quality Assurance
Quality Assurance for internal dosimetry programs is addressed in DOE-STD-1121-2008,
Section 11. Quality assurance in support of internal dosimetry programs should be conducted in
accordance with this DOE standard.
The internal dosimetry program should be included as a functional element subject to the
internal audit requirements of 10 CFR 835.102. Chapter 3 provides guidance on internal audit
programs. External peer-review by qualified individuals, on a periodic basis, is also
recommended.
5.3 Air Monitoring and Contamination Control Programs
The objectives of an air monitoring program are to verify the integrity of radioactive material
containment, detect the release of radioactive materials from some routine operations, detect
inadvertent releases of those materials in the workplace, evaluate and provide the basis for
modification to containment systems, provide a basis for the design of radiobioassay programs,
and verify that selected groups do not need to participate in a radiobioassay program. Air
monitoring programs and internal dosimetry programs are complimentary. The air monitoring
program provides an indication of the effectiveness of engineering and administrative controls in
preventing or minimizing worker intakes and the internal dosimetry program provides
verification of the adequacy of these controls in preventing or minimizing worker intakes.
DOE G 441.1-1C 55
5-19-08
The air monitoring and contamination control programs supplement the individual
monitoring program by providing a prospective assessment of radiological conditions, facilitating
decisions regarding postings, access controls, work authorizations, and individual monitoring,
and providing back-up data for use in individual dose evaluations. Because of the need to
evaluate individual internal doses from intakes of radioactive material from uncontained
sources, airborne radioactive material, and surface contamination, the air monitoring and
contamination control programs should include methods for assessing the degree of hazard
arising from each of these hazards to which individuals may be exposed. Guidance for
implementing contamination control and air monitoring programs is provided in Chapters 10 and
11 of this Guide.
In most cases the air monitoring program is used to supplement and validate the individual
monitoring program. However, in the case when there is no practical radiobioassay method or
when there is a technology shortfall (e.g., the DIL is less than the MDA) the air monitoring
program may be the basis for the determination of internal doses. These two cases are
discussed below.
5.3.0 Air Monitoring When There Is No Practical Radiobioassay Method
Section 50
In situations where no radiobioassay method is available for the radionuclides in question,
and no radiobioassay program, either routine or special, can show compliance with 10 CFR 835,
personal (BZ) air monitoring may be used for demonstrating compliance with 10 CFR 835. BZ air
monitoring is part of the Individual Monitoring Program which is detailed below. However, other
fixed or portable monitoring instruments that provide either real-time (such as continuous air
monitors) or retrospective (such as grab sampling which is analyzed at some time after the
sample is collected) may be required when BZ monitoring data is not available or to supplement
or validate the BZ data if it is available. Radionuclides with short half-lives, including the
short-lived decay products of 222Rn (“radon” decay products 218Po, 214Pb, 214Bi, and 214Po) and
220Rn (“thoron” primary decay products 212Pb and 212Bi) are examples of radionuclides where
intakes cannot be determined through radiobioassay and must be determined from personal air
monitoring. For detailed information on non-background exposures to radon and thoron, see
DOE-STD-1121-2008, Section 4.5. Monitoring programs for radon and thoron should be in
accordance with the DOE standard.
5.3.1 Recourse for Technology Shortfall (DIL<MDA)
DILs for reasonable and practical routine radiobioassay programs may be significantly less
than the achievable MDA for certain radionuclides, such as plutonium. Since a technology
shortfall for routine radiobioassay exists, the facility should consider the following actions (note
that some of these suggested actions fall under the category of individual as opposed to area
monitoring, but for completeness they are all listed below):
enhance contamination and air monitoring and the use of indicators (e.g., unexpected
glove or surface contamination, increase in airborne radioactive material contamination,
nasal smears) to trigger early special radiobioassay monitoring;
enhance personal contamination monitoring (e.g., clothing, skin) to trigger special
radiobioassay monitoring;
DOE G 441.1-1C 56
5-19-08
use the best practicable radiobioassay monitoring methods;
implement enhanced design, operation, controls, and personnel protection equipment
and procedures to minimize intakes;
implement supplementary air monitoring; and
document and justify the planned supplementary approach in the facility's internal
dosimetry technical basis documentation.
When air monitoring data are used, each worker's stay times (in hours) and the average
concentration (in DACs) to which the worker is exposed should be multiplied to yield exposures
to airborne radioactive materials in units of DAC-hours. Forty (40) DAC-hours corresponds to 0.1
rem (0.001 Sv) committed effective dose for radionuclides with a stochastic ALI.
A technology shortfall for routine radiobioassay should not be sufficient cause for failing to
place individuals on a minimum or best-available radiobioassay program. Refer to
DOE-STD-1121-2008, Section 4.4.4, for a discussion and examples of technology shortfalls and
suggested methods to handle such situations.
5.4 Individual Monitoring Program
Individual monitoring programs should be designed in accordance with Section 4 of
DOE-STD-1121-2008 and should:
provide for investigation of suspected intakes;
provide data for evaluating internal dose; and
Section 51
provide results that are adequate to demonstrate compliance with the radiation dose
limits given in 10 CFR 835. The primary methods of routine and special worker
radiobioassay are direct (in vivo) radiobioassay and indirect (in vitro) radiobioassay.
In situations where there is no practical radiobioassay, representative air monitoring (e.g.
breathing zone (BZ) air monitoring) is the preferred measurement method on which to base
dose evaluations. Additional guidance on air monitoring programs may be found in Chapter 10
of this Guide.
5.4.0 Establishing the Need for Individual Monitoring
Radiological workers who could likely receive intakes resulting in 0.1 rem (0.001 Sv) or more
committed effective dose in a year shall participate in an internal dose evaluation program
[10CFR 835.402(c)(1)]. Declared pregnant workers, occupationally exposed minors, and
members of the public are also required, under specific conditions [see 10 CFR 835.402(c)] to
participate in internal dosimetry programs. Criteria for participation in individual monitoring
programs which include baseline radiobioassay, routine radiobioassay and/or air sampling, radon
and thoron monitoring, special radiobioassay, and termination or task-ending radiobioassay,
radiobioassay for declared pregnant women, and confirmatory radiobioassay are covered in
DOE G 441.1-1C 57
5-19-08
DOE-STD-1121-2008, Section 5. This section of the technical standard also discusses timely
receipt of radiobioassay results. Participation in individual monitoring programs for internal
dosimetry should be in accordance with the DOE technical standard.
Situations may arise where a decision is made to monitor radiological workers who are not
likely to receive intakes that exceed 0.1 rem (0.001 Sv) committed effective dose in a year. Such
monitoring may be useful for demonstrating compliance with 10 CFR 835.401(a) or established
for other purposes. The internal dosimetry program documentation should clearly identify
those individuals or groups of individuals being monitored for such purposes.
5.4.1 Investigation Levels/Derived Investigation Levels
Refer to DOE-STD-1121-2008, Sections 4.3 and 4.4 for a discussion of and reference levels for
Investigation Levels (ILs) and Derived Investigation Levels (DILs). Programs should be designed in
accordance with this technical standard.
Refer to DOE-STD-1121-2008, Section 4.4.1 for a discussion of factors affecting the DIL.
Additionally, section 4.4.2 provides guidance for calculating the DIL for a given sample frequency,
Section 4.4.3 discusses factors affecting the DIL for air sampling, and Section 4.4.4 deals with
supplementing routine radiobioassay programs when DIL< MDA (technology shortfall).
Programs should be designed in accordance with this technical standard.
5.4.2 Minimum Detectable Amount (MDA)
The internal dosimetry program staff should determine the minimum detectable amount
(MDA) for each radiobioassay and BZ air monitoring method for each radionuclide present. The
MDAs should be documented in procedures and their statistical bases given in the internal
dosimetry technical basis documentation. ANSI Standard N13.30-1996, Performance Criteria for
Radiobioassay, (ANSI/HPS 1996) provides extensive guidance on the calculation of MDAs.
Section 52
As MDAs are affected by various aspects involved with individual monitoring methods,
procedures should contain descriptions of the method(s) of individual monitoring measurements
(e.g., urinalysis, fecal analysis, in vivo counting, BZ air monitoring), analytical methodology (e.g.,
chemical separation followed by alpha counting), and measurement parameters (e.g., counting
time or instrument efficiency) to be used in each component of the individual monitoring
program.
Several other factors affect the method of radiobioassay used and its associated MDA. They
include:
the possible need for improved detection capability to assess individual dose during the
special radiobioassay following an intake requiring internal dose evaluation, due to
diminishing amounts of material in compartments as time goes on;
the need for improved precision and accuracy if residual retention and excretion from
prior intakes interferes with the detection of additional intakes in subsequent years;
timeliness of results needed to manage individuals and keep subsequent intakes low
DOE G 441.1-1C 58
5-19-08
enough to avoid exceeding dose limits;
convenience to the affected individuals;
costs, including lost production time while individuals are participating in the
radiobioassay program; and
the impact of the method of radiobioassay on the frequency of radiobioassay
measurements.
Where practicable, the method of individual monitoring, analytical methodology, and
measurement parameters should result in an MDA less than the corresponding DIL for all
radionuclides to which an individual might be exposed.
The methods of radiobioassay and air monitoring measurements, their MDAs, and their
accuracies should be specified in the internal dosimetry technical basis documentation, along
with a rationale or justification for the methods chosen.
5.4.3 Frequency of Measurement
The routine radiobioassay measurement frequency depends on the radiobioassay
measurement method and associated MDA. The frequency should be chosen so that it is
unlikely that intakes by an individual in a year will result in doses exceeding one IL without
detection.
5.4.4 Detection and Confirmation of Intakes
Section 6 of DOE-STD-1121-2008 provides acceptable methods for detecting and confirming
intakes through workplace monitoring and radiobioassay. Statistical methods for confirming that
an intake has occurred are also discussed. Decisions regarding the detection and confirmation of
suspected occupational intakes of radioactive material should be based on answers to the
following questions:
Can it be concluded reliably that the analyte is present in the measured sample (>Lc)?
Is the measurement result unexpected? In other words, is the result beyond the range
of values that would be expected due to environmental “background” sources or due to
previously recognized intakes?
Is the intake (and resulting dose) implied by the measurement significant enough
(e.g., greater than the IL) to warrant follow-up measurements or investigation?
If the answer to all these questions is “yes”, then follow-up measurements or investigation
is warranted. Internal dosimetry programs should establish appropriate and technically-based
decision criteria to assist in answering these questions. Such decision criteria should be
included in the technical basis document for the site or facility.
The proper decision criteria for the first question is the Lc which is a purely statistical
concept based on an acceptable probability of “false positive” conclusions. The Lc for
Section 53
DOE G 441.1-1C 59
5-19-08
radiobioassay and air sample measurements should be set by considering the acceptable rate
of false positives, the cost and consequences of false positives, and the dosimetric
consequences of false negatives. The analytical laboratory Lc should be based on a reagent
blank. Radiobioassay results above the Lc may be expected in the absence of a new intake due
to normal statistical fluctuations, non-occupational or environmental sources, or prior
confirmed intakes. In the case of environmental sources of interference (e.g., uranium in
urine) an “occupational decision level” should be established, above which the measurement
result is concluded to be statistically significant and above the range of values that would
normally be expected from environmental sources of the radionuclide. In the case of prior
confirmed intakes, an individual-specific “occupational decision level” should be established,
which takes into account the expected contribution from the prior intakes. Finally, for each
route of intake, measurement type, and radioactive material of interest (taking into account
particle size, material type, etc.), time-dependent DILs should be established. Such DILs are
based solely on dosimetric considerations, and typically correspond to an implied intake (and
corresponding dose) of 1 investigation level, i.e., 0.1 rem. This Guide has adopted the value of
0.1 rem (0.001 Sv) committed effective dose as the value which, for regulatory purposes, is
regarded as sufficiently important to justify further investigation. However, a site or facility
may wish to establish lower follow-up levels for ALARA purposes.
If the measurement result is statistically significant, unexpected, and dosimetrically
significant, then follow-up measurements and/or an investigation should be done to attempt to
confirm or rule out the intake. An intake should be considered to be confirmed if the three
criteria above are satisfied and the measurement result is associated with a known incident, or
appropriate follow-up measurements meet the three criteria above, or follow-up investigation
indicates that an intake has occurred.
Refer to DOE-STD-1121-2003, Section 6, for additional information on the detection and
confirmation of intakes. Table 3 addresses reference levels for interpreting or responding to
intake monitoring results. Program elements which address the detection and confirmation of
intakes of radionuclides should be in accordance with the DOE technical standard. Additionally,
NCRP Report No. 84, General Concepts for the Dosimetry of Internally Deposited Radionuclides
(NCRP 1985) and ICRP Publication 30, Limits for Intakes of Radionuclides by Workers (ICRP 1979),
may be useful references.
5.4.5 Internal Dose Management
Internal dose management, which includes routine radiological worker dose management,
management of dose from previous intakes (work restrictions), control of dose to the
embryo/fetus, control of dose to minors and students, dose limitation, interface with the
external dosimetry program, lifetime dose control, accidental dose control, and internal dose
control after an incident, is covered in DOE-STD-1121-2008, Section 8. Individual programs
should be in accordance with the DOE technical standard.
5.4.6 Planned Special Exposures
Planned special exposures are included in an individual’s occupational dose record, but shall
not be considered when determining compliance with the occupational dose limits of
10 CFR 835 [10CFR 835.204(a)]. In order to maintain separate records of doses resulting from
Section 54
DOE G 441.1-1C 60
5-19-08
planned special exposures and routine occupational exposures, dosimetry adequate to measure
the potential doses and appropriate for the work to be performed and specific radiological
circumstances should be provided for the planned special exposure.
5.4.7 Medical Response
Medical response is addressed in DOE-STD-1121-2008, Section 10. The standard addresses
situations where internal dosimetry actions and medical treatment occur simultaneously, the
role of the health physicist in medical treatment, when to treat, how to treat, the impact of
therapy on dosimetry, and the counseling of workers. Medical response should be handled in
accordance with the DOE technical standard.
5.5 Internal Dose Evaluation
10 CFR 835 requires internal dose evaluation programs for assessing intakes of radionuclides
and for maintaining adequate worker exposure records. Technical details and extensive
references for internal dose evaluation are given in DOE-STD-1121-2008. NCRP Report No. 84 is
an additional suggested reference.
5.5.0 Required Dose Calculations
Internal doses should be evaluated for all confirmed intakes, as defined in Section 5.3.5 of
this Guide. For intakes confirmed with radiobioassay results below the DIL, no further
investigation or follow-up radiobioassay are indicated. For intakes confirmed with radiobioassay
results above the DIL or exposures greater than 40 DAC-hours, follow-up radiobioassay (if
practical) and investigation should be performed.
In the 2007 amendment to 10 CFR 835, section 835.702(b) was modified and a provision
was added regarding the recording of internal dose (committed effective dose or committed
equivalent dose). The provision allows for not recording of any positive monitoring result
estimated to correspond to an individual receiving less than 0.01 rem (0.1 mSv) committed
effective dose. Typically, this would be for very sensitive bioassay protocols or for radionuclides
which are easy to detect at very low doses (e.g., routine tritium bioassay). The bioassay or air
monitoring result used to make the estimate shall be maintained in accordance with 10 CFR
835.703(b) and the unrecorded internal dose estimated for any individual in a year shall not
exceed the applicable monitoring threshold at 10 CFR 835.402(c).
The extent of the investigation and the number and frequency of special radiobioassay
measurements following a suspected or confirmed intake should be determined and
documented on an individual, case-specific basis, taking into account the potential
magnitude of the intake, the effective clearance half-time, the health of the worker, and
the number of measurements needed to evaluate the internal dose.
The schedule and frequency of long-term special radiobioassay measurements to evaluate
the committed effective dose to an individual who has had an intake resulting in a dose in excess
of one IL should depend on the expected magnitude of the committed effective dose and the
likelihood of the individual receiving additional intakes.
DOE G 441.1-1C 61
5-19-08
While the investigation should be tailored to the specific individual and exposure
circumstances, the trigger levels and preliminary actions to be taken for exposures to the
different radionuclides encountered at the facility should be documented in the internal
dosimetry technical basis documentation and procedures.
5.5.1 Interpretation of Radiobioassay Data
Section 55
Technical details on the interpretation of radiobioassay data including the use of biokinetic
models are given in DOE-STD-1121-2008, Section 7. Radiobioassay data should be interpreted in
accordance with the applicable portions of this DOE technical standard.
Evaluations of committed effective dose from a specific intake should account for expected
values of radiobioassay measurements from prior confirmed intakes.
5.5.2 Evaluation of Internal Dose from Radiobioassay and Air Monitoring Data
Methods for evaluating the various doses from intakes should be specified in the internal
dosimetry technical basis documentation. The methods should be based on recommendations,
consistent with DOE requirements, given in ICRP Publications, NCRP Reports, and ANSI standards
which embody improvements and updates of the science of internal dosimetry. Other methods
may be used provided they are documented and justified in the procedures and/or internal
dosimetry technical basis documentation.
In the calculation of internal doses less than one IL, default parameters may be used. These
parameters (e.g., intake date, deposition fractions, retention functions, organ masses, and
absorption fractions) should be based on the recommendations of the ICRP, NCRP, other relevant
technical references, or facility-specific factors as documented in the internal dosimetry
technical basis documentation. If the initial evaluation of an intake indicates a dose in excess of
10 times an IL, individual-specific and facility-specific factors should be used when more
appropriate parameters are expected to change the dose calculations by a factor of 1.5 or more
Between 1 and 10 times the IL, either default parameters or individual- and facility-specific
parameters may be used, as deemed appropriate and documented by the internal dosimetry
staff. The basis for determining which individual-specific and facility-specific factors are
expected to change the dose calculations by a factor of 1.5 or more should be documented in
the internal dosimetry technical basis documentation. Determination of individual retention
patterns for a worker requires participation in the special radiobioassay program and may
require temporary work restriction or reassignment to prevent subsequent intakes from
confounding the dose evaluation.
5.5.3 Periodic Reevaluation of Internal Dose
In the case of certain well-retained radionuclides (e.g., plutonium), long-term follow-up and
reevaluation of doses may be required. The internal contribution to lifetime occupational dose
should continue to be reevaluated as further radiobioassay results and improved methods for
evaluating internal dose become available.
DOE G 441.1-1C 62
5-19-08
Evaluations for general employees with prior confirmed intakes should be revised when
information demonstrates a change in the currently evaluated committed effective dose of 0.5
rem (0.005 Sv) or a factor of 1.5 of the previously assigned dose for that intake, whichever is
higher. In cases where intakes are detected or confirmed in a year subsequent to the year of the
intake, the committed effective dose should be attributed to the known or assumed year of the
intake, and all records and reports for that year should be amended as appropriate. An
acceptable approach would be for DOE sites to update their dosimetry program to reflect the
amended 10 CFR 835 tissue and radiation weighting factors, and to assess doses using the
updated factors at some predetermined time. It is not expected that DOE sites recalculate all
previously completed dose estimates performed at that site. Note the Department did not
require recalculation of previous internal doses resulting from uranium intakes when it granted
a DOE contractor an exemption from those requirements in 10 CFR 835 requiring the use of the
specified tissue weighting factors, thus, permitting the use of the tissue weighting factors in
ICRP 60 when calculating internal doses from uranium.
Section 56
DOE does not encourage routine recalculation of internal doses in response to changes in
internal dosimetry methodologies such as biokinetic models, tissue weighting factors, or
improved bioassay techniques after a final dose estimate has been completed and recorded.
Internal doses calculated using technically sound and defensible methods available at the time
of the dose estimate are an acceptable way to meet the Department’s expectations for internal
dose monitoring and compliance with occupational exposure dose limits promulgated in 10 CFR
835. However, in the process of updating methodologies it is recommended that DOE sites
should maintain close communication with cognizant DOE personnel.
DOE recognizes there may be unique situations in which a DOE site may consider or be
directed to reevaluate an internal dose estimate. Examples of such situations are a response to
litigation, determination that an internal dose has been incorrectly estimated, or availability of
new bioassay data. In such cases the decision to recalculate a final internal dose estimate should
be made on a case-by-case basis and consider:
The magnitude of the expected change,
Programmatic costs,
Impact on compliance with dose limits,
Documentation of the recalculated result in official records, and
Communication of the recalculated dose to current and former workers.
To ensure compliance with record-keeping provisions of 10 CFR 835 subpart H, the technical
basis and results of determinations to recalculate a completed internal dose assessment should
be documented in official site records.
5.6 Recordkeeping and Reporting
Requirements and guidance for recording and reporting internal doses and related
information are provided in Chapter 14 and DOE-STD-1121-2008, Section 9. Record-keeping and
DOE G 441.1-1C 63
5-19-08
reporting of internal doses and related information should be in accordance with these DOE
documents.
DOE G 441.1-1C 65
5-19-08
6.0 EXTERNAL DOSIMETRY PROGRAM
Due to the types of material handled or processed, low-level, chronic occupational
exposures to external ionizing radiation are difficult to avoid, necessitating an external dosimetry
program at most DOE and DOE-contractor facilities that use, handle, or store radioactive
materials. An external dosimetry program generally consists of three elements:
an area monitoring program, using an array of fixed and portable devices, as
appropriate;
an individual monitoring program, using personnel dosimeters; and
a dose evaluation program that evaluates the data collected by the area and individual
monitoring programs to determine the magnitude of individual doses.
6.0.1 Protection and Operational Quantities
The ICRP Publication 60 dosimetric quantities adopted in 10 CFR 835 have been designated
by ICRP as “protection quantities” that are intended for defining and calculating the numerical
limits and action levels used in radiation protection standards such as 10 CFR 835. Protection
quantities provide a way to relate the magnitude of a radiation exposure to the risk of a health
effect that is applicable to an individual and that is largely independent of the type and source
(internal or external) of the radiation. In addition the protection quantities can be easily
calculated for use in planning radiological work.
Section 57
These goals are achieved using a combination of theoretical and practical considerations.
For example, absorbed dose is assumed to be averaged over a tissue or organ. Radiation
weighting factors are used to account for the biological effectiveness of various types and
energies of radiation and tissue weighting factors are used to account for the sensitivity of
various tissues to radiation induced cancer. See Appendices F and G of Chapter 16 of this Guide
for listings of values. The tissue and radiation weighting factors are based on both biological and
epidemiological studies and have been updated as new research became available.
Nevertheless, the values of these weighting factors are approximations that account for both
uncertainty in the underlying data and the need to ensure that the protection quantities do not
underestimate the true dose and hence the risk. Protection quantities used in 10 CFR 835
include: equivalent dose, effective dose, committed equivalent dose, committed effective dose,
total effective dose, and cumulative total effective dose.
Because protection quantities were developed to provide an index of the risk resulting from
energy imparted to tissue by radiation, they are theoretical and not measurable. Fortunately, it
is possible to use the measurable properties of radiation fields and radioactive materials
associated with exposure to external radiation sources or intake of radioactive materials to
estimate and demonstrate compliance with the protection quantities. These measurable
quantities are called operational quantities.
Although many types of operational quantities are possible, a well characterized set of
operational quantities for assessing doses received from external exposure have been selected
by the International Commission on Radiation Units and Measurements (ICRU) in Report 51,
Quantities and Units in Radiation Protection Dosimetry. These operational quantities have been
DOE G 441.1-1C 66
5-19-08
adopted in recommendations of the ICRP and in the standards implementing the ICRP
recommendations written by the International Atomic Energy Agency (IAEA) and the European
Union (EU). In addition, the ICRP, in Publication 74, Conversion Coefficients for Use in
Radiological Protection Against External Radiation, compared and contrasted doses determined
using the ICRP system of protection quantities with doses determined using the ICRU based
operational quantities. For almost all situations considered, doses determined with the
operational quantities were greater or equal to the doses determined using protection
quantities. These operational quantities and their relation to the protection quantities listed in
the final version of 10 CFR 835 are listed below.
Relation between protection quantities and operational quantities for individual monitoring of
external exposure
Protection quantity Operational quantity (depth [d] in tissue [mm])
Equivalent dose to the whole body from
external sources*
Hp(10)
Equivalent dose to the lens of the eye
from external sources
Hp(3)
Equivalent dose to the extremity or skin
from external sources
Hp(0.07)
Where Hp(d) is the personal dose equivalent at depth d in tissue
See ICRU Report 51 for the definition of Hp(d)
* Same as effective dose from external sources.
For doses resulting from intakes of radioactive materials operational quantities have been
published in ICRP, IAEA and EU documents.
Section 58
Relation between protection quantities and operational quantities for individual monitoring of doses
from intakes of radioactive material
Protection quantity Operational quantity
Committed effective dose
j
ingjingeffj
j
inhjinheffj IhIh ,,50,,,,50,,
Committed equivalent dose
j
ingjingTj
j
inhjinhTj IhIh ,,50,,,,50,,
Where: hj,eff,50,inh is the committed effective dose per unit of radioactivity intake by inhalation (inh)
hj,eff,50,ing is the committed effective dose per unit of radioactivity intake by ingestion (ing)
hj,T,50,inh is the committed equivalent dose to a tissue (T) per unit of radioactivity intake by inhalation
hj,T,50,ing is the committed equivalent dose to a tissue (T) per unit of radioactivity intake by ingestion
Ij,inh is an intake by inhalation
Ij,ing is an intake by ingestion
j is a radionuclide
For the total effective dose, the following operational quantity is suggested.
Protection quantity Operational quantity
Total effective dose Hp(10) +
j
ingjingeffj
j
inhjinheffj IhIh ,,50,,,,50,,
DOE G 441.1-1C 67
5-19-08
In addition to the operational quantities used for individual monitoring, the following table
contains operational quantities that may be measured to characterize certain aspects of
radiation fields in the workplace.
Operational quantities for use in characterizing workplace radiation fields
Workplace measurement Suggested operational quantity
Control of effective dose H *(10)
Control of dose to the skin, the extremities
and the lens of the eye
H '(0.07, Ω)
Control of dose to the lens of the eye H '(3, Ω)
Where: H *(10) is the ambient dose equivalent at a depth of 10 mm in tissue
H '(0.007, Ω) is the directional dose equivalent at a depth of 0.07mm in the ICRU sphere
H '(3, Ω) is the directional dose equivalent at a depth of 3 mm in the ICRU sphere
Ω defines the direction of the radiation field
See ICRU Report 51 for the definitions of ambient dose equivalent and directional dose equivalent
In the 2007 amendment to 10 CFR 835, DOE deleted the terms deep dose and shallow dose.
The following was added to the definition of equivalent dose: “For external dose, the equivalent
dose to the whole body is assessed at a depth of 1 cm in tissue; the equivalent dose to the lens
of the eye is assessed at a depth of 0.3 cm in tissue, and the equivalent dose to the extremity
and skin is assessed at a depth of 0.007 cm in tissue.”
The 10 CFR 835 definition of “absorbed dose” is taken from ICRP Publication 71, which
reads:
Absorbed Dose: the physical dose quantity, which is given by:
dE/dm
where dE is the mean energy imparted by ionizing radiation to the matter in a volume
element and dm is the mass of the matter in this volume element. The SI unit for absorbed dose
is joule per kilogram (J /kg) and its special name is gray (Gy).
The 10 CFR 835 definition:
Absorbed dose (D) means the average energy imparted by ionizing radiation to the matter in
a volume element The absorbed dose is expressed in units of rad (or gray) (1 rad = 0.01 gray).
While the 10 CFR 835 definition does not include the equation or the definition of the terms
in the equation as does ICRP Publication 71, it does state that absorbed dose is expressed in
units of rad, i.e., energy per mass (J/kg). Accordingly, for purposes of compliance, the 10 CFR
835 definition is considered equivalent to the ICRP Publication 71 definition.
6.1 Implementation Guidance
DOE G 441.1-1C 68
5-19-08
Section 59
This chapter provides guidance for establishing and conducting an external dosimetry
program for individuals who are likely to be exposed to external sources of ionizing radiation.
Conduct of an external dosimetry program involves determining area and individual monitoring
methods and frequencies, distributing and controlling monitoring devices, and evaluating
external doses. This chapter also addresses program organization, administration, staffing, and
training.
An external dosimetry program should include the following features:
adequate staff provided with appropriate technical training;
a technical basis document that explains each program element;
procedures that address each step in the activities that determine external dose;
criteria and methods for implementing the area monitoring program;
criteria and methods for identifying individuals who require individual monitoring;
appropriate personnel dosimeter measurement methods and frequencies;
methods for control, accountability, and safe handling of dosimeters;
appropriate dosimetric models and default parameters for evaluating external dose;
timely analysis of personnel dosimeter measurements and transmission of results, dose
evaluation, and recommendations to monitored individuals, management, and DOE, as
appropriate;
historical records of the external dosimetry program, procedures, and results; and
a quality assurance (QA) program that covers all steps in the activities that determine
individual external dose.
6.2 Program Management and Administration
6.2.0 General Requirements
The external dosimetry program implemented to demonstrate compliance with
10 CFR 835.402(a) shall be adequate to demonstrate compliance with the dose limits established
in Subpart C of 10 CFR 835 [10 CFR 835.402(b)] and shall be:
accredited by the DOE Laboratory Accreditation Program (DOELAP); or
excepted from DOELAP accreditation in accordance with the DOELAP standards; or
DOE G 441.1-1C 69
5-19-08
determined by the Secretarial Officer responsible for environment, safety and health to
have performance substantially equivalent to that of programs accredited under the
DOE Laboratory Accreditation Program for Personnel Dosimetry [10 CFR 835.402(b)].
Guidance for achieving accreditation or exception from accreditation under the DOELAP
Program is provided in DOE-STD-1111-98. DOE will consider requests for other program
approvals on a case-by-case basis. Programs excepted from DOELAP under the specific
exception criteria established in the governing documents of that program are considered to be
operated in conformance with the program. However, these programs would not be considered
to be in conformance with DOELAP if conditions established in granting that exception, such as
maintenance of alternate accreditation, were not maintained by the contractor.
Section 60
The specification of accreditation requirements only for programs implemented to
demonstrate compliance with 10 CFR 835.402(a) does not reflect an intent to provide a lesser
degree of protection to individuals unlikely to receive doses exceeding the regulatory monitoring
thresholds, nor does it reflect DOE’s intent for it’s contractors to establish two separate
individual monitoring programs (i.e., an accredited program for individuals likely to exceed the
regulatory monitoring thresholds and a non-accredited programs for individuals who are unlikely
to exceed these thresholds). Rather, those individuals who are unlikely to exceed the regulatory
monitoring thresholds are provided an adequate degree of protection by the various engineering
and administrative controls that limit their doses. Implementation of a comprehensive area
monitoring program verifies the effectiveness of these controls. When an accredited dosimeter
program already exists and management of any given facility chooses to provide monitoring for
those individuals who are unlikely to exceed the regulatory monitoring threshold, consideration
should be given to using the accredited program. This will obviate the need to implement two
dosimeter programs, one accredited and the other not. In addition, it will avoid giving workers
who are not required to be monitored the impression that they are being provided a lesser
degree of protection. However, this does not imply that the monitoring program for those
unlikely to exceed the monitoring threshold must be accredited.
Sections 401 - 403 of 10 CFR 835 establish specific monitoring requirements for areas and
individuals. 10 CFR 835 also establishes requirements for preserving dosimetric records and
reporting external radiation doses to individuals.
6.2.1 Organization, Staffing, and Facilities
6.2.1.0 Organization
The external dosimetry program should be administered by the radiological control
organization under the leadership of the radiological control manager. When elements of the
external dosimetry program are performed by a subcontractor, the radiological control
organization should establish contractual standards and assessments that ensure the
subcontractor meets all applicable requirements in 10 CFR 835, the documented radiation
protection program, DOELAP standards, and the technical basis document.
6.2.1.1 Staffing
DOE G 441.1-1C 70
5-19-08
Management should maintain an adequate staff with the necessary expertise and skill to
implement the external dosimetry program. For staff members responsible for evaluating
external doses, management should establish minimum qualification standards that include
both experience and education requirements. Additional guidance on education, skills, and
training is provided in Chapter 3 and DOE STD-1107-2007, KNOWLEDGE, SKILLS, AND ABILITIES
FOR KEY RADIATION PROTECTION POSITIONS AT DOE FACILITIES (DOE 2007g). Personnel should
be familiar, at a level commensurate with their assigned responsibilities, with relevant external
dosimetry literature and related recommendations of national and international scientific
organizations.
6.2.1.2 Facilities and Resources
Computational facilities and software tools used by external dosimetry personnel should be
adequate for performing calculations required for dose evaluation. A library of handbooks,
reference materials, scientific publications, applicable regulations and guidance documents
should be readily available.
6.2.2 Technical Basis Document
Section 61
A technical basis document should be developed for the external dosimetry program to
provide (or provide reference to) the regulatory, scientific, and technical foundation of the
program. The technical basis document should include:
the methods used for evaluating external doses from workplace and individual
monitoring data and the technical basis for those methods;
justification of categories selected for participation in and exception from DOELAP
personnel dosimeter performance testing;
QA procedures for dosimeters that are outside of the DOELAP testing protocol, as
appropriate;
the physical characteristics of external radiation to be monitored, methods for
calculating external doses, methods for documenting calculations, dose evaluation
quality assurance, and procedures for recording and reporting external dose results;
the methodology used in determining the dose of record when multiple dosimeters are
used and when dosimeters are relocated;
individual monitoring methods, their lower limits of detectability, and monitoring
intervals, along with a rationale or justification for the methods and intervals chosen;
calibration models, parameters, assumptions, and default values used in dosimetric
modeling and evaluation; and
statistical methods for evaluating dosimeter data, using appropriate controls, identifying
above-background values, and analyzing trends.
DOE G 441.1-1C 71
5-19-08
The technical basis document should be reviewed periodically and updated as necessary to
ensure that it remains appropriate for current conditions. The technical basis document should
be handled as a controlled document and retained as an RPP record.
6.2.3 Procedures
10 CFR 835 requires that written procedures be developed and implemented as necessary to
ensure compliance, commensurate with the radiological hazards created by the activity and
consistent with the education, training, and skills of the individuals exposed to those hazards
(10 CFR 835.104). All functions of the external dosimetry program should be specified in written
procedures that provide for appropriate quality control and QA measures. The procedures
should be consistent with 10 CFR 835, the DOELAP technical standards, and the technical basis
document. In summary, the procedures should provide the following information:
methods and requirements for measuring, evaluating, and recording external dose;
methods for consistent collection of workplace and personnel monitoring data, its
evaluation, documentation of results, and records maintenance;
components and reporting structure of the external dosimetry program;
responsibilities of line management and members of the dose evaluation group; and
elements of the area monitoring program that are germane to external dose
determination.
Additional guidance on written procedures is provided in Chapter 3.
6.2.4 Quality Assurance
Internal audits shall be conducted such that all functional elements are reviewed no less
frequently than every 36 months and shall include program content and implementation
(10 CFR 835.102). External peer-review by qualified individuals, on a periodic basis, is also
recommended. See Chapter 3 for further information on internal audits.
6.3 Area Monitoring Program
Section 62
The area monitoring program supplements the individual monitoring program by providing a
prospective assessment of radiological conditions, thus facilitating decisions regarding postings,
access controls, work authorizations, and individual monitoring, and providing back-up data for
use in individual dose evaluations. Because of the need to evaluate individual external doses
(prospectively and retrospectively) from contained sources, airborne radioactive material, and
surface contamination, the area monitoring program should include methods for assessing the
degree of hazard arising from each of these hazards to which individuals may be exposed.
Guidance for implementing surface contamination and airborne radioactivity monitoring
programs is provided in Chapters 10 and 11. Guidance for implementing area monitoring for
other external sources of radiation is provided below. For each element of the area monitoring
program, additional guidance is provided in Chapter 5 of the RCS.
DOE G 441.1-1C 72
5-19-08
6.3.0 Monitoring Instruments and Devices
External radiation monitoring instruments and devices include both fixed and portable
instruments that provide real-time indication of radiation levels and passive monitoring devices
(such as TLDs and radio-sensitive film) that provide a retrospective indication of radiological
conditions. Guidance on portable instrument selection, calibration, and checking for operability
is provided in Chapter 9. While Chapter 9 addresses portable instruments, many of the
concepts and practices discussed in Chapter 9, and in the referenced consensus standards, may
be applicable to fixed instruments.
Although fixed instruments provide the advantage of continuous operation with little or no
attention, their application is limited by their lack of mobility. Fixed instruments should be used
to monitor areas and installations:
having a known and relatively predictable operation where little variation in the
radiological hazards is expected;
where monitoring of an access point (and possible provision of an alarm function) is
desirable to warn individuals of hazards in the area;
where it is desirable to continuously monitor an area to detect changes in radiological
conditions, possibly as a result of an unplanned change in process functions;
where continuous monitoring and alarm functions are necessary to prevent unplanned
exposures; and
as necessary to provide input into interlocks, control devices, and alarm systems that are
dependent upon or that control the operation being monitored
Portable instruments are most appropriate for use in performing prospective monitoring
for the purposes of work planning, radiological condition verification, facility integrity
verification, and operational assessments. The quality and utility of the data provided by
portable instruments are highly dependent upon the knowledge and skills of the user.
Because of these important applications and significant vulnerabilities, portable instruments
should be used only by trained individuals (such as specifically-trained radiological workers
and radiological control technicians). Passive monitoring devices (e.g., area monitoring TLDs)
should be placed in areas surrounding radiological areas to verify that doses in these areas
do not exceed the individual monitoring threshold. Passive monitoring devices should be
placed where they will be exposed to radiation fields similar to those affecting individuals
frequenting the area, but should be protected from loss or vandalism. The use of passive
monitoring devices to characterize radiation fields as a part of pre-job planning should also
be considered.
Section 63
6.3.1 Performance of Area Radiation Monitoring
10 CFR 835 defines radiation and high radiation areas in terms of the radiation levels at a
distance of 30 centimeters from the source or from any surface penetrated by the radiation.
Similarly, 10 CFR 835 defines very high radiation areas in terms of the radiation levels at a
DOE G 441.1-1C 73
5-19-08
distance of 100 centimeters. Therefore, area radiation monitoring should be performed at
these distances (consistent with facility hazards) to ensure compliance with the
10 CFR 835.603 area posting requirements. However, actual and likely exposure conditions
should be considered when performing monitoring for task planning, hazard analysis or dose
assessment should also include consideration of. If an individual is likely to linger at a
distance of several feet from a shield wall, use an obvious travel path between stations, or
work within a few inches of a radiation source, measurements should be made at those
locations (and recorded as such) to provide representative information. Such monitoring
should be performed as necessary to ensure compliance with 10 CFR 835.401(a). Methods
used in performing area radiation monitoring should also be adequate to identify localized
variations in radiation levels to facilitate dosimeter placement and individual exposure
reduction actions.
Important variables that should be considered for inclusion in procedures and training
include instrument selection, operation, functional testing, detector orientation, response time,
operational limitations, source-to-detector distance considerations, and documentation
requirements.
6.3.2 Allowance for Physical Characteristics
The physical characteristics of the radiation field present should be considered in the design
of the monitoring program and in the evaluation of external equivqlent dose. These character-
istics include radiation quality, energy, fluence rate, and direction of incidence. If certain
characteristics are not known, the assumed values used as the basis for the area monitoring
program design should be documented in the technical basis document. For instance, if
monitoring for beta particles is performed, but the energies are not known, the energy assumed
and rationale used for calibration purposes should be recorded.
6.3.3 Recourse for Technology Shortfall
The technology may not be available to perform area monitoring for some types of radiation
at levels indicative of the monitoring requirements. If the performance objectives cannot be
achieved for this reason, the facility should
use the best practicable monitoring methods, and
implement enhanced design, operational controls, personnel protection equipment, and
procedures to control external exposures.
6.4 Individual Monitoring Program
This section discusses program features for individual monitoring, compensatory actions for
lost, damaged, or contaminated dosimeters, nuclear accident dosimetry, and dosimetry for
planned special exposures.
6.4.0 Establishing the Need for Individual Monitoring
DOE G 441.1-1C 74
5-19-08
Section 64
It is usually not necessary for all individuals at a facility to wear dosimeters unless there is a
documented technical basis. Unnecessary issuance of dosimeters should be avoided. If an
individual does not enter areas where there is a likelihood of external exposure resulting in a
dose near or in excess of the regulatory monitoring thresholds, issuance of a dosimeter to that
individual is discouraged. For reasons of practicality and uniformity, decisions regarding those
individuals to whom dosimeters are issued should be made on the basis of work group
affiliation, type of work to be performed, and/or areas to be entered. There is generally no need
to perform calculations regarding individual dose expectations to support decisions regarding
the provision of individual dosimeters. The issuance of dosimeters to concerned individuals
should not be a substitute for providing information, training, access controls, and a
comprehensive area monitoring program. The criteria for the selection of individuals to be
monitored should be documented in the technical basis document.
10 CFR 835 establishes individual monitoring requirements based on the likelihood of an
individual receiving a dose in excess of a regulatory monitoring threshold. In determining the
likelihood of potential exposures, the use of professional judgment is necessary. This judgment
should include consideration of the following:
areas to which the individual will have access;
the individual's previous occupational dose during the current year;
activities taking place in the areas to be entered;
restrictions on areas entered or time in these areas;
design basis radiological conditions in the areas to be entered;
documentation of actual radiological conditions in the areas to be entered, obtained
through prior individual and area monitoring; and
potential for changes that may affect the radiological conditions.
Except for provisions for nuclear accident dosimetry, it is not necessary to include
consideration of accidents or emergencies, because these events are not considered "likely."
There are many instances where groups conduct site tours. A common practice is to only
monitor the individual conducting the tour. This may be appropriate depending on the areas
being toured and the classification of the individuals on the tour. For example, this practice is
appropriate for tours limited to members of the public touring well characterized areas with no
measurable radiation levels above background. If it is later found that there was an unexpected
exposure, doses may be evaluated from the dosimeter of the individual conducting the tour.
This is consistent with RCS Section 511, which states that DOE discourages the issuance of
dosimeters to individuals other than those entering areas where there is a likelihood of external
exposure in excess of the monitoring thresholds given in 10 CFR 835.
DOE G 441.1-1C 75
5-19-08
If the tour group consists of individuals receiving occupational exposure (i.e., situations
where being on the tour is part of an individual’s job function, such as tours by external auditors
or subject matter experts) and the tour could result in individual receiving measurable doses,
then an evaluation should be made on the need for monitoring the individuals on the tour. The
evaluation should consider the expected magnitude of any dose received during the tour and
during subsequent work as well as consideration of previous occupational doses received during
Section 65
the year, and individual dose monitoring requirements of 10 CFR 835.402. Where this evaluation
cannot be accurately performed by the site because of complexity or lack of dosimetry
information (e.g., the individual has visited, or may visit, more than one site or has not received
dosimetry reports) each individual should be monitored.
When the tour guide carries the dosimeter for the tour, each member of the tour should
be told that their dose will be assigned based upon the tour guide’s dosimeter and given the
opportunity to request an individual dosimeter be issued to that individual.
Individuals should not wear a dosimeter at multiple sites without appropriate administrative
controls. If an individual is allowed to wear his or her resident site issued dosimeter at another
site (in lieu of being issued a dosimeter at the visited site), acceptable methods to meet the
reporting requirements include:
Processing the dosimeter at the conclusion of each site visit;
Issuing a self-reading dosimeter and using the results to assess dosimeter of record
results by location; and
Attributing dose only to those sites where the monitoring is performed in accordance
with 10 CFR 835.402.
The method selected should have a sound technical basis and be consistent with external
dosimetry technical basis documentation for all affected sites, The RPP and the external
dosimetry technical basis documentation should also discuss the geographic boundaries of the
site where that method will be applied.
6.4.1 Routine Monitoring of Individual External Doses
Individual monitoring shall be performed for those individuals likely to receive external
doses exceeding the monitoring thresholds provided in 10 CFR 835 and for individuals entering
high radiation or very high areas [10 CFR 835.402(a)]. The frequency of collecting and
processing personnel dosimeters depends on the measurement method and associated lower
limit of detectability. The collection/processing frequency should be chosen so that it is
unlikely that an individual will receive a dose equal to or greater than the values listed in
10 CFR 835.402(a) from external radiation without detection and quantification. The specific
physical characteristics of the radiation field should be considered in choosing the
measurement method. These characteristics include radiation type, quality, energy, fluence
rate, and direction of incidence. If these characteristics are not quantified, conservative
DOE G 441.1-1C 76
5-19-08
assumptions should be used until further information is available, and should be stated in the
technical basis document.
6.4.1.0 Whole Body Monitoring
10 CFR 835.402(a) requires monitoring for individuals likely to exceed the specified whole
body dose threshold as a result of exposure to external radiation sources. For radiological
workers this is an effective dose of 0.1 rem (0.001 Sv) or more in a year. 10 CFR 835.2(b)
specifies that for external dose, the equivalent dose to the whole body is assessed at a depth of
1 cm (1000 mg/cm2) in tissue. It also specifies that equivalent dose to the whole body may be
used as effective dose for external exposures [10 CFR 835.2(b), Equivalent dose and Effective
dose].
DOELAP accredited monitoring performed under the previous (10 CFR 835; 1993 - 1998)
definitions (i.e., where deep dose equivalent from external exposures was allowed to be used as
the effective dose equivalent to the whole body and where the effective dose equivalent to the
whole body was evaluated at a tissue depth of 1 cm (1000 mg/cm2) is considered acceptable
monitoring to meet these definitions.
Section 66
For individuals who require individual monitoring, external dose should be determined using
such devices as thermoluminescent dosimeters, track-etch dosimeters, or radiation-sensitive
film. The dosimeter should be worn to provide a measurement of the maximum dose received
at any location on the whole body. When the whole body is exposed fairly uniformly, the
location should be on the front of the torso between the neck and waist. For non-uniform
irradiation, multiple dosimeters should be used or the primary dosimeter should be relocated to
the area receiving the highest dose. Guidance on the use of multiple dosimeters and dosimeter
relocation is provided later in this chapter.
6.4.1.1 Lens of the Eye Monitoring
The equivalent dose to the lens of the eye is assessed at a depth of 0.3 cm in tissue
(300 mg/cm2) [10 CFR 835.2(b), Equivalent dose].
For uniform exposures, a measurement taken in the torso region is sufficient. For
non-uniform exposures that would result in an individual receiving a significantly higher dose to
the lens of the eye than to the whole body, such as access to or near reactor beams, X-ray
machines, sources of beta radiation, and shield penetrations, the dose should be measured near
the eye, such as with a dosimeter worn on the side of the head or forehead.
For beta particles with maximum energies less than about 3.5 MeV, the dose limit to the skin
is more restrictive than that for the lens of the eye. At higher energies, the lens of the eye dose
limit dominates. Therefore, at beta energies below 3.5 MeV, if it can be shown that skin
monitoring is not required, then it follows that lens of the eye monitoring is also not required
(See International Commission on Radiation Units and Measurements (ICRU) Report No. 43,
Determination of Dose Equivalents from External Sources - Part 2 [ICRU 1988)]. Protective
eyewear using 1/10-inch (0.254 cm) of acrylic plastic will completely attenuate beta particles
with maximum energies < 800 KeV. This covers most beta-emitting isotopes with the exception
of P-32, Y-90, and Pa-234. See the Radiological Health Handbook (BRH 1970).
DOE G 441.1-1C 77
5-19-08
6.4.1.2 Skin and Extremity Monitoring
Exposure to the extremities and skin from external radiation (except for non-uniform
exposure of the skin as discussed in Section 6.4.1.4 ) shall be assessed at a depth of 0.007 cm
(7 mg/cm2) in tissue [10 CFR 835.2(b), Equivalent dose].
Monitoring for skin exposure is usually performed in conjunction with that for the effective
dose to the whole body using a single whole body dosimeter. This method is adequate for
uniform or nearly uniform fields. Guidance on the use of extremity dosimeters is provided later
in this chapter.
When monitoring the extremities, if the most exposed location is not directly monitored, a
field correction factor may be applied based the gradient between the location monitored and
the most exposed location (or the equivalent dose at contact if there is direct source-to-skin
or -extremity contact). Because of difficulties associated with inducing an albedo effect
necessary for proper function of commonly-available neutron dosimeters, monitoring for
neutron dose to the extremities can present special challenges to the external dosimetry
program. Neutron dose to the extremities may be determined by a variety of methods:
direct measurement by neutron sensitive dosimeters, when available;
Section 67
barring sufficient neutron energy information, or for ease in implementation, a factor of
two (i.e., a doubling) may be applied to neutron doses calculated using the existing
neutron quality factors;
application of a gamma dose to neutron dose correction factor determined through the
measurement of the gamma and neutron dose rates incident to the affected extremities;
or
application of a whole body dose to extremity dose correction factor determined
through measurements of the neutron dose rates incident to both the whole body and
the affected extremities.
Justification for the choice of dosimeter and placement of dosimeter and results of field
gradient measurements should be provided in the technical basis document.
6.4.1.3 Embryo/Fetal Monitoring
Following the pregnancy declaration, a declared pregnant worker should continue to wear
her dosimeter in the normal manner if she will be entering areas or performing work for which
individual monitoring is required. If she is in an area where the dose is likely to approach 50
millirem (0.5 mSv) in a month, a supplemental dosimeter should be worn to obtain a monthly
estimate of the dose. If she is exposed to localized sources of radiation, the supplemental
dosimeter should be worn on or near the abdomen.
Guidance for determining the dose to the embryo/fetus is provided in Chapter 8.
6.4.1.4 Non-Uniform Radiation Fields
DOE G 441.1-1C 78
5-19-08
When individuals will be exposed to radiation in a manner that will result in significantly
non-uniform doses to various areas of the whole body, multiple dosimeters should be issued or
the primary dosimeter should be relocated to the area of the whole body likely to receive the
highest dose. Such a situation may result from an irregular distribution of radiation sources in
the area, a continued positioning of the individual that causes an irregular radiation exposure to
the body, or the effects of personal protective equipment (e.g., lead aprons) or other shielding
devices that do not protect all portions of the whole body in a uniformly effective manner.
Multiple dosimeters should be used to assess whole-body dose when radiation fields vary by >
50% over the whole body and the anticipated dose to the maximally-exposed area is >
100 millirem (1 mSv) (equivalent dose to the whole body) or 1 rem (0.01 Sv) (equivalent dose to
the skin or extremity) during the dosimeter issue period. The technical basis document should
provide details regarding the basis for dosimeter location(s) under non-uniform exposure
conditions. Preliminary judgments on the need for multiple dosimeters and placement of
multiple dosimeters should be made from direct exposure rate surveys with portable monitoring
instruments or monitoring with dosimeters placed on phantoms. Multiple dosimeters may be
used at any time to provide more detailed information for estimates of whole body dose.
Additional guidance on the use of multiple dosimeters is provided in ANSI/HPS N13.41, Criteria
for Performing Multiple Dosimetry (ANSI/HPS 1997a). Guidance on the evaluation of individual
dose from multiple dosimeter results is provided later in this chapter.
When the radiation field is well characterized and the individual's orientation is known,
relocation of the primary dosimeter may be preferable to issuance of multiple dosimeters. If
dosimeter relocation is desirable, the individual's dosimeter should be relocated to the portion
Section 68
of the whole body likely to receive the highest dose. Dosimeter relocation should be conducted
in conformance with management-approved procedures or work authorizations, such as
radiological work permits. Dosimeter relocation should not be performed by individuals without
written authorization.
Multiple dosimeters should be placed at locations on the body likely to receive the highest
dose equivalent. Common locations for multiple dosimeter placement include the head,
chest, back, gonads, upper arms, and upper legs. If multiple dosimeters are used, the routine
whole body dosimeter should be replaced with the set of multiple dosimeters during the
multibadging activity. This keeps the normal dosimetry on its regular processing cycle and
eliminates the possibility of "double counting" dosimetry results.
6.4.1.5 Supplemental Dosimeters
Supplemental dosimeters include, but are not limited to, electronic dosimeters, pocket
dosimeters, and other self-reading, alarming dosimeters. Any individual entering a high
radiation area or very high radiation area shall wear a supplemental dosimeter or be monitored
by another means capable of providing an immediate estimate of that individual’s integrated
equivalent dose to the whole body during the entry (e.g., stay-time tracking)
[10 CFR 835.502(a)].
Supplemental dosimeters should be read periodically while in use. The range and energy
dependence of supplemental dosimeters, particularly to low-energy beta and X-ray radiation,
DOE G 441.1-1C 79
5-19-08
should be considered in determining their applicability. Supplemental dosimeters with a limited
range should be selected with the lowest range applicable for the anticipated exposure.
Chapters 3 and 5 of the RCS provide additional guidance on the use of supplemental dosimeters.
6.4.2 Lost, Damaged, or Contaminated Dosimeters
An individual whose dosimeter is lost, damaged, or contaminated should place work in a
safe condition, immediately exit the area, and report the occurrence to the radiological control
organization.
Reentry of the individual into radiological areas should not be made until a review has been
conducted, the individual has been issued a new dosimeter, and management has approved
reentry. The review may be as simple as a documented survey showing the dosimeter not to be
contaminated, in which case the worker may go back to work immediately. Otherwise, a review
should include a dose evaluation to replace the results of the lost, damaged, or contaminated
personnel dosimeter and should determine if work can continue while an investigation is in
progress.
6.4.3 Nuclear Accident Dosimetry
Nuclear accident dosimetry shall be provided to individuals in installations possessing
sufficient quantities of fissile material to potentially constitute a critical mass, such that the
excessive exposure of individuals to radiation from a nuclear accident is possible
[10 CFR 835.1304(a)]. Nuclear accident dosimetry shall include:
a method to conduct initial screening of individuals involved in a nuclear accident to
determine whether significant exposures to radiation occurred;
methods and equipment for analysis of biological materials;
a system of fixed nuclear accident dosimeter units; and
personal nuclear accident dosimeters [10 CFR 835.1304(b)].
Section 69
Initial screening methods should include measurements of activation products in and on the
bodies of exposed individuals (e.g., sodium-24 in the body, activation of jewelry) and/or
evaluation of individual locations during the accident, as appropriate. Methods and equipment
for analysis of biological materials should include appropriate counting systems maintained in
operable condition and sample collection and preparation processes. Acceptable methods for
implementing a nuclear accident dosimetry program are described in ANSI N13.3, Dosimetry for
Criticality Accidents (ANSI 1988). Additional guidance is provided in Chapter 5 of the RCS.
Placement of fixed nuclear accident dosimeter units should consider the nature of the
operations, structural design characteristics, accessibility of areas to personnel, and recovery of
units after a criticality accident. The number of fixed nuclear accident dosimeter units, their
locations, the effect of intervening shielding, and an analysis demonstrating the above
performance criteria should be documented in the technical basis document.
DOE G 441.1-1C 80
5-19-08
6.4.4 Planned Special Exposures
Planned special exposures are included in an individual's occupational dose record, but shall
not be considered when determining compliance with the occupational dose limits
[10 CFR 835.1(b)]. In order to maintain separate records of doses resulting from planned special
exposures and routine occupational exposures, dosimeters adequate to measure the potential
doses and appropriate for the work to be performed and specific radiological circumstances
should be provided for the planned special exposure.
6.4.5 Personal Protective Equipment
Use of personal protective equipment (such as shielded aprons or other clothing items) may
present special challenges in the placement of personnel dosimeters and the determination of
the dose equivalent. Use of such items may create non-uniform radiation field conditions similar
to those discussed in Section 6.4.1.4 of this Guide. If so, the placement of dosimeters and
determination of the individual dose equivalent should be conducted consistent with that
guidance. If the effect of personal protective equipment is not significant enough to create a
non-uniform radiation field as described in the technical basis document, then the dosimeter
should be placed on the area of the body likely to receive the highest equivalent dose. The
effect of the personal protective equipment on albedo effects that are critical for the proper
function of neutron dosimeters should also be considered.
6.5 External Dose Evaluation
Radiation protection requirements are expressed in terms of limiting values of equivalent
dose to individuals. The limiting values for equivalent dose in 10 CFR 835 are specified as total
effective dose to the whole body and equivalent dose for other organs and tissues.
Methods for evaluating the various doses from external exposures should be based on
recommendations given in International Commission on Radiological Protection (ICRP)
Publications, NCRP Report No. 91, Recommendations on Limits for Exposure to Ionizing Radiation
(NCRP 1987b), and other reports of the NCRP that address improvements and updates of the
science of external dosimetry. Other methods may be used provided they are documented and
justified in the procedures and/or technical basis document. The dose calculation methodology
shall use the radiation weighting factors and tissue or organ weighting factors in the definition
section of 10 CFR 835 [10 CFR 835.203(b)].
Section 70
6.5.0 Required Dose Calculations
Records shall be maintained to document the doses received by all individuals monitored in
accordance with 10 CFR 835.402 and to document doses received as a result of planned special
exposures, doses exceeding the monitoring thresholds of 835.402, and authorized emergency
exposures [10 CFR 835.702(a)]. The following quantities shall be recorded for external dose
received during the year:
effective dose from external sources of radiation (equivalent dose to the whole body
may be used as effective dose for external exposure) [10 CFR 835.702(c)(3)(i)];
DOE G 441.1-1C 81
5-19-08
equivalent dose to the lens of the eye [10 CFR 835.702(c)(3)(ii)];
equivalent dose to the skin [10 CFR 835.702(c)(3)(iii)]; and
equivalent dose to the extremities [10 CFR 835.702(c)(3)(iv)].
For airborne radionuclides that pose an external exposure hazard, the derived air
concentration (DAC) values in Appendix C of 10 CFR 835 shall be used to control exposure to
airborne radionuclides [10 CFR 835.209(a)]. See Appendix C of Chapter 16 of the Guide for a
listing of values. The technical basis document should note which radionuclides could be
present and whether the individual dosimeter responds correctly to the quality of the radiation
or whether immersion exposures should be calculated separately and added to dosimeter
results. When it is necessary to apply airborne radioactivity monitoring results to individual
external dose assessment, such applications should include consideration of the concentration
of the contaminant in the workplace and the duration of the exposure (i.e., maintenance of
records of DAC-hours of exposure). The air immersion DAC values in 10 CFR 835 Appendix C
were calculated for a continuous (2,000 hours per year), non-shielded exposure via immersion in
a semi-infinite atmospheric cloud. 10 CFR 835 allows modification of the DAC values contained
in Appendix C to allow for submersion in a cloud of finite dimensions.
Personnel dosimeters should be calibrated to monitor for dose directly or indirectly through
the use of a calibration factor. Dosimetry services that process dosimeters typically report
personnel doses in units or subunits of rem and no further calculations need be performed
unless modifying factors are applied.
When neutron monitoring is performed, the neutron equivalent dose is added to the non-
neutron equivalent dose to determine the total equivalent dose to the whole body, and added,
as applicable, to the extremity equivalent dose, and/or the lens of the eye equivalent dose.
Varying neutron energy spectra are encountered at field locations, depending on the original
energy of the neutrons and the degree of moderation and attenuation. These neutron energy
spectra may not be representative of the energy spectra used in DOELAP. If this situation exists,
specific field correction factors should be developed and used to adequately assess the neutron
equivalent dose. The development and use of the field correction factors should be reflected in
the technical basis document. Examples of methods for developing field correction factors can
be found in Personnel Neutron Dose Assessment Upgrade (PNL 1988b) and in Neutron Dose and
Energy Spectra Measurements at Savannah River Plant (PNL 1987).
Section 71
The adoption of ICRP Publication 60 dosimetric quantities and units results in revising the
assessment of neutron exposures from using the quality factors to using radiation weighting
factors. For the energy range of 0.1 to 2 MeV the radiation weighting factor is approximately a
factor of two greater than the corresponding quality factor (from 10 to 20). Specific field
correction factors may be developed and used to adequately assess the neutron equivalent
dose. In lieu of this approach, a scaling factor may be developed and used. The scaling factor
may be based on the neutron spectrum and taking a ratio of the differences between the quality
factor and radiation weighting factor for each neutron energy grouping. Barring sufficient
neutron energy information, or for ease in implementation, a factor of two (i.e., a doubling) may
be applied to neutron doses calculated using the existing neutron quality factors. DOE will
DOE G 441.1-1C 82
5-19-08
continue to evaluate neutron dose assessment using radiation weighting factors and will provide
additional guidance as more information is obtained.
DOELAP is working towards adopting standards consistent with ICRP Publication 60
dosimetric quantities and units. It is anticipated that this change will be effective prior to the 10
CFR 835 amendment compliance due date of July 8, 2010. This should address issues relating to
use of personnel monitoring devices to assess neutron exposures. Prior to DOELAP updating its
requirements, sites may consider implementing the above mentioned scaling factor or a
comparable approach for assessing neutron exposures from personnel monitoring devices.
In addition, sites may find it advantageous for certain applications to continue calibrating
portable neutron survey instruments using the existing neutron quality factors. For example,
neutron calibrations using existing neutron quality factors may correlate better with surveys
conducted to meet Department of Transportation requirements. If this approach is taken, the
above mentioned scaling factor or a comparable approach may then be applied to portable
neutron survey instrument results and used for controlling and limiting individual neutron
exposures.
6.5.1 Special Considerations
Personnel dosimeter measurements are the preferred source of data for evaluating the
external dose of individuals likely to exceed the monitoring thresholds. Area monitoring data
and other personnel monitoring data should be used to evaluate external dose if personnel
dosimeter measurements are not feasible or are not available. When personnel dosimeter
measurements are not available, a dose evaluation should be performed for that period. The
dose evaluation should be based on personnel dosimeter results from other individuals in the
same area, on previously recorded doses (provided no significant changes in exposure rates
would be anticipated), or on area monitoring results of the ambient radiation levels. These
estimated or assigned doses shall be clearly recorded and maintained as such [10 CFR 835.702(a)
and (g)]. When area monitoring results are used to estimate individual dose, the results of
surveys, measurements and calculations used to determine individual occupational exposure
from external sources shall be recorded [10 CFR 835.703(b)].
Section 72
When an individual is provided multiple dosimeters, the dose measured by the highest
responding dosimeter on the whole body should be assigned as the whole body dose of record.
When multiple dosimeters are employed more than once during the year, dosimeter results may
be summed by location and the highest total assigned as the whole body dose of record.
However, sufficient records should exist to demonstrate that the dose to portions of the whole
body between the monitoring locations did not exceed that recorded for the monitoring
location. For example, if both the left and right upper arms were monitored, adequate records
should be maintained to demonstrate that the dose to the head and torso, which may have been
exposed as a result of exposure to both arms, did not exceed the dose to either upper arm.
If tissue weighting factors are used to calculate effective dose from external radiation fields,
the weighting factors in 10 CFR 835.2 shall be used [10 CFR 835.203(b)]. If necessary, a
compartmentalization methodology, such as that recommended in ANSI/HPS N13.41 (ANSI/HPS
1997) modified to use the 10 CFR 835 specified tissue weighting factors, may be applied to the
multiple dosimeter results. A calculation of this type provides a better representation of the risk
DOE G 441.1-1C 83
5-19-08
to the monitored individual. Whatever methodology is selected, all multiple dosimeter results
shall be recorded [10 CFR 835.702(a) and (g)].
When supplemental dosimeters are used, the results should be compared to the results
from the primary dosimeter issued to the same individual (if the issue periods for the primary
and supplemental dosimeters are the same). If the dose results differ by >50% from the primary
dosimeter and the dose from the primary dosimeter is >100 millirem (1 mSv), an investigation
should be initiated to explain the difference.
10 CFR 835.205 places additional requirements on evaluating and recording doses from
non-uniform exposures of the skin from X-rays, beta radiation, and/or radioactive materials on
the skin, including hot particles. The technical basis document should provide the basis for the
action level used to identify the need for such evaluations. Decisions regarding the appropriate
action levels should be based upon such factors as the likely magnitude of events resulting in
non-uniform exposure of the skin, the likelihood of repeated events, and potential resulting
doses (total of all events). An action level of 100 millirem (1 mSv) for the evaluation of skin dose
for general employees is recommended. Further information regarding hot particles can be
found in NCRP Report No. 106, Limit for Exposure to "Hot Particles" on the Skin (NCRP 1989).
For non-uniform exposures of the skin, the assessment of the exposed area should be
recorded with the equivalent dose to the skin. Non-uniform exposures of the skin of the
extremities from X-rays, beta radiation, and radioactive materials on the skin, including hot
particles, should be assigned to the extremity, not the skin. If the non-uniform equivalent dose
to the skin does not exceed 1 rem (0.01 Sv), then recording of the dose is not required
[10 CFR 835.702(b)].
When an individual has been monitored for extremity exposure at some time during the
calendar year, but is not monitored for the entire year, the equivalent dose to the skin or
extremity from the whole body dosimeter should be used as the extremity dose of record for
periods when extremity dosimeters are not worn.
Section 73
If it is necessary to determine an equivalent dose to the lens of the eye in the absence of
reliable monitoring data (i.e., in the absence of properly calibrated lens of the eye dosimeters),
the equivalent dose to the skin or extremity should be used as an approximation of the lens of
the eye dose or appropriate dose conversion factors should be used to convert the dosimeter
reading to the lens of the eye dose. Appropriate dose conversion factors may be found in ICRP
Publication 74, Conversion Coefficients for Use in Radiological Protection Against External
Radiation (ICRP 1996), or peer-reviewed journals or may be determined locally through
performance of a series of tests using dosimeters with different filters.
In the case of a large dose, actual or suspected, quick initial estimates should be made based
on stay time and exposure rate. These estimates should be used to limit further external dose
until dosimeter and bioassay results are available.
6.6 Recordkeeping and Reporting
10 CFR 835 requires that records be maintained to document certain aspects of the external
dosimetry program. These records include radiation dose records, instrument and equipment
DOE G 441.1-1C 84
5-19-08
calibration records, monitoring procedures, and area monitoring results. 10 CFR 835 also
requires that certain reports be provided to individuals on their exposure received while
performing their duties. Chapter 13 provides detailed guidance on the records necessary to
document the external dosimetry program and the reports to individuals required by
10 CFR 835. Chapter 7 of the RCS provides additional guidance.
DOE G 441.1-1C 85
5-19-08
7.0 RADIATION GENERATING DEVICES
The Radiation Generating Devices (RGDs) addressed in this chapter may be classified as
either devices that are electrically energized to produce ionizing radiation or sealed radioactive
sources that emit radiation continuously. RGDs are used at DOE sites with a great variety of
configurations and operating characteristics and in a wide spectrum of applications. This Guide
addresses RGDs used for industrial and research applications, but does not address RGDs used
for patient diagnostic or therapeutic medical applications. Medical RGDs should be registered
with the cognizant regulatory agency which typically is a Federal, state or local level authority.
Specific examples of RGDs addressed by this Guide include: sealed photon- or
neutron-emitting radioactive sources; X-ray producing radiography equipment; research and
analytical X-ray or electron beam machines; sealed radioactive sources used as irradiators;
particle accelerators; neutron generators; Van de Graff generators; electromagnetic pulse
generators (if capable of producing ionizing radiation); electron microscopes; electron arc
welders; microwave cavities that produce X-rays incidentally, and cabinet X-ray machines used
for security applications.
Note that sealed radioactive sources are specifically addressed in Chapter 15. The guidance
provided in this Guide should be considered in addition to that provided in Chapter 15 for those
sealed radioactive sources that produce radiation fields exceeding 100 millirem (1 mSv) in one
hour at a distance of 30 centimeters from the source.
7.1 Implementation Guidance
10 CFR 835 must be generic to cover the wide spectrum of facilities and activities within the
DOE complex. To ensure an adequate level of radiological safety and compliance with
10 CFR 835, the requirements and guidance provided in the following secondary documents
should be implemented, to the extent appropriate to site-specific activities and hazards.
Section 74
10 CFR 34, Licenses for Radiography and Radiation Safety Requirements for
Radiographic Operations (NRC 1992);
ANSI N43.3, American National Standard For General Radiation Safety - Installations
Using Non-Medical X-Ray and Sealed Gamma-Ray Sources, Energies Up to 10 MeV
(which updates ANSI N543-1974) (ANSI 1993);
ANSI/HPS N43.2, Radiation Safety for X-Ray Diffraction and Fluorescence Analysis
Equipment (ANSI/HPS 2001a); and
ANSI/HPS N43.5, Radiological Safety Standard for the Design of Radiographic and
Fluoroscopic Industrial X-Ray Equipment (Formerly called N537) (ANSI/HPS 2005).
Should any conflict exist between the requirements and guidance provided in these
standards and the requirements of 10 CFR 835, then the requirements of 10 CFR 835 take
precedence. This Guide provides guidance that supplements that provided by the ANSI
Standards discussed above.
DOE G 441.1-1C 86
5-19-08
7.2 Administrative Organization and Controls
RGD control should be maintained by individuals responsible for RGD operations. Overview
for radiological safety should be provided by the independent radiological control organization.
Within smaller organizations, where one individual may be responsible for multiple roles (such
as RGD custodian, qualified expert, and radiological control staff), independent oversight of that
individual’s activities should be provided to ensure the ongoing quality of the RGD program.
7.2.0 Contractor Management
To implement their responsibilities, management should perform the following:
appoint a RGD Custodian for each RGD;
exercise supervision to ensure safe RGD operation;
review RGD procedures and operational and maintenance logs;
schedule periodic inspections and monitoring;
approve operating and emergency procedures;
schedule and otherwise provide for training to ensure that RGD Custodians and RGD
Operators are trained and re-certified (see Chapter 14 for guidance concerning training
of personnel); and
promptly terminate the operation of any unsafe RGD installation.
7.2.1 RGD Custodian
The appointed RGD Custodian should provide direct control over RGD installations and
operations. The RGD Custodian should ensure that the RGD installation is operated and
maintained safely and in accordance with the requirements of the site-specific RPP. Specific
responsibilities of the RGD Custodian should include the following:
controlling the keys to RGD installations, RGDs, and/or RGD storage facilities and
authorizing the operation of the RGD installation;
ensuring that RGD Operators follow applicable operating procedures;
ensuring that RGD Operators follow the applicable Radiological Work Permit (RWP), or
other written authorization;
ensuring that required dosimeters are properly worn;
ensuring that inspections of RGD interlocks, warning lights, and other safety features are
performed and documented;
ensuring that all required monitoring is performed and documented;
DOE G 441.1-1C 87
5-19-08
ensuring that all RGD Operators are trained;
reviewing and approving materials used for training RGD Operators, in cooperation with
the radiological control staff;
ensuring that accountability records of assigned RGDs are maintained;
notifying the radiological control staff of changes in shielding configuration, use,
storage, disposal, or loss of a RGD;
ensuring proper disposition of unneeded RGDs;
ensuring that sealed radioactive source integrity tests are performed; and
Section 75
maintaining schematics (mechanical and electrical), safety device wiring diagrams,
manufacturer provided instruction manuals, and operations and maintenance records.
7.2.2 RGD Operator
RGD Operators are those individuals authorized by the RGD Custodian to use the RGD.
The RGD Operator should:
ensure proper control of the RGD installation and/or area;
ensure that inspections and monitoring are performed and documented;
ensure that required dosimeters are worn properly by all individuals in the vicinity of
RGD operations;
follow the applicable RWP, or alternative authorization, and ensures that other
individuals also adhere to the requirements of those documents;
establish control of all adjacent areas where individuals could receive a dose
approaching administrative limits and ensure that those areas are unoccupied during
RGD operations;
maintain access control over the actual RGD exposure area;
follow all applicable operating procedures; and
promptly terminate unsafe RGD operations.
7.2.3 Qualified Expert
A qualified expert(s) should be appointed by management. To ensure technical
qualification, the qualified expert should be approved by the radiological control manager. The
qualified expert should have knowledge and training necessary to: (1) measure ionizing
radiations; (2) analyze the significance and evaluate the potential health effects of monitoring
DOE G 441.1-1C 88
5-19-08
results; and (3) advise on matters related to radiological control as it pertains to installations
covered by this Guide. The qualified expert should have in-depth knowledge of characteristics
associated with RGDs, RGD installations, and applicable Rules, Manuals, Orders, and Standards.
If the radiation generating device is capable of producing very high acute doses, i.e., such that
the hazard are to be analyzed in the documented safety analysis, the expertise should include
familiarity with any associated safety system software and hardware used to prevent major
radiological accidents.
The qualified expert should periodically review the following areas and provide
recommendations to the radiological control manager:
the design or modification of RGD installations;
the results of pre-operational inspections and radiological monitoring;
the engineered safety features and administrative controls;
the need for and adequacy of the personnel monitoring program for the installation;
and
the training materials used for the RGD Custodians and Operators.
7.2.4 Radiological Control Manager
A radiological control manager should be designated to ensure independent overview of
radiological operations, including RGDs. The radiological control manager's function is similar to
that of the radiological protection supervisor or radiation protection officer, as described in the
specific ANSI standards referenced in this Guide and publications of the National Council on
Radiation Protection and Measurements (NCRP). Additional guidance for radiological control
manager responsibilities is provided in RCS Articles 141and 142 and ANSI N43.3.
7.2.5 Radiological Control Organization
The radiological control organization (RCO) should provide support to managers and
radiological workers. The radiological control staff should be established consistent with
Chapter 1 of the RCS.
Radiological control staff should perform the following tasks to implement their functions
described in RCS Articles 141 and 143:
Section 76
evaluate adherence to the RPP by conducting pre-operational and periodic inspections
and radiation monitoring of RGD installations;
under the direction of the radiological control manager, provide radiological support to
line managers and RGD operations;
ensure that all inspections and monitoring are performed and documented;
perform radiation monitoring of open installations to verify proper posting and control
DOE G 441.1-1C 89
5-19-08
of boundaries during operations and removal of hazards (and associated temporary
postings and barriers) after operations;
monitor all RGD installations for potential or actual unsafe operations or conditions and
conformity to the site-specific RPP; and
review the operational and maintenance logs maintained by RGD Custodians and
Operators to ensure that controls are commensurate with existing or potential
radiological hazards.
7.3 Development of Site-Specific Documents
10 CFR 835.104 requires that written procedures be developed and implemented as
necessary to ensure compliance with that regulation, commensurate with the radiological
hazards created by the activity and consistent with the education, training, and skills of the
individuals exposed to the hazards (10 CFR 835.104). Written procedures should be developed
and implemented as necessary to ensure proper implementation of the radiation protection
program elements addressed in this Guide. Additional guidance is provided in Chapter 3.
7.3.0 Radiological Monitoring
Radiological monitoring should be conducted to determine and document the integrity and
adequacy of the shielding and to verify that posting and access control requirements are
satisfactory before the RGD is turned over to the RGD Custodian for routine operation and
periodically thereafter. If there is a potential for exposure in accessible areas adjacent to the
installation, then the adjacent areas should be monitored and should be vacated when
pre-operational monitoring is performed.
Specifically, the pre-operational monitoring program should be designed to:
determine dose rate or integrated dose received in any 1 hour as dependent upon the
pulse capability of the RGD;
evaluate the exposure potential of the RGD at the maximum value of applied voltage or
current, or at the maximum exposed position of the source for sealed radioactive source
installations. RGD(s) should be operated in steps of increasing beam strength until the
highest values are achieved;
include the use of mechanical or electrical devices that restrict beam orientation and
magnitude, and determine the degree of beam restriction, with and without those
devices;
detect and measure potential leaks in the shielding and barriers; and
encompass all geometries in which the useful beam can be directed.
Special monitoring should be conducted as follows:
DOE G 441.1-1C 90
5-19-08
during the performance of maintenance and alignment procedures if the procedures
require the presence of a primary beam;
when any component in the system is disassembled or removed;
any time an inspection of the components in the system reveals an abnormal condition;
whenever personnel monitoring dosimeters or area monitoring show a significant
increase over a previous monitoring period or are approaching administrative limits;
following maintenance or calibration prior to restoration to fully operable status; and
after any modification.
Section 77
It is not necessary to perform radiological monitoring of electrically-energized RGDs (that is,
those RGDs that do not contain radioactive material) during periods when they have been
removed from service and placed in storage. However, when any RGD which has been in
"storage" is being reactivated for use, functional and operational inspections and radiological
monitoring should be performed prior to initial use.
For open installations, where irradiation configurations and boundary conditions are likely
to change frequently, radiation monitoring shall be conducted in response to changing working
parameters [10 CFR 835.401(a)].
After the initial assessment, independent inspections and monitoring should be conducted
as necessary to verify: 1) that RGD operations continue to remain safe; 2) that during the
operation of any open installation, the proper location and posting of boundaries is maintained;
and 3) that after any modification or removal from storage of a RGD installation, the
effectiveness and operability of safety features are adequate. Additional guidance on area
monitoring is provided in Chapter 6.
7.3.1 Sealed Radioactive Source Leak Testing
A program of sealed radioactive source accountability and leak testing for radioactive
contamination and encapsulation integrity shall be implemented (10 CFR 835.1202). Guidance
for this program is provided in Chapter 15.
7.3.2 Area Posting
7.3.2.0 Radiological Conditions
Guidance for posting radiological hazards is provided in Chapter 12.
7.3.2.1 Operational Status
Posting should be used to signify the presence of an intermittent radiation condition. The
posting should also express the method used to convey that a radiation field is present. An
example of such a sign is:
DOE G 441.1-1C 91
5-19-08
"CAUTION: RADIATION BEING PRODUCED OR RADIATION
AREA EXISTS WHEN RED LIGHT IS ON"
The qualified expert should be notified of status changes and pertinent details, e.g., safety
system software errors as well as safety device malfunctioning.
7.3.2.2 Maintenance Status
Any time an installation requires maintenance, the entrance to the area in which the
installation is located and the inside of the installation should be conspicuously posted to
indicate the maintenance status of the installation. Posting should be established:
during the performance of maintenance and alignment procedures if the procedures
require the presence of radiation; and
any time an inspection or monitoring reveals a deficient condition for any safety device.
When a safety device or interlock has been approved to be by-passed or is awaiting repair,
the entrance to the installation and the RGD enclosure should be posted with a prominent sign
bearing the words "SAFETY DEVICE NOT FUNCTIONING" or a similar message.
The qualified expert should be notified of status changes and pertinent details, e.g., safety
system software errors as well as safety devices affected by maintenance or malfunction.
DOE G 441.1-1C 92
5-19-08
7.3.3 Training
Guidance for radiation safety training is provided in Chapter 14 of this Guide. This training
should be augmented with pertinent material provided in DOE-HDBK-1108-2002,
RADIOLOGICAL SAFETY TRAINING FOR ACCELERATOR FACILITIES (DOE 2002b) and
DOE-HDBK-1130-2008, RADIOLOGICAL WORKER (RW) TRAINING MATERIALS, APPENDIX C:
RADIATION SAFETY TRAINING FOR RADIATION-PRODUCING (X-RAY) DEVICES (DOE 2008h).
Additional training guidance is provided in Chapters 3 and 6 of the RCS.
Section 78
7.3.4 Records
Guidance for generation and maintenance of records sufficient to meet the requirements of
10 CFR 835 are provided in Chapter 13.
7.4 Engineered Safety Controls
10 CFR 835.1001 requires that measures be taken to maintain radiation exposures in
controlled areas ALARA. The primary method used shall be engineered controls (e.g.,
confinement, ventilation, remote handling, and shielding); administrative controls shall be
incorporated only as supplemental methods and for specific activities where engineered
controls are demonstrated to be impractical (10 CFR 835.1001). 10 CFR 835.1003 further
requires that during routine operations, the combination of engineered controls and
administrative controls shall provide that the anticipated occupational dose to general
employees does not exceed regulatory limits and that the ALARA process is utilized for
personnel exposures to ionizing radiation. Safety system hardware and software are sometimes
associated with engineered safety features, i.e., for hazards that must be analyzed in a
documented safety analysis.
Engineered controls typically include features that are used to control the work
environment, such as permanent structures, systems, and controls, including shielding, filtered
ventilation systems, remote controls, containment devices, and the use of designs and materials
that facilitate operations, maintenance, and other activities. Temporary engineered controls
(e.g., temporary shielding, confinement and ventilation systems) are typically used to facilitate
short-term or emergent operations when the installed engineered controls do not provide the
desired level of protection. Administrative controls typically include controls that are
implemented by the individual at the work site, including written procedures, technical work
documents, work authorizations, and other controls that are used to guide individual actions in
a manner that will facilitate implementation of the ALARA process (10 CFR 835.1001).
ANSI N43.3 and N43.2 provide specific guidance that should be considered for exempt
shielded (including cabinet X-ray), shielded, unattended, and open installations. As discussed in
the introduction to Chapter 7, not all of the ANSI guidance for shielded, unattended, and open
installations meets the requirements of 10 CFR 835. If the design of the facility cannot be
upgraded in a practical manner to meet the 10 CFR 835 exposure rate criteria, then the
alternative is the implementation of additional access and occupancy controls to meet the
design objectives.
7.4.0 Shielding, Controls, & Safety Devices
DOE G 441.1-1C 93
5-19-08
7.4.0.0 Shielding
Permanent shielding should be designed and installed consistent with the guidance
provided in ANSI N43.3.
The effect of temporary shielding should be evaluated prior to its installation. The
installation, use, and removal of temporary shielding should be controlled by procedures and in
accordance with RCS 314.
7.4.0.1 Access Control and Safety Devices
10 CFR 835.501 establishes requirements for maintaining control over entries into
radiological areas. 10 CFR 835.502 establishes supplemental requirements for entry controls for
high and very high radiation areas. Viewed collectively, these provisions establish a hierarchy of
controls, with general, flexible requirements for all radiological areas and more specific and
stringent requirements for areas of greater hazard.
Section 79
Guidance for establishing appropriate signs and barricades as required by 10 CFR 835.501 is
provided in this Guide. Guidance for establishing appropriate administrative controls is
provided in Chapters 4 and 11. The RCS provides additional guidance for all these. The
remainder of this chapter provides guidance for implementing the physical controls required by
10 CFR 835.501 and 502.
The purpose of access control devices is to prevent unauthorized or inadvertent entry into a
radiological area and/or to warn of a hazard.
If locked entryways are used, the keys used for one RGD installation or storage facility
should not provide access to another RGD installation or storage facility.
Additional measures shall be implemented to ensure individuals are not able to gain
unauthorized or inadvertent access to very high radiation areas [10 CFR 835.502(c)]. Such
measures (i.e., physical constraints) should include locking or securing service doors and panels
with tamper resistant fasteners or the use of multiple and redundant access controls.
Due to the lack of intrinsic shielding and the nature of use, access to a very high radiation
area could be possible for an "open" installation. Additional measures (e.g., interlocked
"photoelectric eye" light beams) should be established to meet this requirement.
There are many situations where, when the access points of a radioactive material
container are closed, there are no physically controlled high radiation areas exterior to the
container. In some of these situations, opening on access point creates a physically
controlled high radiation area exterior to the container. An acceptable approach for these
situations is to implement one or more of the features of 10 CFR 835.502 for the
container. This approach would be consistent with the requirements of 10 CFR 835.502
in acting to prevent uncontrolled or unplanned exposures to individuals.
In addition, in situations where an individual could enter a container and access a
physically controlled high radiation area, one or more of the features of 10 CFR 835.502
DOE G 441.1-1C 94
5-19-08
should also be implemented for the container. In this case, the walls of the container
form the boundary of an accessible physically controlled high radiation area.
The 10 CFR 835.502 features discussed above could include either controlling access
to the container itself or controlling access to the room where the container is residing.
Generally, entryways that are secured closed in such a manner that a tool, such as a
hoist, must be used to gain access, may be considered locked. However, if the opening
tool was left in place such that an individual would not need to make a determined effort
to gain access the entry, in this situation, would not be considered adequately locked or
otherwise secured. Similar unacceptable examples would include leaving a ladder
secured adjacent to a fence meant to restrict access or securing an entryway with a single
bolt and leaving the wrench attached to the bolt. These examples are analogous to the
unacceptable situation of locking an entryway with a key lock and leaving the key in the
lock. These examples are not considered consistent with 10 CFR 835.501(b), which
requires that the degree of control be commensurate with existing and potential
radiological hazards within the area.
While the purpose of locking these areas is to maintain a high level of positive access
Section 80
control, it is recognized that these controls cannot absolutely prevent determined
circumvention of the physical barrier such as with the use of wire cutters or unbolting the
hinges to a doorway. Instances of such determined circumvention should be addressed
with appropriate disciplinary action.
In addition to the above mentioned controls, the entryways or access point to the
container would also need to be labeled, per 10 CFR 835.601, if adequate warning is not
provided by control measures and required posting. The label should specify that the
entryways should not be opened without radiological control approval and that significant
levels of radiation may exist. In the above referenced situation, neither container labeling
nor other posting was implemented to warn individuals not to open the container.
Also, all individuals in the controlled area need to be trained, in accordance with 10
CFR 835.901 (a), in radiation safety prior to receiving occupational exposure during
access to controlled areas at a DOE site or facility. This training would need to address
the importance of following posting and labeling directions as well as the site specific
information and policy concerning the use of tools to open entryways.
7.4.0.2 Interlocks
Doors and/or access panels in exempt shielded, shielded, and unattended installations
should be equipped with one or more fail-safe safety interlocks to prevent irradiation of an
individual [ANSI N43.3(6.5.2)].
DOE G 441.1-1C 95
5-19-08
If an area radiation monitor is incorporated into a safety interlock system, the circuitry
should be such that a failure of the monitor shall either prevent normal access into the area or
operation of the RGD.
7.4.0.3 Device Controls
One or more physical control devices should be used to secure the RGD to prevent
unauthorized access and use. The control system governing the production of radiation should
be equipped with a lock and key to prevent unauthorized use. The key controlling the
production of radiation in one RGD should not control the production in another.
Control devices used to limit RGD time, position (irradiation geometry), current, voltage,
beam intensity, or control panel lights or system indicators should be fail-safe.
7.4.0.4 Run-Safe and Emergency Shutdown Devices
Administrative procedures should be implemented to ensure that the RGD installation and
the RGD safety interlock control devices are such that:
radiation cannot be produced until the interlock system logic has been completely
satisfied;
production of radiation cannot be resumed by merely reestablishing the interlock circuit
at the location where an interlock was tripped; and
the safety circuit cannot be re-energized or reestablished automatically (i.e., there
should be a manual safety circuit reset on or near the main control console).
For each area designated as a high radiation area or very high radiation area,
10 CFR 835.502 provides an option that permits a control device to automatically generate
audible or visible alarm signals to alert individuals and the cognizant RGD Operator of a
potential entry into the area before it occurs. In order to meet ANSI N43.3 guidance, warning
devices should be provided as an addition to any other access control feature in accordance
with the installation specific requirements delineated in Section 7.4.1 of this Guide. These
warning devices are typically warning lights.
Section 81
All RGD warning lights should be red or magenta for consistency. A sufficient number of
lights should be installed so that at least one light is easily visible from all reasonably occupied
areas that may have dangerous radiation levels and from reasonable avenues of approach to
such areas.
However, warning lights (even though interlocked to fail-safe if burnt out) are only passive
in nature. When operating, they generally do not prevent an individual from physical access to a
radiation beam unless they are used as part of a photosensitive circuit. Such a circuit would
remove the radiation beam or field if any individual intercepted the light beam.
Due to the passiveness (i.e., reliance on worker attention and action) of this safety feature
and the potential for failure, at least one interlocked warning light should be used in all
DOE G 441.1-1C 96
5-19-08
circumstances. The interlocked warning light should be used to provide visual indication that
radiation is being produced, and should be used in conjunction with any interlocked safety
device which restricts physical access to a radiation beam or field. This is recommended above
and beyond the installation specific requirements in this Guide, or the minimum required by
10 CFR 835.502. When used in this fashion, the RGD should not be operable when the warning
light is out.
It should not be possible to override the operation of any warning device activated by a
fail-safe function without positive actions by the operator such as resetting controls at the
control console. Where feasible, i.e., for new or significantly modified RGDs that are capable of
producing very high acute doses, i.e., that must be analyzed in the documented safety analysis,
safety system hardware and software should provide additional safety via computer-assisted
operations as well as indicate all abnormal events at the console and remotely notify cognizant
personnel of abnormal events and conditions.
7.4.0.5 Monitoring Instruments
Requirements and guidance for instruments used to measure radiation are given in
10 CFR 835.401(b) and Chapter 9 of this Guide.
7.4.1 Guidance for Specific RGD Installations
In addition to the general guidance in this Guide, there is specific guidance cited from ANSI
N43.3 and N43.2 for each of the primary RGD installations and the open and shielded beam
analytical RGDs. The analytical RGD installations may enclose one or more X-ray devices and/or
sealed radioactive sources.
The ANSI standards specify dose rates that are to be used for installation categorization only
and are not to be interpreted as permissible levels.
7.4.1.0 Accelerators
Small (low voltage, less than or equal to 10 MeV) accelerators used for radiography, ion
implantation, or the production of incidental photons or particles (e.g., neutron generators) in
exempt shielded, shielded, or open installations should be operated in accordance with the
guidance specified by this Guide and the applicable ANSI standards. When accelerators are used
outside of exempt shielded or shielded installations, requirements for open-air radiography
prevail.
When used within shielded installations, determination must be made whether the
requirements for the exempt shielded or shielded installations prevail. Although the basic
radiological control program requirements discussed in this Guide are generally applicable to
the large multi-purpose research accelerators, the complexities associated with these facilities
may require additional consideration beyond the scope of this Guide. Additional requirements
for those RGDs with particle energies exceeding 10 MeV are provided in DOE O 420.2B, Safety of
Accelerator Facilities.
Section 82
7.4.1.1 Electron Devices that Generate X-Rays Incidentally
DOE G 441.1-1C 97
5-19-08
These devices are usually shielded to attenuate the emission of X-rays. Requirements for
the exempt shielded or shielded installations prevail. Examples include electron beam welders,
electron microscopes, pulse generators, etc., and microwave cavities if used as beam guides.
Preoperational inspections and monitoring should be performed initially upon receipt.
However, the requirement for the routine semiannual inspections and monitoring may be
modified at the discretion of the radiological control manager.
7.4.1.2 Cabinet X-Ray Systems
Since these RGDs are used primarily in security applications and are commercially available,
manufacturer requirements for these RGDs are delineated in 21 CFR Part 1020.40.
These RGDs should be procured, categorized, inventoried, operated, inspected and
monitored, and decommissioned in accordance with this Guide to ensure compliance with
10 CFR 835.1001& 1003). Inspections and surveys should be performed as specified in Section
7.4.1.1, of this Guide.
If not commercially obtained, the requirements for an exempt shielded installation prevail.
DOE G 441.1-1C 98
5-19-08
8.0 EVALUATION AND CONTROL OF RADIATION DOSE TO THE
EMBRYO/FETUS
DOE has codified in 10 CFR 835.206 radiation dose limits for the embryo/fetus as a result of
the occupational exposure of a declared pregnant worker. These requirements are established
to provide protection to the embryo/fetus in a manner that does not discriminate against the
rights of the pregnant worker.
Programs established to evaluate and control radiation dose to the embryo/fetus need to
balance protection of the embryo/fetus (from hazards that may arise from the mother's
occupational radiation exposure) against the possibility of work discrimination against the
mother. The choice of providing additional protection to the embryo/fetus is left entirely to the
voluntary discretion of the mother. The Supreme Court ruled in United Automobile Workers v.
Johnson Controls, Inc., 499 U.S.187, 206 (USLW 1991) that "... decisions about the welfare of
future children must be left to the parents who conceive, bear, support, and raise them rather
than to the employers who hire those parents."
8.1 Implementation Guidance
Essential elements of an acceptable program to evaluate and control radiation dose to the
embryo/fetus include:
voluntary, formal declaration of pregnancy, including the estimated date of conception;
voluntary, formal withdrawal of declaration of pregnancy;
work restrictions for workers who have voluntarily declared their pregnancies;
counseling of workers;
dose calculation and monitoring methods;
worker training;
record-keeping; and
reporting.
Acceptable methods for implementing these program elements are discussed in this
chapter.
8.2 Declaration of Pregnancy/Withdrawal of Declaration
Due to the higher sensitivity of the embryo/fetus to ionizing radiation (relative to the
sensitivity of adults), 10 CFR 835 establishes provisions for individuals to voluntarily declare their
pregnancy and to accept restrictions on the equivalent dose to the embryo/fetus (i.e., 0.5 rem
DOE G 441.1-1C 99
5-19-08
(0.005 Sv) gestation period equivalent dose limit, uniform exposure rate) (10 CFR 835.206). It
remains the sole and fundamental responsibility of the worker to decide whether to formally
Section 83
declare her pregnancy and consequently become subject to the above dose limits and
restrictions. It is the employers' responsibility to ensure that the worker is fully informed and
provided with counseling to assist in her decision making. Deciding whether or not to accept
the risk from radiation dose to the embryo/fetus is entirely the responsibility of the pregnant
worker.
A pregnancy may be declared by the pregnant worker or the worker who is planning a
pregnancy, and shall be formally declared in writing [10 CFR 835.2(a)]. The declaration shall
include the estimated date of conception [10 CFR 835.704(d)], and should be declared as early
in the pregnancy as possible. A declared pregnant worker that is planning a pregnancy should
notify her supervisor as soon as possible following verification of conception. The statement
should be signed by the employee and delivered to her supervisor or to a designated contact in
health physics, laboratory safety, occupational health, or medical services. A sample declaration
form is provided in Appendix 8.A of this Guide.
10 CFR 835 also allows an individual who has declared her pregnancy to withdraw her
declaration and to return to the general employee occupational dose limit (5 rem (0.05 Sv) total
effective dose in a year). The employer is considered to be notified of the withdrawal of the
declaration of pregnancy at the time that the individual submits a signed and dated statement
to her supervisor or to the designated contact, indicating that she is withdrawing her formal
declaration of pregnancy. A sample form is provided in Appendix 8.B of this Guide. No
additional explanation or justification should be requested by the employer. The worker shall
be allowed to withdraw her declaration of pregnancy at any time [10 CFR 835.2(a), Declared
pregnant worker], thus terminating any work restrictions. Once such notification has been
made, it is the employer's responsibility to remove any imposed work or area restrictions as
discussed in Section 8.3.
The rights (e.g., right to work) and privacy of the worker should be maintained before,
during, and following any declaration of pregnancy. All aspects of the worker's withdrawal of
the declaration of pregnancy should also be maintained confidential. The rights and privacy of
workers who have chosen not to declare their pregnancy should also be respected. Because
10 CFR 835.901 requires that radiation safety training include discussions of the risks of
exposure to radiation and radioactive materials during pregnancy, and include an individual's
rights and responsibilities as related to the facility's radiation protection program, there is no
need to remind an undeclared pregnant worker of the opportunity for a pregnant employee to
avail herself of the special limits for protection of the embryo/fetus. Such reminders would be
inappropriate in light of the United Auto Workers v. Johnson Controls, Inc. case previously cited.
Chapter 14 provides guidance on initial and biennial training, as well as recommendations for
annual refresher training.
8.3 Work Restrictions Following Declarations of Pregnancy
DOE G 441.1-1C 100
5-19-08
Following the submittal of a declaration of pregnancy, the radiation equivalent dose
received by the embryo/fetus prior to the declaration (i.e., from the estimated date of
conception to the date of declaration) should be calculated as soon as practicable. Section 8.5 of
Section 84
this Guide provides an acceptable methodology. Once this equivalent dose has been calculated,
the dose equivalent allowed for the remaining gestation period should be determined. An
evaluation of the equivalent dose that the embryo/fetus is likely to receive while the declared
pregnant worker is performing her current job duties should be performed to determine if work
restrictions are necessary. The evaluation should take into consideration the 0.5 rem equivalent
dose limit, the equivalent dose remaining for the gestation period, and the requirement not to
vary substantially above a uniform exposure rate that would satisfy the 0.5 rem limit during the
gestation period. If the nature of the declared pregnant worker’s duties make it likely that either
the 0.5 rem limit will be exceeded or that substantial variation will occur, then work restrictions
shall be established [10 CFR 835.206(a) and (b)]. If it is determined that the equivalent dose to
the embryo/fetus has already exceeded 0.5 rem, the declared pregnant worker shall not be
assigned to tasks where additional occupational exposure is likely during the remainder of the
gestation period [10 CFR 835.206(c)], unless she voluntarily revokes her pregnancy declaration.
A uniform exposure rate in rem/week may be calculated by subtracting the equivalent dose
received by the embryo/fetus prior to the declaration of the pregnancy from the 0.5 rem limit
and then dividing this difference by the approximate number of weeks remaining in the
gestation period. For example, for a pregnancy that was declared at 10 weeks into the gestation
period with a calculated equivalent dose of 200 mrem to the embryo/fetus prior to the
declaration of the pregnancy, a uniform exposure rate for the remainder of the pregnancy
would be (500 mrem-200 mrem)/30 week or approximately 10 mrem/week. 10 CFR 835 allows
flexibility for a facility specific determination of what constitutes a “substantial variation.” The
value selected will vary depending onsite-specific factors such as nature of work performed,
radiological conditions in the areas to be entered, and the sensitivity and accuracy of the
individual monitoring methods used. DOE recommends a value equal to the calculated uniform
equivalent dose rate per week +100%. In the example cited above, this would be any dose rate
greater than 20 mrem/week. Each facility should determine and document the methods used to
identify a “substantial variation.”
Additional work or area restrictions for the declared pregnant worker, based on limiting the
total dose (internal and external) may be established as necessary to ensure compliance with
the total equivalent dose and “substantial variation” criteria. Procedures should provide for
coordination between radiation protection and line management, occupational health or
medical services. Examples of typical restrictions include reducing the time allowed in
radiological areas (including prohibiting access to certain areas), restricting the time spent in
certain areas within a radiological area, restricting performance of certain tasks, and requiring
use of supplemental controls, such as shielding, ventilation, and personal protective equipment.
To determine whether restrictions should apply, each facility should evaluate the worker's dose
history and radiological conditions in those areas to which the declared pregnant worker may
have access. Also, employers should provide declared pregnant workers the option of a
Section 85
DOE G 441.1-1C 101
5-19-08
mutually agreeable work assignment that does not involve additional occupational dose. The
training for workers should identify such restrictions and options (see Chapter 14).
Due to difficulties in evaluating fetal dose resulting from radioactive material intakes,
restrictions should be imposed to minimize a declared pregnant worker’s radioactive material
intakes. Consideration should be given to restricting declared pregnant workers from entering
areas where they may receive an intake of radionuclides. ALARA (total dose) aspects should also
be considered in implementing these restrictions. If it is not practical to restrict the declared
pregnant worker from entry into areas where intakes are likely to occur, enhanced use of
engineered controls (primary) and administrative controls (secondary) should be considered.
Any additional workplace restrictions for the declared pregnant worker shall
(10 CFR 835.206) remain in place until the baby is born, the declaration of pregnancy has been
withdrawn (see the sample declaration and withdrawal forms in Appendices 8.A and 8.B), or it is
determined that such restrictions are not required to ensure compliance with 10 CFR 835.206.
Radiological work restrictions apply only to declared pregnant workers. If the worker does
not declare her pregnancy, she cannot be restricted in her work or in the dose that she receives
unless these restrictions apply to all employees of similar position, i.e. general employees or
radiological workers as specified in 10 CFR 835.
8.4 Counseling
An employee with expertise in health physics, laboratory safety, occupational health, or
medical services should be designated as a contact for female workers to obtain counseling or
additional information on the subject of the risks to the embryo/fetus from exposure to ionizing
radiation. Individuals who provide this counseling should receive training in risk communication
and be knowledgeable of the risks of fetal radiation exposure. NRC Regulatory Guide 8.13,
Instruction Concerning Prenatal Radiation Exposure (NRC 1987) and NCRP Report No. 116,
Limitation of Exposure to Ionizing Radiation (NCRP 1993) provides information on the risks of
radiation dose to the embryo/fetus.
Counseling of any worker on the risks of exposure to radiation to the embryo/fetus should
be documented regardless of the worker's decision to declare or not to declare the pregnancy.
8.5 Dose Determination and Monitoring Methods
8.5.0 Dose Determination
The equivalent dose to the embryo/fetus should be determined as soon as practicable after
a worker submits a declaration of pregnancy, at sufficient intervals after declaration to ensure
the limit is not exceeded and that substantial variations do not occur, and at the end of the
gestation period. It may be necessary to include the dose for the entire reporting period during
which conception occurred, unless more detailed records are available to determine the fraction
of the dose received since the time of conception. If enough information is available to assume
DOE G 441.1-1C 102
5-19-08
that the previous dose was received in a linear fashion, the fraction of the dose may be used
that corresponds to the fraction of the reporting period during which the worker was pregnant.
This method is appropriate for the majority of workers who work on a variety of tasks during a
reporting period, none of which results in a significant dose. At the conclusion of a declared
Section 86
pregnancy the dose received by the embryo/fetus prior to the declaration of pregnancy plus the
dose received during the remainder of the pregnancy should be calculated as the sum of:
the equivalent dose to the embryo/fetus from external sources of radiation;
the equivalent dose to the embryo/fetus from intakes of radionuclides in the
embryo/fetus; and
the equivalent dose to the embryo/fetus resulting from intakes of radionuclides in the
declared pregnant worker.
A sample dose record form is provided in Appendix 8.C. Detailed equivalent dose
calculations should be attached to the record form. The dose to the embryo/fetus from
radiation external to the mother should be taken as the equivalent dose to the whole body to
the mother's abdomen or torso. For external dose, the equivalent dose to the whole body is
assessed at a depth of 1 cm in tissue.
If an intake of radioactive material occurs, or occurred between conception and the
declaration of pregnancy, the equivalent dose to the embryo/fetus should be determined as
follows. The equivalent dose to the embryo/fetus from radionuclides in the embryo/fetus and
in the mother that are relatively uniformly distributed, such as Cs-137 and compounds of H-3
and C-14 that are not organically bound, may be considered to be the same as the equivalent
dose to the mother because, under these circumstances, the same energy would be deposited
per gram of tissue in both the mother and the fetus. Refer to ICRP Publication 88, Doses to the
Embryo and Fetus from Intakes of Radionuclides by the Mother, (ICRP 1998) for methodologies
for estimating dose to the embryo/fetus. If other methods are used, the basis for their use in
demonstrating an equivalent or better level of protection should be documented.
DOE G 441.1-1C 103
5-19-08
8.5.1 Monitoring Methods
Guidance on internal and external dose monitoring methods is provided in Chapters 5 and 6
of this Guide.
8.6 Training
It is important that all individuals who enter a controlled area understand the risk to the
embryo/fetus from ionizing radiation received as a result of the mother’s occupational
exposure. It is also important that procedures regarding fetal exposure be well understood by
workers and their supervisors.
Note that the radiation safety training requirements in 10 CFR 835.901(which include the
risk of prenatal exposure to ionizing radiation) pertain to workers who are allowed unescorted
access to, and/or receive occupational radiation dose in, controlled areas. Under certain
conditions, it is possible that a pregnant worker outside of the controlled area could receive a
dose exceeding the 50 millirem (0.5 mSv) monitoring threshold, but not be subject to the
10 CFR 835.901 training requirements. If such conditions exist, measures should be
implemented to ensure that affected workers are aware of the risks of fetal radiation exposure
and their rights to declare their pregnancy. This information should be disseminated through
radiation safety training or equivalent measures.
Additional guidance on radiation safety training programs can be found in Chapter 14 of this
Guide and NRC Regulatory Guide 8.13.
8.7 Record -Keeping and Reporting
Record-keeping and reporting guidance may be found in Chapter 13.
DOE G 441.1-1C 104
5-19-08
Appendix 8.A
Declaration of Pregnancy Form
DECLARATION OF PREGNANCY
Section 87
In accordance with Section 206 of 10 CFR 835, I am voluntarily declaring that I am pregnant, for the
purposes of lowering the dose received by my embryo/fetus. I realize that work restrictions may be
imposed to ensure that the embryo/fetus does not receive a dose in excess of that given in 10 CFR 835
(500 mrem, or 0.005 Sv, during the entire gestation period). I also realize that supplemental dosimetry
may be supplied to me, along with periodic reports of the dose received by my embryo/fetus.
Estimated Date of Conception ____________________________
____________________________________________________
Printed name of worker ID#
____________________________________________________
Signature of worker Date
____________________________________________________
Printed name of supervisor Title
____________________________________________________
Signature of supervisor Date
____________________________________________________
Printed name of Health Physics Title
or Medical Representative
DOE G 441.1-1C 105
5-19-08
Appendix 8.B
Withdrawal of Pregnancy Declaration Form
WITHDRAWAL OF PREGNANCY DECLARATION
I am withdrawing my previous declaration of pregnancy. I understand that, as a result of signing
and submitting this form, any work restrictions that have been imposed as a result of the previously
submitted "Declaration of Pregnancy" will be lifted.
Date of Pregnancy Declaration ___________________________
____________________________________________________
Printed name of worker ID#
____________________________________________________
Signature of worker Date
____________________________________________________
Printed name of supervisor Title
____________________________________________________
Signature of supervisor Date
____________________________________________________
Printed name of Health Physics Title
or Medical Representative
____________________________________________________
Printed name of Health Physics Title
or Medical Representative
____________________________________________________
Signature of Health Physics Date
or Medical Representative
DOE G 441.1-1C 106
5-19-08
Appendix 8.C
Embryo/Fetal Equivalent Dose Record Form
EMBRYO/FETAL EQUIVALENT DOSE RECORD
_______________________________________________________________
Printed name of worker ID#
Date of Declaration of Pregnancy _______________________
Estimated Date of Conception _______________________
Estimated External Dose _______________________
(prior to declaration of pregnancy)
External Dose for remaining _______________________
period of pregnancy
Estimated Internal Dose _______________________
(prior to declaration of pregnancy)
From radionuclides in the _______________________
embryo/fetus
From radionuclides in the mother _______________________
Subtotal _______________________
Internal Dose for remaining _______________________
period of pregnancy
From radionuclides in the _______________________
embryo/fetus
From radionuclides in the mother _______________________
Subtotal _______________________
Total Dose during gestation period _______________________
______________________________________________________________
Printed name of Evaluator Title
______________________________________________________________
Signature of Evaluator Date
DOE G 441.1-1C 107
5-19-08
9.0 PORTABLE MONITORING INSTRUMENT CALIBRATION
A comprehensive radiation protection program (RPP) requires reliable means of monitoring
Section 88
radiological conditions. Such monitoring requires the use of properly functioning radiation
monitoring instruments.
10 CFR 835.401(b) requires that instruments and equipment used for monitoring
radiological conditions shall be appropriate for the radiation(s) encountered and the
environmental conditions and be routinely maintained, calibrated, and tested. American
National Standards Institute (ANSI) Standard N323A, Radiation Protection Instrumentation Test
and Calibration, Portable Survey Instruments (ANSI 1997a) provides comprehensive guidance for
implementing a portable monitoring instrument calibration program.
This Guide provides guidance for a portable monitoring instrument calibration program that
addresses selection (acceptance testing), calibration, tests for operability (functional tests and
performance tests), maintenance, calibration equipment, calibration quality, laboratory
documentation, facilities, and staff. Note that, while 10 CFR 835.401(b) applies to all radiation
monitoring instruments and equipment, the guidance provided in this Guide applies specifically
to portable monitoring instruments only. This Guide does not provide specific guidance for:
installed or stationary monitors such as air monitors, portal monitors, and other
non-portable monitoring instrumentation;
laboratory equipment such as liquid scintillation counters and complex laboratory
multi-channel analyzers;
low exposure rate instruments (even if they are portable) with ranges extending below
0.1mrad/h;
personal monitoring devices, such as thermoluminescent dosimeters and radio-sensitive
film. These devices are addressed by DOE-STD-1111-98, DEPARTMENT OF ENERGY
LABORATORY ACCREDITATION PROGRAM ADMINISTRATION (DOE 1998a);
pocket ionization chambers. These devices are addressed by ANSI N13.5, Performance
Specifications for Direct Reading and Indirect Reading Pocket Dosimeters (ANSI 1989a)
and ANSI N322, American National Standard Inspection, Test, Construction, and
Performance Requirements for Direct Reading Electrostatic/Electroscope Type
Dosimeters (ANSI 1997b); and
electronic dosimeters. Appropriate guidance regarding selection, calibration, testing
and maintenance of electronic dosimeters is provided in ANSI N13.27, Performance
Specifications for Pocket-sized Alarming Dosimeter/Ratemeters (ANSI 1992a).
While this Guide does not apply directly to the above listed devices, many of the concepts
and practices discussed in this Guide, and in the referenced consensus standards, may be
http://webstore.ansi.org/ansidocstore/product.asp?sku=N322%2D1997
http://webstore.ansi.org/ansidocstore/product.asp?sku=N322%2D1997
http://webstore.ansi.org/ansidocstore/product.asp?sku=N322%2D1997
DOE G 441.1-1C 108
5-19-08
applicable to these devices. These concepts and practices should be considered when
establishing calibration and maintenance programs for these devices.
9.1 Implementation Guidance
This chapter provides guidance for selecting, calibrating, testing, and maintaining portable
radiation monitoring instruments and equipment. The portable monitoring instrument
maintenance and calibration program should be developed and conducted consistent with ANSI
N323A.
The essential elements of an acceptable portable instrument calibration program are shown
below with reference to 10 CFR 835, with additional elements provided in ANSI N323A:
a system that ensures calibration shall be performed periodically on each instrument
Section 89
[10 CFR 835.401(b)(1)]. ANSI N323A (4.9) recommends that calibration be performed at
least annually;
an internal audit program shall be conducted no less frequently than every 36 months
(10 CFR 835.102); and
a records program shall be established that documents results of maintenance and
calibration performed on instruments and equipment used for area monitoring and
contamination control [10 CFR 835.703(d)], includes the maintenance of training
records [10 CFR 835.704(a)], documents changes in equipment, techniques, and
procedures used for monitoring, [10 CFR 835.704(e)], and documents the results of
internal audits [10 CFR 835.704(c)].
Further, the following elements should be in place for those activities that perform their
own instrument calibrations:
procedures addressing the calibration of reference sources, support instruments, and
field instruments;
a method to determine when instruments have been returned out-of-calibration and a
method to notify users of out-of-calibration instruments;
adequate technical staff with appropriate training in instrument calibration; and
a dedicated facility that permits calibrations without outside physical interference.
For those activities that rely on contracted organizations to perform calibration services, the
RPP should include or make reference to a Memorandum of Agreement with the calibration
contractor(s) that assures compliance with applicable DOE requirements.
9.2 Instrument Selection
DOE G 441.1-1C 109
5-19-08
Instruments shall be selected that are appropriate to measure the type(s), levels, and
energies of radiation(s) encountered and for the existing environmental conditions
[10 CFR 835.401(b)(2) and (b)(3)]. To ensure these requirements are met, the initial instrument
selection process should include knowledge of facility radiation types, energies, anticipated or
known ranges, and results of available instrument performance and testing data (vendor or
independent). The selection process should include type testing and acceptance testing.
9.2.0 Type Testing
DOE encourages implementation of a formal instrument qualification (type testing) process
in accordance with the relevant portions of ANSI N323A, ANSI N42.17A, Performance
Specifications for Health Physics Instrumentation - Portable Instruments for Use In Normal
Environmental Conditions (ANSI 1989b), and ANSI N42.17C, Performance Specifications for
Health Physics Instrumentation - Portable Instruments for Use In Extreme Environmental
Conditions (ANSI 1989c).
The Department recognizes that hundreds of different types of instruments are used
throughout the complex, including both commercially available and unique instruments. Some
individual sites have well over one hundred different instruments in use. Testing of these
instruments at each DOE site to the standards established in ANSI N42.17A would not be cost
effective. While testing of instrument types in accordance with ANSI N42.17A is encouraged,
such testing is not required.
9.2.1 Acceptance Testing
Prior to use, new instruments should be subjected to acceptance testing as detailed in ANSI
N323A. Instruments that do not meet the selected specifications should not be accepted or
used by the facility. ANSI N320, American National Standard Performance Specifications for
Reactor Emergency Radiological Monitoring Instrumentation, (ANSI 1979) provides performance
parameters for various types of instruments for monitoring releases of radionuclides associated
Section 90
with an accident at a reactor facility.
9.3 Instrument Calibration
ANSI N323A sets forth criteria for proper portable monitoring instrument calibration. An
instrument calibration shall be performed on each instrument periodically at an established
frequency [10 CFR835.401(b)(1)]. ANSI N323A establishes an annual calibration frequency for
portable monitoring instruments. The calibration frequency should be determined and the
calibration should be performed according to the details presented in the above referenced
consensus standards. If routine checks (e.g., routine operability tests and as-found tests)
indicate that the response of an instrument (or type of instrument) remains stable over a long
period of time, then the calibration frequency may be extended. Conversely, if routine checks
indicate that an instrument (or type of instrument) fails to provide a stable response over the
prescribed calibration interval, then the calibration interval should be shortened. The reliability
of an instrument (or type of instrument) and appropriate calibration frequency should be
determined by collecting and analyzing data in accordance with National Conference of
DOE G 441.1-1C 110
5-19-08
Standards Laboratories Recommended Practice RP-1, Establishment and Adjustment of
Calibration Intervals (NCSL 1996).
Sites may find it advantageous for certain applications to continue calibrating portable
neutron survey instruments using the existing neutron quality factors. For example, neutron
calibrations using existing neutron quality factors may correlate better with surveys conducted
to meet Department of Transportation requirements. If this approach is taken, as previously
mentioned, a scaling factor or a comparable approach may be applied to portable neutron
survey instrument results and used for controlling and limiting individual neutron exposures.
9.4 Operability Tests
Functional tests should be performed prior to initial use of an instrument in the field.
Functional tests should be detailed in the instrument-use procedures and should include, as a
minimum: general condition; battery condition; verification of current calibration (i.e., check to
see that the date due for calibration has not passed); background readings; and other tests (high
voltage, zero setting, alarm functions, etc.) as applicable to the instrument. Functional tests
should also include a source response check (i.e., observing the instrument response to a check
source) before initial operation. During use in the field, instruments should be tested with a
check source to ensure that the readings remain within prescribed limits. This should be done
as prescribed in ANSI N323A. The performance of functional tests during use in the field should
be appropriately documented. This may be as simple as a check-list on the survey sheet.
Performance tests should be performed periodically and after maintenance to ensure that
the instruments continue to meet performance requirements for field measurements.
Examples of performance tests are tests for geotropism and response time. Performance
requirements should be met as specified in the applicable sections of ANSI N323A, ANSI
N42.17A, and ANSI N42.17 C. These tests may be conducted as part of the calibration
procedure.
9.5 Maintenance
Maintenance shall be performed periodically on an established frequency
[10 CFR 835.401(b)(1)]. Maintenance activities should be directed toward ensuring that the
Section 91
instruments continue to meet the required accuracy for field measurements.
All preventive and corrective maintenance should be performed using components and
procedural recommendations at least as stringent as those specified by the instrument
manufacturer. If the manufacturer does not provide routine maintenance procedures, a
procedure should be written and approved by staff and management in the organization
performing the maintenance.
9.6 Calibration Equipment/Calibration Quality
The calibration laboratory should possess and maintain appropriate radiation and
non-radiation standards to achieve reliable operation.
DOE G 441.1-1C 111
5-19-08
Instruments should be calibrated with appropriate standards that are traceable to the
National Institute of Standards and Technology (NIST) or its international equivalents.
Calibrations of reference radiation fields or sources, calibration assemblies, maintenance of
standards, and check sources should be in accordance with ANSI N323A. For information on
acceptable reference sources for calibration for various radiation types, refer to Table 2 of ANSI
N323A. Instruments should be calibrated using a source of appropriate energy for the
radionuclides anticipated to be encountered. Calibration quality including calibration field
accuracies and quantities should be in accordance with ANSI N323A.
For non-radiation quantities (e.g., temperature, humidity, pressure, voltage, current, etc.),
the facility may use standards based on traceability to NIST.
9.7 Laboratory Documentation
The calibration laboratory should maintain the following sets of documentation: (1) the
laboratory protocol; (2) the laboratory records; and (3) the calibration records. Historical
records should be maintained to detail any changes or revisions in procedures or protocols. The
laboratory protocol describes the laboratory operations, i.e., what the laboratory is expected to
do and how it is expected to do it. This documentation should also include the detailed
calibration procedures for each instrument routinely calibrated. The laboratory records, on the
other hand, are those records that document the activities of the laboratory. Finally, the
calibration records are those records that document the maintenance, calibration, and testing of
each instrument and source used.
9.7.0 Laboratory Protocol
Each DOE laboratory should have a written protocol for operations. Components that
should be included in the protocol are listed in ANSI/NCSL Z540-1-1994, American National
Standard for Calibration - Calibration Laboratories and Measuring and Test Equipment - General
Requirements (ANSI/NCSL 1994). Radiation detection instruments that are commonly used to
perform area and individual monitoring required by 10 CFR 835 need not be considered to be
measuring and test equipment (M&TE) as discussed in ANSI/NCSL Z540-1-1994. ANSI N323
provides appropriate guidance for establishing and operating a calibration program for portable
radiation monitoring instruments. While ANSI/NCSL Z540-1 provides guidance that may be
useful in such programs, this guidance need not be applied to calibration of radiation detection
instruments used in operational settings. Radiation detection instruments that are used as
calibration standards should be considered M&TE and used, handled, stored, and calibrated in
accordance with the applicable standards.
9.7.1 Laboratory Records
Section 92
Guidance for record-keeping can be found in ANSI N323A and ANSI/HPS N13.6, Practice for
Occupational Radiation Exposure Records Systems (ANSI/HPS 1999). Chapter 13 provides
additional guidance for maintaining records consistent with the requirements of 10 CFR 835.
9.7.2 Instrument Calibration Records
DOE G 441.1-1C 112
5-19-08
A record shall be maintained for results of calibration and maintenance performed for each
instrument [10 CFR 835.703(d)]. Refer to Chapter 9 and ANSI N323A for specific items that
should be included.
9.7.3 Instrument Location
A system for tracking the location of portable survey instruments and for recalling those
instruments for recalibration should be established. The location of portable survey instruments
should be known by the calibration staff or by some identifiable group assigned with that
responsibility. Because instruments may incorporate or be accompanied by an accountable
sealed radioactive source, instrument tracking may be required as part of the sealed radioactive
source control program. See Chapter 15 to determine if this is the case.
9.8 Laboratory and Staff
The location, design, and use of the calibration laboratory should ensure that conditions
within the laboratory will not affect calibration quality. In addition, the laboratory shall be
designed to keep worker exposures ALARA in compliance with 10 CFR 835.1001 - 1003. The
laboratory should also have an appropriate selection of calibration equipment and should be
operated with a properly organized and trained staff. Additional guidance may be found in
Chapter 4 of this Guide and Chapter 3 of the RCS.
9.8.0 Laboratory
The effect of external conditions on the internal environment of the calibration laboratory
should be considered in selecting the facility site. The laboratory should be sited away from, or
otherwise isolated from, sources of mechanical vibration and shock, sources of electrical and
electromagnetic interference, and other potential sources of interference with the proper
calibration of instrumentation. If such potential sources exist, the laboratory should have
documentation that demonstrates an absence of adverse effects on calibration accuracy.
The electrical power should be appropriate for the equipment used, suitably stable, and free
of switching surges and significant line noise. When necessary, local auxiliary voltage stabilizers,
filters, and uninterruptible power supplies should be provided.
The laboratory environment should be controlled to ensure that environmental conditions
do not affect the calibration quality. The conditions described in ANSI N323A, Table 1, should be
considered and implemented, to the extent practicable and appropriate.
Calibration areas should not be used for storage of instruments, equipment, or sources.
Such storage may lead to variable scatter or abnormal ambient radiation conditions.
98.1 Calibration Staff Qualifications
The calibration laboratory manager and the individual in charge of the day-to-day operation
of the calibration laboratory should have the authority to conduct operations free from any
DOE G 441.1-1C 113
5-19-08
influence that could adversely affect the quality or impartiality of the services offered. Refer to
DOE STD-1107-2007, Chg1, KNOWLEDGE, SKILLS, AND ABILITIES FOR KEY RADIATION
PROTECTION POSITIONS AT DOE FACILITIES (DOE 2007g) and Chapter 14 for guidance on the
Section 93
recommended education, training, and skills for these two positions. The laboratory manager
should understand the laboratory protocol, ensure it is followed, and should, at least annually,
evaluate staff competence and the need for training. In smaller operations, the manager may
also be in charge of day-to-day operations.
9.8.2 Calibration Staff Training
All staff employed in calibration work shall be trained in radiation safety prior to receiving
occupational exposure [10 CFR 835.901(a)]. Chapter 14 provides additional guidance.
Apart from radiation safety training, the staff should receive training on the theory of
radiation detectors, interaction of radiation with matter, basic statistics, maintenance of
records, quality assurance, and other topics related to the safe and efficient operation of
calibration equipment.
9.9 Assessments
Internal audits of the radiation protection program shall be conducted such that, over a
three year period, all functional elements are assessed, including program content and
implementation (10 CFR 835.102). Chapter 3 provides guidance on the required internal audits.
DOE G 441.1-1C 114
5-19-08
10.0 AIR MONITORING
The purposes for conducting an air monitoring program can be characterized as the need to
assess individual exposures to airborne radioactive material, determine the need for and
prescribe appropriate personnel protection from airborne radioactive material, and provide
early warning of unexpected increases in airborne radioactivity levels. The type of air
monitoring to be performed will depend on the purpose of the monitoring and how the
monitoring results will be used. Under 10 CFR 835, air monitoring results are required to
measure the concentrations of airborne radioactive material, determine posting requirements,
determine the effectiveness of the engineered controls and barriers used to contain and confine
radioactive material, determine appropriate protective equipment and measures, and provide
warnings of significantly elevated levels of airborne radioactive materials. In addition, air
monitoring results may be used to estimate individual intake. 10 CFR 835 establishes the basic
elements of an air monitoring program: periodic air samples to assess actual and potential
individual exposures and real-time air monitoring to provide immediate warning of increases in
airborne radioactive material concentrations.
When implementing an air monitoring program, it is important to achieve a proper balance
between the basic elements of the program -- air sampling and real-time air monitoring. The
balance will depend on the characteristics of each facility and the justification for the approach
taken should be included in program documentation.
The primary difficulty in meeting the air monitoring requirements in 10 CFR 835 is in
collecting samples that can reliably reveal and estimate the magnitude of individual exposures.
However, it should be possible to reliably detect increases in airborne radioactive material
concentrations above baseline levels. This information can be used to initiate bioassay
evaluations to verify whether an exposure has occurred and, if so, to estimate the magnitude of
the exposure.
Real-time air monitoring is performed to provide warning of significantly elevated levels of
airborne radioactive materials. The primary challenge in performing effective real-time air
monitoring is placing the monitors where they will provide a rapid and reliable warning that an
unexpected release has occurred. The number and placement of real-time air monitors should
be optimized. Proper strategy for the placement of real-time air monitors is critical to the
effectiveness of the air monitoring program.
Section 94
The air monitoring program is only one element of a comprehensive radiation protection
program. Therefore, individuals involved with the air monitoring program should coordinate
their efforts with other radiation protection program personnel, particularly with those involved
in contamination control and internal dosimetry.
10.1 Implementation Guidance
Monitoring of airborne radioactivity is required where an individual is likely to receive an
exposure of 40 or more derived air concentration (DAC)-hours in a year or as necessary to
characterize the airborne radioactivity hazard where respiratory protective devices for
protection against airborne radionuclides have been prescribed [10 CFR 835.403(a)]. )]. See
Appendix A of Chapter 16 of the Guide for a listing of values. Real-time air monitoring is
DOE G 441.1-1C 115
5-19-08
required to be performed, as necessary, to detect and provide warning of airborne radioactivity
concentrations that warrant immediate action to terminate inhalation of airborne radioactive
material [10 CFR 835.403(b)].
This chapter describes acceptable methods for establishing and operating an air monitoring
program adequate to demonstrate compliance with 10 CFR 835. The discussion is divided into
the following topics:
determining the need for air monitoring;
placement of air sampling and real-time air monitoring equipment;
selection and operation of air sampling equipment;
selection and operation of real-time air monitoring equipment;
sample analysis and data review;
quality control and quality assurance; and
administrative controls.
NUREG-1400, AIR SAMPLING IN THE WORKPLACE (NRC 1993), was developed by the U.S.
Nuclear Regulatory Commission to provide technical information on air sampling for facilities
following NRC’s related regulatory guidance. The technical information provided in this
document is useful for DOE facilities using this Guide. NUREG-1400 contains the following
technical information:
evaluation of the need for air sampling, including air sampling based on potential
intakes and concentrations, and air sampling systems;
location of air samplers, including purpose of airflow studies, determination of airflow
patterns, and selecting sample location;
demonstration that air sampling is representative of inhaled air;
adjustments to derived air concentrations;
measurement of the volume of air sampled; and
evaluation of sampling results, including detecting changes in air concentrations over
time, efficiency of collection media, and detection sensitivity.
NUREG-1400 should be consulted to obtain pertinent technical information concerning
regulatory guidance provided in this Guide.
10.2 Determining the Needs for Air Monitoring
DOE G 441.1-1C 116
5-19-08
The decision to perform air monitoring should be based on consideration of both actual and
potential radiological conditions. Actual conditions are typically confirmed by air sampling
results with detectable levels of activity. Potential conditions are identified through the use of
professional judgment and experience regarding the likelihood that a radiological condition will
exist. When evaluating potential conditions, both normal situations and unusual situations
which can reasonably be expected to occur should be considered. NUREG-1400, (Section 1)
provides an acceptable methodology for evaluating the need for air sampling by predicting likely
intakes for some individuals who might receive a significant intake. This methodology provides
an acceptable approach to justify and document decisions based on professional judgment and
experience.
Section 95
When performing air monitoring to demonstrate compliance with either 10 CFR 835.403(a)(1) or
(2), the method used must be appropriate for the existing environmental conditions, consistent
with 10 CFR 835.401(c)(3). Any conflicts between this requirement and the specific monitoring
requirements of 10 CFR 835.403(a) should be considered in development of the RPP.
10.2.0 Exposure Assessment
Air monitoring through the use of representative sampling is used for the assessment of an
individual's exposure to airborne radioactivity. Air monitoring results may be used to determine
an individual's type and frequency of bioassay measurements and to estimate an individual's
dose from exposure to airborne radioactive material.
Determinations of the need for air sampling should include consideration of occupancy factors
to determine if an individual is likely to receive a 40 DAC-hour exposure in a year. For example,
if a worker is present in a work area only 200 hours per year and enters no other areas of
significant airborne radioactivity, the individual could be exposed to an air concentration just
less than 20% of a DAC without receiving an exposure equal to or exceeding 40 DAC-hours in a
year.
10.2.0.0 Type and Frequency of Bioassay
10 CFR 835 requires that internal dose monitoring programs be conducted for individuals likely
to exceed certain internal dose thresholds [10 CFR 835.402(c)]. The air monitoring program can
provide significant information for determining the type and frequency of bioassay
measurements.
An effective air monitoring program, in combination with an effective and reliable access
control program, can facilitate tracking of an individual's exposure to airborne radioactive
materials measured in DAC-hours. A DAC-hours tracking program should be considered for
DOE activities where individuals could routinely be expected to be exposed to greater than 40
DAC-hours in a year. Internal dose monitoring programs typically assign bioassay frequency
and methods based on actual or anticipated individual exposures. Therefore, tracking of
individual exposures in DAC-hours can facilitate determination of the type and frequency of
required bioassay measurements. For example, if a radiological worker receives greater than
40 DAC-hours in a year, the individual would be required to participate in the bioassay
monitoring program. The bioassay frequency and methodology may be determined based on
DOE G 441.1-1C 117
5-19-08
the radionuclides inhaled and the frequency of intakes or exposure to airborne radioactive
material.
10.2.0.1 Estimation of Dose
The estimation of internal dose shall be based on bioassay data rather than air concentration
values unless bioassay data are:
unavailable;
inadequate; or
internal dose estimates based on air concentration values are demonstrated to be as or
more accurate [10 CFR 835.209(b)].
Bioassay data may meet these conditions as a result of instrumentation limitations, sampling
discrepancies, or other conditions. Chapter 5 provides guidance on evaluation of internal dose
from air monitoring data.
If bioassay measurements are not available or their validity is questionable, internal dose
estimates may be determined from the number of DAC-hours tracked for that individual. When
DAC-hours are used for this purpose, any adjustments, such as protection factors for respiratory
protection, shall be documented [10 CFR 835.702(g)]. Additional guidance is provided in
Chapter 5.
Section 96
When using respiratory protection devices for radiological protection, as an initial approach one
should consider selecting a respiratory protection device which has an assigned protection
factor greater than the peak concentration value, in multiples of DAC, expected. As an alternate
approach, to ensure the radiological protection occupational exposure limit of 5 rem TED is not
exceeded, one may establish an administrative control level for that activity that is much lower
than the 5 rem TED limit and use the conversion of 2.5 millirem per DAC hour and account for
the protection factor of the respiratory protection device and the time in the area. However,
there are some considerations before using this approach. Regardless of the approach taken,
the ALARA provisions of 10 CFR 835 would need to be appropriately considered.
DOE has addressed the special case where the sensitivity of the bioassay analysis is
technologically limited (such as with certain plutonium isotopes). Acceptable methods of
dealing with technology shortfalls have been addressed in Chapter 5 and DOE-STD-1121-2008
(DOE 2008j).
As required by 10 CFR 835.209(b)(3), when used for determinations of individual dose
equivalents, air sampling results must provide dose determinations that are as or more accurate
than those provided by bioassay. The air sample should closely approximate both the airborne
radioactivity concentration and the physical and chemical properties of the airborne radioactive
material. Personal air monitoring is typically used for obtaining air samples that are used for
dose determination. Chapter 10 provides additional guidance for situations where air
monitoring is used when there is no practical bioassay method.
DOE G 441.1-1C 118
5-19-08
Normally, real-time air monitoring should not be used in lieu of air sampling when the results
may be used to estimate an individual's dose and intake. The results from real-time air
monitoring may not be representative of the air actually breathed by individuals, linked to the
individual in that area, or sufficient to use in the estimation of internal dose.
10.2.1 Personnel Protection
Air monitoring is performed to determine the need for “Airborne Radioactivity Area” posting
and access controls, evaluate the effectiveness of engineered controls, and determine the
proper respiratory protective device.
10.2.1.0 Need for Posting
10 CFR 835.603(d) requires posting of airborne radioactivity areas. Air sampling may be used to
determine whether an area should be posted as an airborne radioactivity area. Grab sampling is
typically used to determine whether the criteria for posting airborne radioactivity areas have
been exceeded. The sample volume should be sufficient to ensure the achievement of
adequate counting system detection capabilities.
Chapter 12 of this Guide and Chapter 2 of the RCS provide detailed guidance on posting airborne
radioactivity areas.
10.2.1.1 Effectiveness of Engineered Controls
Engineered controls for facilities and systems include measures to preclude and control releases
of airborne radioactive material. Air monitoring should be performed in facilities and around
systems with engineered controls designed to prevent the release of airborne radioactivity and
also following modifications which could affect air flow and ventilation balance. Fixed-location
air sampling should be considered in the design and modification of facilities where uncontained
radioactive material would be used or releases of airborne radioactive material would be
anticipated. Results from fixed-location air sampling are particularly useful during the startup of
a new facility or new operation within an existing facility to establish baseline airborne
radioactive material concentrations and verify containment integrity.
Section 97
Temporary engineered controls are used to protect individuals when permanent
controls cannot adequately contain radioactive material. When engineered controls, such
as ventilation, vacuum cleaners, or containment devices, are used to reduce or maintain
airborne radioactivity concentrations, air monitoring should be performed to determine the
adequacy and effectiveness of the engineered controls. Generally, for installed controls,
such as fume hoods, fixed-location air sampling is preferred, whereas for temporary
controls, such as portable ventilation or use of vacuum cleaners, grab sampling is preferred.
Real-time air monitoring for determining the adequacy of installed controls may also be
appropriate or required. Chapters 4 and 11 of this Guide and the RCS provide guidance on
the use of engineered controls.
10.2.1.2 Proper Respiratory Protective Equipment
DOE G 441.1-1C 119
5-19-08
Respiratory protective equipment is used to reduce an individual's intake of airborne radioactive
materials. Each respiratory protective device is assigned a protection factor that indicates the
degree of protection afforded by the respirator. Respiratory protective devices should be
chosen based on the protection factor and actual or potential airborne radioactivity levels,
taking into account ALARA considerations, other industrial hazards, and worker safety. DOE
requires its respiratory protection programs to be conducted, for DOE contractors in accordance
with 10 CFR 851, and for DOE Federal employees in accordance with DOE O 440.1B, Worker
Protection Program for DOE (Including the National Nuclear Security Administration) Federal
Employees (DOE 2007c). 10 CFR 851 and DOE O 440.1B require adherence to ANSI Z88.2,
Practices for Respiratory Protection (ANSI 1992b) and 29 CFR 1910.134.
An important step in selecting the proper respiratory protective equipment is determining the
actual or potential concentration of airborne radioactivity in the area the individual is to enter.
Air sampling shall be performed as necessary to characterize the airborne radioactivity hazard
where respiratory protection against airborne radionuclides has been prescribed
[10 CFR 835.403(a)(2)]. Typically, grab sampling is used to determine the airborne radioactivity
concentration. Real-time air monitoring may be useful in areas where substantial work is being
performed and airborne radioactivity concentrations fluctuate,. If the individual is entering an
area where the airborne radioactivity concentration is routinely sampled and is not likely to
have changed since air monitoring was last performed, previously obtained samples may be
used to characterize the airborne radioactivity hazard. When the need for air monitoring is not
clear, historical data from fixed-location air sampling and real-time air monitoring should be
analyzed to determine whether respiratory protection is appropriate. NUREG-1400 provides a
methodology for predicting the potential intakes which can be useful in determining the need
for respiratory protection (Section 1.2).
10.2.2 Early Warning
Real-time air monitoring shall be performed as necessary to detect and provide warning of
airborne radioactivity concentrations that warrant immediate action to terminate exposure to
airborne radioactive material [10 CFR 835.403(b)]. Typically, real-time air monitoring should be
used in areas where unexpected increases in airborne radioactivity levels could result in an
Section 98
exposure to an individual exceeding 40 DAC-hours in one week. This exposure is typically
representative of a committed effective dose of approximately 100 millirem (1 mSv). To provide
the necessary warning, real-time air monitors should have alarm capability and sufficient
sensitivity to detect airborne radioactivity at these levels.
Unlike air sampling, the need for real-time air monitoring is based on the likelihood that an
individual will be exposed to an unexpected increase of airborne radioactivity greater than a given
level. The use of real-time air monitors is based upon the expectations of discrete events, rather
than determination of ambient airborne radioactivity concentrations.
Examples of situations for which real-time air monitoring may be appropriate include the
following:
within or at the boundaries of areas where work is performed that creates or has the
potential to create airborne radioactivity;
DOE G 441.1-1C 120
5-19-08
within or at the boundaries of areas where a power failure or other disruption of
engineered controls could result in the release of airborne radioactivity; and
within or at the boundaries of established airborne radioactivity areas when work is
being performed that has the potential to significantly increase the ambient airborne
radioactivity levels.
These examples serve to emphasize that real-time air monitoring is intended to protect
individuals both inside and outside of work areas.
Real-time air monitors may not be appropriate or necessary in established airborne radioactivity
areas where ambient airborne radioactivity levels are not expected to increase (i.e., unexpected
releases are not likely). Grab samples are typically used to monitor airborne radioactivity levels
and to detect trends. Historical workplace air monitoring records and knowledge of the type of
work to be performed in the area can be used to justify the decision not to use a real-time air
monitor.
10.3 Placement of Air Sampling and Real-Time Air Monitoring Equipment
Once the need for air monitoring has been established, the monitor/sampler location(s) can be
determined. Location is important because inappropriately placed equipment may not provide
representative results. Concentrations of airborne radioactivity in an area can vary greatly from
one location to another.
In general, air sampling equipment is most effective when located close to individuals to
provide an indication of airborne radioactivity levels to which they are exposed. Real-time air
monitoring equipment should be located to provide an early warning to individuals of a
significant increase in levels of airborne radioactive material.
When selecting locations for air sampling and real-time air monitoring equipment,
consideration should be given to the locations of possible release points and workers, the
purpose of the sample, and room air flow patterns. The cost of real-time monitors and the
time required to collect and analyze sample media limit the number used in a facility. This
consideration, together with the need for a rapid response to an unplanned release, means
that optimal placement is critical. The technical basis for air sampling and real-time air
monitoring equipment placement should be documented. The following considerations
should be included in technical basis documentation:
10.3.0 Locations of Release Points and Individuals
Actual and potential release points in an area should be identified. Actual release points can be
Section 99
determined from past operating experience. Potential release points can be determined from a
review of safety analysis documentation for the facility. The location of individuals in relation to
these release points should also be identified. Finally, occupancy times for individuals near the
release locations should be estimated.
DOE G 441.1-1C 121
5-19-08
10.3.1 Purpose of Sample
The purpose of air monitoring is to measure the concentrations of airborne radioactive material
to:
estimate individual intakes;
determine posting requirements;
determine the effectiveness of the confinement of radioactive material;
determine appropriate protective equipment and measures; and
provide warnings of significantly elevated levels of airborne radioactive materials.
To estimate exposures and intakes, a sample representative of the air breathed by the individual
should be taken. The air sampling equipment should be positioned in the vicinity of the
individual, taking into consideration the air flow path from likely release points to the individual.
Alternatively, if the purpose is to indicate containment or confinement control, then air
sampling equipment should be positioned near the release point, or likely release point, in a
downstream direction. The downstream direction can be determined by performing air flow
studies.
Real-time air monitoring equipment, such as continuous air monitors (CAMs), should be
positioned strategically in the affected area or at the affected area boundaries. If there is only
one potential release point in an area, then placement of the real-time air monitor as close to
the release point as possible in a downwind direction may be adequate. If there are multiple
release points and a limited number of real-time air monitors, such that one cannot be placed
near each release point, then the real-time air monitors should be placed at locations expected
to provide the most reliable indication of a release with the least delay from the onset of the
release, should one occur. The general objective is to provide a rapid and reliable warning to
the greatest number of individuals that a release has occurred.
10.3.2 Room Air Flow Patterns
Air flow studies should be used to determine the placement of air monitors and facilitate the
interpretation of the results of air monitoring. The extent of air flow testing will depend on the
type of air monitoring being performed. More extensive air flow testing should be performed
when locating fixed-location air samplers and real-time air monitors than when locating air
samplers being used as grab samplers for short duration jobs. Air flow studies may be useful in
placement of grab samplers to ensure that samples are indeed representative. Air flow testing
is not needed for personal air monitoring since proper placement of personal air samplers on
the worker ensures collection of representative samples. Acceptable methods for determining
air flow patterns are discussed, in detail, in NUREG-1400 (Section 2.3).
DOE G 441.1-1C 122
5-19-08
The radiation protection organization should be aware of facility characteristics, operations, and
changes that may affect airflow patterns. The radiation protection organization should perform
and document a review of the adequacy of sampling and monitoring systems periodically and as
part of any facility or operational change affecting radiological control. The periodicity of the
review should be documented as part of the technical basis for the placement of the air
sampling and real-time monitoring equipment.
Section 100
Placement of fixed-location air sampling and real-time air monitoring equipment should be
reevaluated after changes to the ventilation system have been made or after equipment or
structures have been added that may influence air flow. Air flow patterns in a given area should
be reevaluated at a minimum every 36 months or when major room or building renovation has
occurred.
10.4 Air Sampling Equipment
Types of air sampling equipment include fixed-location air samplers, portable air samplers
(high-volume and low- volume), and personal (lapel) air samplers. Selection of air sampling
equipment should be based on the type of sample being collected (e.g., breathing zone air
sample, source-specific air sample, or grab air sample). Detailed technical information regarding
air sampling systems is provided in NUREG-1400 (Section 1.3).
10.4.0 Breathing Zone Air Monitoring
Breathing zone air monitoring should be used when air monitoring results are used to assign
internal doses and when determining the effectiveness of respiratory protection equipment.
Breathing zone air monitoring involves collecting an air sample from the individual's breathing
environment, making allowances to eliminate interferences the samplers themselves may have
on the individual's activities. Such air samples provide the most reliable indicator of the
potential for inhalation of airborne radioactivity and can provide an estimate of the magnitude
of possible exposures. Breathing zone air samples can be collected using fixed-location air
samplers, portable air samplers, or personal air samplers. When fixed-location air sampling
equipment will not provide a representative indication of the individual's breathing zone, then
personal air sampling equipment should be used. When using personal air samplers, the
radiation protection staff should ensure that the low flow rate will allow collection of enough
radioactive material to meet the minimum sensitivity requirement for air monitoring.
Breathing zone air monitoring should also be used in areas where workers are likely to exceed
an exposure of 40 DAC-hours in a year, and to identify possible worker internal exposures and
the need for follow-up bioassay measurements. Breathing zone air monitoring data may be
used to estimate intakes of radioactive material and subsequent internal dose in accordance
with the requirements of 10 CFR 835.209(b).
10.4.1 Source-Specific Air Sampling
Source-specific air sampling is the collection of an air sample near an actual, or likely, release
point in a work area. Fixed-location and portable air samplers can be used for source-specific air
sampling to verify containment or confinement integrity, document airborne radioactive
DOE G 441.1-1C 123
5-19-08
material levels (can be used for determining the need for posting), and provide information
relevant to determining when the use of respiratory protective devices is necessary.
10.4.2 Grab Sampling
Grab sampling should be used for temporary or non-routine situations and as a backup for other
types of air sampling in the event of equipment failure. Grab sampling can be used to
determine whether areas should be posted as airborne radioactivity areas and respiratory
protective devices should be used for protection against airborne radioactive material. Portable
air sampling equipment should be used for operations requiring grab sampling. Sample flow
rates may vary depending upon the specific application, but should allow collection of a sample
Section 101
volume adequate to ensure that the minimum detectable activity of the sampling and counting
system corresponds to an intake of no greater than 2% of an ALI.
10.4.3 Operability Checks
Operability checks of air monitoring equipment are used to ensure that the equipment is
functioning properly prior to and during use. Operability checks shall be performed routinely on
flow rate meters [10 CFR 835.401(b)(4)]. In addition, because excessive dust loading interferes
with alpha particle detection and reductions in flow rate result in uncertainties in the total air
volume sampled, periodic verification of flow rates should be performed. At a minimum, the
flow rates should be verified when sample media are exchanged. Rapid or significant changes in
flow rate should be investigated immediately. These instances may indicate the need for more
frequent changes of sample media or loss of integrity of filter or sampling equipment. The
sample flow rate used for estimating air concentration should be the average of the flow rate
when the sample was started and the flow rate when the sample medium was removed.
10.5 Real-Time Air Monitoring Equipment
10.5.0 Instrument Selection
Instruments used for real-time air monitoring shall be appropriate for the type(s), levels, and
energies of radiation(s) encountered in the workplace [10 CFR 835.401(b)(2)] and for existing
environmental conditions [10 CFR 835.401(b)(3)]. The selection of real-time air monitors should
be based on the characteristics of the airborne radioactive material, the anticipated range of
airborne radioactive material concentrations and the possible variations of the concentrations
over time. The type of real-time air monitor used depends on the type of facility in which it is
used, the radioisotopes being monitored, and the physical and chemical forms of the radioactive
material. Commonly used monitors at DOE facilities are: particulate-radioactive material
continuous air monitors (e.g., alpha CAMs and beta CAMs); impactor air monitors; and gaseous
radioactive material monitors. Monitors that use background-reduction methods (e.g.,
activity-fractioning monitors and pseudo-coincidence monitors) may also be used. CAMs should
not be used when high levels of contamination or other factors would prevent them from
providing reliable results. Use of CAMs for particulates and noble gases is acceptable; however,
detection of radon requires a different monitoring methodology that provides real-time
information and alarm capabilities. In these cases, the use of working level monitors may be
DOE G 441.1-1C 124
5-19-08
acceptable. If such monitoring instruments are taken credit for in the documented safety
analysis, their initial quality and maintenance level should also be appropriate, including any
that of any associated safety system hardware and software.
If a real-time air monitor is likely to become highly contaminated or if unreasonably high flow
rates are needed, then one of the following techniques can be used: (1) periodic direct reading
of fixed air sample media by using portable survey instruments; or (2) periodic grab samples
with rapid analysis.
10.5.1 Alarm Set Points
Section 102
Real-time air monitors should be capable of measuring 1 DAC when averaged over 8 hours (8
DAC-hours) under laboratory conditions. Alarm set points for real-time air monitors used for
routine monitoring should be set at the lowest practical level so as to accurately indicate loss of
containment or the need for corrective action without causing a significant number of false
alarms. When monitoring for alpha emitters shows high radon and thoron concentrations, an
alarm set point of up to 24 DAC-hours may be acceptable. In all cases, the actual alarm set point
established for each unit and the technical basis for the alarm set points should be documented.
If real-time monitors are used during work requiring the use of respiratory protective devices,
the alarm set point can be adjusted to provide an early warning that the applicable respiratory
protection factor may be exceeded.
10.5.2 Alarm Capabilities
Real-time air monitors shall have alarm capability and sufficient sensitivity to alert potentially
exposed individuals that immediate action is necessary to minimize or terminate inhalation
exposure [10 CFR 835.403(b)]. The alarm should be audible and have a distinctive tone or sound
so that it is not confused with other work area alarms, such as those for criticality. The audible
alarm intensity should be a minimum sound level of 75 dB at 15 cm. In areas that have a high
ambient noise level (>95 dB), a visual alarm should activate with the audible alarm. The visual
alarm should be distinctive so that it cannot be mistaken for other types of alarms. If the
monitor is installed outside the work area, there should be additional audible and visible alarm
indicators inside the area to ensure that individuals are promptly notified. ANSI N42.17B,
Performance Specifications for Health Physics Instrumentation - Occupational Airborne
Radioactivity Monitoring Instrumentation (ANSI 1989d), provides additional guidance regarding
alarm capabilities.
10.5.3 Operability Checks
Operability checks shall be routinely performed on real-time air monitoring equipment
[10 CFR 835.401(b)(4)]. The following periodic operability checks should be performed at the
frequency indicated:
Daily operability checks should include positive airflow indication, presence of a typical
non-zero response to background activity, and internal check sources or 60 Hz electronic
checks when available. In addition, daily checks should verify the control settings and
the operability of strip chart recorders, if used.
DOE G 441.1-1C 125
5-19-08
Weekly operability checks should verify instrument response with a check source or
with ambient levels of radon or thoron daughters. If an instrument response falls
outside established response limits, it should be taken out of service.
Once each month, every real-time air monitor in active service should be tested to
ensure proper operation of the alarm. Alarm testing should also verify alarm response
when the detector fails.
The adequacy of battery power should be tested monthly for real-time air monitors that rely on
battery backup power in an emergency. Similarly, for those monitors using emergency power
supplies, the adequacy of the emergency power for monitor operation should be verified as a
part of the emergency power checks.
10.6 Sample Analysis and Data Review
Provisions for detecting changes in radiological conditions, detecting the gradual buildup of
Section 103
radioactive material, verifying the effectiveness of engineered and process controls in
containing radioactive material, and identifying and controlling potential sources of individual
exposure to radioactive material require that certain evaluations of air monitoring results be
performed [10 CFR 835.401(a)(3-6)]. Additional technical information regarding evaluation of
sampling results is provided in NUREG-1400 (Section 6).
Air sample results should be evaluated as quickly as practical for special situations, such as the
evaluation of the need for respiratory protection, area evacuation (if necessary), individual
intake, and relief from use of respiratory protective devices. Preliminary assessments of air
samples using field survey techniques should be performed promptly upon removing the sample
from its holder. When background levels of radon and thoron daughters interfere with
evaluation of alpha air samples, prompt field assessments may not be possible. Procedures
should define the methods for counting samples in the field (i.e., detection equipment to use,
configuration of the detector and the sample, and conversion factors). Prompt field
assessments are not required for fixed-location, portable, or personal air samplers used to
routinely sample the individual’s breathing environment unless upset conditions have been
identified.
Appendix A of 10 CFR 835 has a provision that allows the adjustment of DACs to reflect the
actual physical characteristics (e.g., particle size) and chemical characteristics (e.g., solubility in
lung fluid) of the airborne radioactive material. Guidance on making adjustments to DACs can
be found in DOE STD-1121-2008.
10.7 Quality Control and Quality Assurance
Records of the results of air monitoring shall be documented and maintained
[10 CFR 835.703(a)]. To meet this requirement, quality control should be applied to all phases
of the air monitoring program to include sample identification, handling, and storage, air
DOE G 441.1-1C 126
5-19-08
sampling and real-time air monitoring equipment, counting room equipment, and
record-keeping.
10.7.0 Sample Identification, Handling, and Storage
All samples collected should be assigned an identification number that cannot be confused with
samples taken at another location. Sample designators should be placed on all collection
envelopes or containers to reduce the possibility of mislabeling a sample. Other information on
the envelope should include the date and time of sample collection and the sample flow rates.
Samples should be handled carefully to prevent cross-contamination between samples and
should be placed in appropriately labeled containers to reduce the potential for loss.
Arrangements should be made for sample storage prior to counting and between counts if
multiple counts are required.
Each organization should develop a tracking system for its air samples that permits positive
identification of any individual sample, while indicating the results of the sample analysis,
the flow rate, the dates and times of sample collection, the individual performing the
collection, and pertinent information about the sample collection system. A sample log
book or a computerized database should be maintained. This should contain the necessary
entries to provide a complete history of the sample and its analysis.
10.7.1 Air Sampling and Real-Time Air Monitoring Equipment
Section 104
Components of air sampling and real-time air monitoring systems (i.e., air mover, CAM detector,
portable air sampler, fixed sampling head, and sampling line) should be uniquely identified.
Labeling of equipment and maintaining a log of equipment locations will allow the radiation
protection staff to locate a sampling or monitoring unit should there be a questionable sample
result.
Equipment used for air monitoring shall be periodically maintained and calibrated on an
established frequency [10 CFR 835.401(b)(1)]. ANSI N42.17B indicates that air flow meters,
differential pressure indicators, and other devices used to determine volumetric flow rates of air
samplers and monitors should be calibrated to within +_15% of the true reading. Calibrations
should be performed annually at the atmospheric pressure and temperature conditions that are
expected during sampling conditions, or the appropriate correction factor should be applied
during the calculation of the flow rate.
Detectors in real-time air monitors should be calibrated with a calibration source(s) typical of
the radionuclide(s) present in the work environment. The calibration should also be performed
after failure of an operability test. Calibration sources should be traceable to the National
Institute of Standards and Technology (NIST).
At a minimum, air inleakage tests should be performed on real-time air monitors when they are
calibrated, whenever a monitor is replaced, and whenever a monitor's rubber O-rings or other
DOE G 441.1-1C 127
5-19-08
seals are replaced. Ideally, tests for inleakage should also be performed during monthly or
quarterly performance tests. Care should be exercised to prevent equipment damage during
testing. For example, rapid changes in sample line pressure on some real-time air monitors may
damage the detector.
Procedures should be established to address the appropriate review and use of data when
a critical component of an air monitoring system (e.g., detector or airflow meter) is
determined to be out of calibration. Procedures should be established to review the
accuracy of any data generated by that particular equipment since it was last calibrated.
10.7.2 Counting Room Equipment
Counting room equipment shall be routinely tested for operability [10 CFR 835.401(b)(4)]. Daily
performance checks of background count rate and radiation response (source checks) should be
performed on the counting system.
10.7.3 Audits
The radiation protection organization should perform and document a review of the adequacy
of air monitoring systems as part of any facility or operational changes affecting radiological
control. In the absence of such changes, a review should be conducted annually. The air
monitoring program should be reviewed as a functional element in the internal audit program
required under 10 CFR 835.102.
10.7.4 Recordkeeping
10 CFR 835 establishes specific requirements for the documentation of air monitoring. Chapter
13 of this Guide and the RCS discuss these requirements and provide detailed guidance.
10.8 Administrative Controls
10.8.0 Technical Basis Document
A document should be developed that provides the technical basis for selecting, placing, and
operating air sampling and real-time air monitoring equipment. This document should include
information such as:
performance and acceptance testing of new equipment;
filter media characteristics;
sample transport line losses (if applicable);
Section 105
flow rate and duration of sample collection;
identification of relevant supplies and equipment by manufacturer, make, and model;
DOE G 441.1-1C 128
5-19-08
performance of air flow studies;
rationale for the use and placement of air samplers and real-time air monitors;
rationale for demonstrating that air samples are representative of air breathed by
workers;
list of, and a facility map showing, actual locations of air sampling and real-time air
monitoring equipment;
calculation of the decision level, minimum detectable activity, and minimum detectable
concentration for sampling/counting configurations;
procedures for sample analysis;
procedures for sample accountability; and
routine maintenance and calibration of equipment.
This information should be readily available to radiation protection staff and should be
reviewed periodically and revised as necessary.
10.8.1 Written Procedures
Written procedures should be available for:
collecting air samples;
performing operability checks of air sampling and real-time air monitoring equipment;
calibrating flow rate meters;
calibrating any radiation detectors that are part of the air monitoring equipment;
conducting air flow studies to aid in the placement of air sampling and real-time air
monitoring equipment; and
interpreting the air monitoring results.
Other written procedures should be established for the following:
counting room staff, on the operation and routine maintenance of air sample counting
equipment, including the development and continued use of source count statistical
control charts.
radiochemistry staff, on the performance of special analyses.
Any changes in procedures used for monitoring in the workplace shall be documented
[10 CFR 835.704(e)].
DOE G 441.1-1C 129
5-19-08
11.0 RADIOACTIVE CONTAMINATION CONTROL
Work with unsealed quantities of radioactive material creates the potential for generating
radioactive contamination. 10 CFR 835 requires, in part, a contamination control program
sufficient to provide warning of the presence of surface contamination and to prevent the
inadvertent transfer of contamination at levels exceeding specified values outside of radiological
areas under normal operating conditions.
An acceptable contamination control program incorporates two types of control: (1)
Engineered control, and (2) administrative control. Contamination monitoring is part of and
verifies the effectiveness of the contamination control program.
In implementing a contamination control program, engineered controls that control
contamination at the source are the most important element. Engineered controls incorporated
into older facilities may not be sufficient to meet modern contamination control standards. The
engineered controls used in a contamination control program may include temporary
containment and ventilation, which may be the primary methods of controlling airborne
radioactivity and internal exposures to workers in older facilities, during relatively short-term
operations and maintenance, and in other situations in which permanent engineered controls
are unavailable or inadequate. For example, a permanently installed high efficiency particulate
air (HEPA)-filtered ventilation system may be included as a physical design feature in a facility to
control airborne radioactive material concentrations during routine operations, but a temporary
HEPA-filtered ventilation system may be used as an engineering control during certain
Section 106
maintenance activities. Similarly, a drain system may be included as a physical design feature to
route contaminated fluids to a controlled collection point, but temporary drains may be
installed as engineered controls during system breach. Finally, administrative controls, including
access restrictions and the use of specific work practices designed to minimize contamination
transfer, should be used as the tertiary method to control exposure to contamination hazards.
These elements of a contamination control program are not independent. The permanent
engineered controls included in a facility will dictate the types and levels of administrative
controls and engineered controls that are possible and necessary.
A contamination control program is an essential element of a comprehensive radiological
control program. In this Guide, when another element of a radiological control program
interfaces with the contamination control program, the appropriate chapter is referenced and
the topic of interest is listed as it applies to contamination control. Because of these interfaces,
individuals involved with the contamination control program should interact with personnel
working in other elements of the radiological control program, particularly with individuals
DOE G 441.1-1C 130
5-19-08
involved in instrument calibration, posting and labeling, air monitoring, internal and external
dosimetry, As Low As Is Reasonably Achievable (ALARA), training, and record-keeping programs.
Detailed information on contamination controls applicable to specific radiological hazards is
provided for tritium facilities, in DOE-HDBK-1129-2008, TRITIUM HANDLING AND SAFE STORAGE
(DOE 2008f).
11.1 Implementation Guidance
Activities that have the potential to generate surface contamination should be evaluated to
ensure appropriate controls are established. To the extent practicable, contamination controls
should be consistent to facilitate effective implementation by affected individuals. This chapter
describes methods for establishing and operating an acceptable contamination control program.
The discussion is divided into the following topics:
Contamination Control Program Management;
Engineered Controls;
Administrative Control; and
Contamination Monitoring.
Note that the requirements of 10 CFR 835.1101-1102 and the values provided in 10 CFR 835
Appendix D (Surface Contamination Values) apply only to radioactive material that is present in
the form of surface contamination. See Appendix D of Chapter 16 of the Guide for a listing of
values. The storage, movement, and use of radioactive material in other forms (e.g., material
that is intrinsically radioactive or that has been made radioactive through activation processes)
should be controlled consistent with applicable requirements in 10 CFR 835, including the
training requirements under 10 CFR 835.901, the ALARA controls required under 10 CFR 835.101
and 835.1001- 1003, and the controlled area maximum yearly dose expectation provided in
10 CFR 835.602.
11.2 Contamination Control Program Management
Common characteristics of effective contamination control programs include:
strong, written upper management commitment to control of contamination in the
workplace;
consistent line management implementation of required controls through established
procedures, training, and frequent supervision;
detailed work planning, including effective hazards analysis, pre-job briefings, and
Section 107
post-job debriefings; and
DOE G 441.1-1C 131
5-19-08
consistent program support by affected individuals.
Management commitment should be established in a written policy which may be included
in the ALARA Policy statement or other policy-level document. The policy should be
implemented by written procedures, technical work documents, and radiological work permits
commensurate with the hazards and required controls and sufficient to ensure consistent
program implementation given the education, training, and skills of the affected individuals.
Guidance on developing written procedures and on ensuring the appropriate education,
training, and skills of affected individuals is provided in Chapter 3. Guidance on radiation safety
training is provided in Chapter 14. The radiological control manager should be responsible for
the development of the contamination control program, including associated design reviews.
Contamination control is the responsibility of everyone involved in radiological activities. All
individuals working with radioactive material should follow established procedures that meet or
exceed the guidance provided in this Guide and applicable DOE Orders and regulations. Line
managers should be responsible for overseeing program implementation by their subordinates.
Guidance on effective planning for work with radiological hazards is provided in Chapter 4 of
this Guide and Chapter 3 of the RCS.
11.3 Engineered Controls
Appropriate controls that prevent the inadvertent transfer of removable contamination to
locations outside of radiological areas under normal operating conditions shall be maintained
and verified [10 CFR 835.1102(a)]. 10 CFR 835.1001 requires measures to be taken to maintain
radiation exposure as low as is reasonably achievable through engineered controls and
administrative controls. The primary methods used shall be engineered controls (e.g.,
confinement, ventilation, remote handling, and shielding). Administrative controls shall be
employed only as supplemental methods to control radiation exposure [10 CFR 835.1001(a)].
DOE recognizes the fact that the design and operating history of its facilities and the nature
of existing contamination hazards may make control of contamination problematic, particularly
in outdoor areas where legacy contamination may exist. Therefore, DOE regulations do not
require that the controls implemented to prevent the transfer of removable contamination be
impervious to ensure regulatory compliance. However, the controls should be appropriate to
the extent of the hazard and the potential adverse effects that may result from such transfer.
Should the potential exist for radioactive contamination to be transferred outside of posted or
controlled radiological areas (i.e., as a result of human or animal intrusion, containment or
system failures, planned work activities, or natural forces), enhanced monitoring and control
programs should be developed and implemented to identify affected areas and ensure timely
detection of the transfer and institution of appropriate controls over the affected area as
required by 10 CFR 835 and further explained in this Guide.
Radiological control is affected by human performance and engineered design features.
General and radiological design criteria for new facilities and major modifications to existing
DOE G 441.1-1C 132
5-19-08
facilities are provided in 10 CFR 835 and DOE O 420.1B, Facility Safety (DOE 2005d). The design
Section 108
of facilities currently under construction or modification should be planned and evaluated for
adherence to the applicable criteria. The effectiveness of design features should be evaluated
through performance of area and individual monitoring. See Section 11.5 of this Guide and
Chapter 5 of the RCS for further information regarding contamination monitoring.
Engineered controls that should be considered to enhance control of workplace
contamination include:
containment of process materials to the maximum practicable extent;
components and materials that minimize leakage across seals;
catch basins and controlled drains from potential leakage points;
use of multiple barriers as necessary to control the spread of contamination. (For
instance, a room, system or vessel that contains radioactive material should be designed
and operated to retain that material, and should also be equipped as necessary with
drain and ventilation systems to direct any leakage that may occur to appropriate
collection systems);
adequate working space around serviceable components to facilitate maintenance and
repairs;
filtered ventilation from areas of lower to areas of higher contamination levels;
adequate space for donning and removal of protective clothing and individual frisking in
low-background areas; and
location of office and break areas away from radiological areas.
In addition to the above, facility design, including materials selected, shall include features
that facilitate operations, maintenance, decontamination, and decommissioning
[10 CFR 835.1002(d)]. These activities should be facilitated by limiting the size of any
contaminated areas and the magnitude of the contamination levels within those areas. To the
maximum possible extent, materials used should be readily decontaminated using
non-hazardous compounds, particularly water or steam. Smooth, corrosion resistant surfaces
and rounded edges also facilitate decontamination. More detailed information on design
features is provided in Chapter 4 of this Guide and Chapter 3 of the RCS.
When permanent engineered controls are not sufficient to prevent the spread of
contamination in the workplace, temporary engineered controls, such as containment devices
and portable or auxiliary ventilation, should be installed. These circumstances arise frequently
during maintenance, modifications, and decontamination and decommissioning. Planning for
such activities should include evaluation of the potential for contamination spread and the
effectiveness of engineered controls to reduce such potential, and, to the extent that
DOE G 441.1-1C 133
5-19-08
engineered controls will not be effective, prescription of administrative controls to limit the
spread of contamination.
Temporary containment devices may be particularly useful in controlling contamination
spread resulting from system leaks and from maintenance that requires contaminated system
breach. These devices range in complexity from simple plastic catch-basins suspended below
leakage points to complex portable buildings used to enclose an entire work area. Many
commercially-available designs include provisions for glove and equipment ports, ventilation,
and contamination reduction exit portals.
Portable air handling systems used in contaminated areas, including vacuum cleaners,
should be equipped with HEPA filtered exhausts or have their exhausts directed to installed
Section 109
systems that are so equipped. These provisions may not be necessary in areas where only
tritium or radioactive noble gases are present or when the material to be vacuumed is wet
enough to preclude re-suspension after entry into the system collection chamber. Improper use
of vacuum cleaners and portable air-handling equipment may result in the generation of
airborne radioactive material or removable surface contamination. Extended use of air handling
equipment may result in a significant build-up of radioactive material in the ductwork and
filters. Periodic monitoring of the exhausted air and accessible equipment surfaces should be
performed to assess the radiological impact of equipment operation. Chapter 4 of the RCS
provides more detailed information regarding use of portable ventilation units and vacuum
cleaners.
Although use of the devices discussed above has been proven effective in reducing
contamination spread and the associated decontamination costs, these benefits must be
weighed against the potential costs. Use of engineered controls may require expenditure of
worker dose to set up, work in, maintain, and remove the device. There may be financial costs
associated with device purchase or manufacture, training, possible reduced productivity, and
device or component set-up, maintenance, and disposal. These factors are considered in
implementation of an effective ALARA program, which is discussed in more detail in Chapter 4.
11.4 Administrative Control
When the use of engineered controls to limit individual exposures is impractical,
administrative controls shall be implemented to maintain exposures ALARA
[10 CFR 835.1001(b)]. To control the spread of contamination and limit individual exposures, a
graded, multiple-tier system should be used in and around contaminated areas. The
effectiveness of the controls should be verified through the conduct of contamination
monitoring, as discussed in Section 11.5 of this Guide and Chapter 5 of the RCS.
11.4.0 Work Authorizations
Guidance on the use of work authorizations is provided in Chapter 4 of this Guide and
Chapter 3 of the RCS.
DOE G 441.1-1C 134
5-19-08
11.4.1 Access Control
Control of entry to contaminated areas is necessary to ensure that personnel entering the
area are informed of the radiological status and potential hazards and are provided with the
appropriate protective apparel and equipment. Control of egress from contaminated areas
ensures that radioactive material is not inadvertently removed from the area by personnel or
equipment. Efforts should be made to limit the degree of contamination and the size and
number of contaminated areas in the facility, thereby limiting the need for use of protective
clothing and the undesirable side effects of restricted access to facility equipment, heat stress,
and radioactive waste generation.
11.4.1.0 Entry Controls
Protective clothing shall be required for entry into contaminated areas where removable
contamination levels exceed the values provided in Appendix D of 10 CFR 835
[10 CFR 835.1102(e)]. The type of protective clothing required should be prescribed based upon
considerations of contamination levels, chemical and physical form of the contaminant,
activities to be performed, and area accessibility. Other area and activity hazards, such as heat,
flame, hazardous chemicals, physical obstructions, electrical shock, and limited visibility, should
Section 110
be considered when prescribing protective clothing. Appendix C "Compliance Guidelines" of
29 CFR 1910.120 (OSHA 1974) provides guidance on these considerations as follows:
The use of PPE can itself create significant worker hazards, such as heat stress, physical
and psychological stress, and impaired vision, mobility, and communication. For any given
situation, equipment and clothing should be selected that provide an adequate level of
protection. However, over-protection, as well as under-protection, can be hazardous and
should be avoided where possible.
Two basic objectives of any PPE program should be to protect the wearer from safety
and health hazards, and to prevent injury to the wearer from incorrect use and/or
malfunction of the PPE. To accomplish these goals, a comprehensive PPE program should
include hazard identification, medical monitoring, environmental surveillance, selection, use,
maintenance, and decontamination of PPE and its associated training.
The written PPE program should include policy statements, procedures, and guidelines.
Copies should be made available to all employees, and a reference copy should be made
available at the worksite. Technical data on equipment, maintenance manuals, relevant
regulations, and other essential information should also be collected and maintained.
Multiple layers of protective clothing should be prescribed for areas in which the removable
contamination levels exceed 10 times the values provided in Appendix D of 10 CFR 835,
consistent with the consideration provided above. When penetration of the protective clothing
by the contaminant is likely, such as during activities likely to induce heavy sweating or
otherwise wet the individual, an additional layer of impenetrable clothing should be considered.
In some cases, provision of an impenetrable plastic sheet for sitting or kneeling will be adequate
DOE G 441.1-1C 135
5-19-08
and will reduce the hazards of heat stress. Additional guidance is provided in Chapter 3 of the
RCS.
Prior to unescorted access to radiological areas (including contaminated areas) and prior to
performing unescorted radiological work, each individual shall complete radiation safety
training commensurate with the hazards in the area and the required controls
[10 CFR 835.901(b)]. Guidance on radiation safety training is provided in Chapter 14 of this
Guide and Chapters 3 and 6 of the RCS.
11.4.1.1 Egress Controls
Exits from contaminated areas should include provisions to facilitate retention of
contamination in the area and for monitoring of individuals and the area to ensure control has
been maintained. Undress methods should be prescribed to minimize the potential for
contamination spread. When complex methods are necessary for removal of multiple layers of
protective clothing, assistance should be provided.
Individuals exiting contaminated areas shall be monitored, as appropriate, for the presence
of surface contamination [10 CFR 835.1102(d)]. At a minimum, individuals exiting contaminated
areas should perform a whole body frisk, using either portable or automated devices. The use
of automated whole body frisking devices should be considered due to the consistency of
results achievable with such devices. For individuals exiting areas where the only contaminated
areas are laboratory bench surfaces or fume hoods, or where contamination potential is limited
to specific portions of the body, the frisking should concentrate on affected areas. Exiting
Section 111
individuals should be trained to frisk any personal items carried into the area. Personal items
include papers, pens, jewelry, security badges, dosimeters, and other items commonly used
within the area. Necessary monitoring of tools or other material and equipment should be
performed by trained radiological control personnel. See Section 11.5.2 of this Guide for
information concerning necessary monitoring of material and equipment.
The instruments and techniques used for contamination monitoring shall be appropriate for
the types, levels, and energies of the radiations encountered and for the existing environmental
conditions, be periodically calibrated and maintained, and be routinely tested for operability
[10 CFR 835.401(b)]. Detailed guidance on selecting, calibrating, and using portable
contamination control instruments is provided in Chapter 9 of this Guide and Chapter 5 of the
RCS.
Because skin contamination by certain radioisotopes, such as tritium, cannot be reliably
detected by currently available hand-held or automated monitoring instrumentation, individual
frisking is not an appropriate means of detecting skin contamination, as discussed in
10 CFR 835.1102(d). When individual exposure to such contamination hazards is possible,
additional emphasis should be placed on radiobioassay programs and routine contamination
and air monitoring programs. Detailed guidance on radiobioassay and air monitoring programs
is provided in Chapters 5 and 10 of this Guide.
DOE G 441.1-1C 136
5-19-08
If background radiation levels or other conditions at the exit point preclude performance of
personnel frisking, the exit point should be relocated to an area of lower background levels. If
relocation of the exit point is not practicable, individuals should proceed directly from the exit
point to an appropriate area to perform a whole body frisk. The travel path should be
monitored frequently for contamination spread during use and after the detection of any
contamination at the frisking station.
The instruments used for frisking should be capable of detecting contamination at or below
the total surface contamination values provided in Appendix D of 10 CFR 835. Individuals should
be trained in proper frisking techniques, including detector speed and distance, and proper
techniques should be enforced through frequent line management observation. Frisking for
skin contamination while wearing protective clothing will not generally provide detection
capability adequate to ensure compliance with 10 CFR 835. Frisking for hot particles may
require special techniques and should reflect considerations of source to detector size effects.
Such factors should be included in radiation safety training and reinforced through line
management attention.
11.4.1.2 Posting and Labeling
Guidance on area posting and contaminated item labeling is provided in Chapter 12 of this
Guide, and Chapters 2 and 4 of the RCS.
11.4.2 Areas of Fixed Contamination
The control measures discussed above have been proven effective in minimizing the
generation and spread of removable contamination. However, these measures may not be
appropriate for implementation in areas having only fixed contamination. When surfaces with
fixed contamination are located within a radiological area, the radiological area posting and
entry control requirements provide for adequate control of entry and egress. Additional control
Section 112
measures may be necessary to prevent inadvertent or unauthorized removal of the fixed
contamination by methods that disturb the surface. 10 CFR 835 establishes specific
requirements for controlling such locations outside of radiological areas. Although fixative
coatings may be used to bind the contamination to the surface, such usage should be minimized
and removable contamination levels should be reduced to levels that are ALARA prior to
application of the coating.
When located outside of radiological areas, accessible areas in which only the fixed
contamination levels exceed the total surface radioactivity values provided in Appendix D of
10 CFR 835 (i.e., removable contamination levels are below the Appendix D removable surface
radioactivity values) shall [10 CFR 835.1102(c)]:
undergo routine monitoring to ensure removable surface contamination levels remain
below the Appendix D values. Monitoring should be conducted in and around the area
using techniques discussed in Section 11.5.1 of this Guide; and
DOE G 441.1-1C 137
5-19-08
display conspicuous markings to warn individuals of the contaminated status. The
marking may consist of stencils on affected surfaces or postings established at each
access point. The marking should include the radiation warning trefoil and the words
"Caution, Fixed Contamination" and should provide radiation protection instructions
sufficient to prevent inadvertent removal of the contamination.
Additional guidance on labeling of items having only fixed contamination is provided in
Chapter 12. Additional information on control of fixed contamination is provided in Chapter 2 of
the RCS.
11.4.3 Conduct of Radiological Work
Work in contaminated areas should be conducted in a manner that minimizes the spread of
contamination to adjacent surfaces, individuals in the area, and the workplace atmosphere. The
following controls and techniques should be included in work planning and employee training:
minimization of individuals and materials entering contaminated areas;
a dedicated contaminated tool program, if justified by the extent of contaminated area
work activities;
proven work techniques to minimize contamination spread, including techniques to
minimize the release of hot particles;
judicious use of stop-work authority to correct radiological problems before they
escalate;
judicious work area monitoring to detect, and decontamination to reduce,
contamination spread; and
priority repair of leaks to minimize the spread of contamination.
Chapter 3 of the RCS provides more information on these issues.
11.4.4 Personnel and Material Decontamination
Two types of personnel contaminations can occur: skin (or personal clothing) contamination
and wound contamination. In this context, personal clothing includes work clothing provided by
the employer, but does not include protective clothing provided solely for contamination
control purposes. Potential internal contamination caused by exposure to airborne radioactive
material is discussed in Chapter 5 of this Guide, DOE-STD-1121-2003, and Chapter 5 of the RCS.
11.4.4.0 Skin and Clothing Contamination
DOE G 441.1-1C 138
5-19-08
When individuals detect skin (or personal clothing) contamination, they should notify the
radiological control organization to ensure adequate characterization of the potential for
significant skin dose. A qualified radiological control organization representative should:
Section 113
assess the extent of the contamination;
retain samples of the contamination as necessary to perform a detailed dose
assessment. Levels of contamination that trigger the need for dose assessments should
be established for site-specific radionuclides. These trigger levels should not exceed 100
millirem (1 mSv) (equivalent dose to the skin); and
initiate decontamination procedures that minimize skin abrasion and changes in pore
size.
Skin decontamination methods should be established for site-specific radionuclides.
Intrusive decontamination methods, such as tissue removal, require medical assistance.
Contaminated personal clothing should be decontaminated by laundering or other appropriate
methods, monitored, and returned to the owner or, if necessary, disposed of as radioactive
waste.
11.4.4.1 Wound Contamination
Medical treatment of injuries takes precedence over radiological considerations. Emergency
medical care should be administered immediately for injuries involving radioactive materials in
accordance with National Council on Radiation Protection and Measurements Report Number
No. 65, Management of Persons Accidentally Contaminated with Radionuclides (NCRP 1980) and
DOE-STD-1121-2008.
11.4.4.2 Material and Area Decontamination
In general, water and steam are the preferred decontamination agents. Other cleaning
agents should be selected based upon their effectiveness, hazardous properties, amount of
waste generated, compatibility with the contaminated surface and other systems or items that
may be contacted (including protective clothing and waste handling systems), and ease of
disposal.
11.5 Contamination Monitoring
Comprehensive surveillance for contamination is the best available assurance of compliance
with the requirements of 10 CFR 835. Frequent routine and special contamination monitoring
should be performed in and around contaminated areas to verify the levels and locations of
contamination and to alert personnel to changes in levels.
An effective contamination monitoring program includes the capability to calibrate
instruments and perform appropriate operational tests, monitor for contamination, determine
the lower detection limits both for field and laboratory instruments, and conduct the
appropriate quality control checks to assure reliable instrument performance.
DOE G 441.1-1C 139
5-19-08
11.5.0 Contamination Control Values
Appendix D of 10 CFR 835 establishes values above which contamination controls, including
posting, access controls, and radioactive material controls must be implemented. The
contamination monitoring program should be sufficient to identify the location of surfaces
having contamination at such levels. Contamination levels on surfaces outside of contaminated
areas should be maintained below the applicable Appendix D values and as low as is reasonably
achievable.
The footnotes to Appendix D of 10 CFR 835 provide guidance on appropriate means of
determining the surface contamination levels and comparing these levels against the controlling
values. Footnote 3 to Appendix D of 10 CFR 835 indicates that the total contamination levels
may be averaged over an area of one square meter. When averaging total contamination levels
over a square meter, the applicable Appendix D value shall be considered to have been
exceeded if:
the average contamination level in the one square meter area exceeds the applicable
Appendix D value; or
Section 114
the sum of the activity in all isolated spots or particles in any 100 square centimeter
(cm2) area exceeds three times the applicable Appendix D value (10 CFR 835, App. D,
Footnote 3). In practice, this condition may be determined by evaluating a number of
100 cm2 grids and ensuring that the contamination level in any grid is less than three
times the applicable Appendix D value.
There are two different scenarios under which combinations of radionuclides may be
present as radioactive surface contamination:
there may be a combination of radionuclides all of which are within the same
10 CFR 835 Appendix D category (e.g., one horizontal row of the Appendix D table, such
as U-nat, U-235, U-238, and associated decay products); or
there may be a combination of radionuclides in different 10 CFR 835 Appendix D
categories (e.g., radionuclides in more than one horizontal row of the Appendix D table).
If a surface is contaminated with radionuclides all of which fall within the same 10 CFR 835
Appendix D category, then the contamination levels of the various radionuclides should be
summed to determine if contamination levels in any area monitored exceeds the applicable
Appendix D value. For example, if a surface is contaminated with both U-235 and U-238, then
the contamination levels of both radionuclides should be summed to determine whether or not
the applicable Appendix D value has been exceeded.
If a surface is contaminated with a combination of radionuclides in different 10 CFR 835
Appendix D categories, then the values provided in Appendix D of 10 CFR 835 may be
considered to be independent of one another. It is not necessary to perform a sum of the
fractions calculation to determine if the contamination levels in any area monitored exceed the
applicable Appendix D value. For example, if a surface is contaminated with both U-235 and
Sr-90, then the contamination levels of the two radionuclides may be compared independently
DOE G 441.1-1C 140
5-19-08
to the applicable Appendix D values. Although it is permissible to do so, there is no need to sum
the U-235 and Sr-90 contamination levels or their fractions relative to the applicable Appendix D
values. In practice however, it is often more convenient to determine the sum of the
contamination levels of the various radionuclides and to compare this figure to the most
conservative applicable Appendix D value.
Footnote 5 to Appendix D of 10 CFR 835 discusses application of the listed surface
contamination values for Sr-90. DOE recognizes that Sr-90 is typically present in equilibrium
with its daughter, Y-90. Therefore, the values given for Sr-90 in Appendix D should be applied to
the total activity from the Sr-90/Y-90 contamination. If the Sr-90 contamination resulted from
processes involving the separation and purification of Sr-90, the lesser values (200 dpm/100
cm2 - removable, 1,000 dpm/100 cm2 - total) should be applied. If the Sr-90 contamination is
present as a constituent of a mixture of fission products, the higher values should be applied
(1,000 dpm/100 cm2 - removable, 5,000 dpm/100 cm2 - total).
The following application of footnote 5 in appendix D of 10CFR835 to Sr-90 combined with
mixed fission products is considered an acceptable approach for compliance with 10CFR835:
Where the Sr-90 fraction is 50 percent or less, the mixed fission products surface activity
values apply.
Where Sr-90 fraction is between 50 percent and 90 percent of the total activity, surface
radioactivity values should be 3000 dpm/100 cm2 or less.
Section 115
Where the Sr-90 fraction exceeds 90 percent the total activity, Sr-90 surface
radioactivity values should be applied to the material.
If contamination by a radionuclide not listed in 10 CFR 835 Appendix D, such as certain
isotopes of uranium (e.g. U-234), is suspected or verified, the actual contamination level should
be compared to the Appendix D value(s) for radionuclides most similar to the contaminant(s)
(i.e., radiological and chemical properties). Appropriate actions (e.g., posting, labeling, access
controls) should be based on the results of these comparisons.
11.5.1 Monitoring
Individual and area monitoring shall be performed to demonstrate compliance with
10 CFR 835, document radiological conditions in the workplace, detect changes in radiological
conditions, detect the gradual buildup of radioactive materials in the workplace, verify the
effectiveness of engineering and process controls in containing radioactive materials and
identify and control potential sources of individual exposure to radiation and/or radioactive
material [10 CFR 835.401(a)]. Monitoring frequencies should be based on potential and actual
radiological conditions, probability of change in conditions, and area occupancy factors. The
contamination monitoring program should incorporate the following features:
scheduled routine monitoring for removable contamination and, where feasible, fixed
contamination. Schedules should be adjusted to reflect changes in conditions, activities,
and previous results;
DOE G 441.1-1C 141
5-19-08
special monitoring as necessary to accommodate planned events, such as maintenance
and repairs, barrier breach or leakage, material movement, and unplanned events such
as spills;
sample analysis and monitoring using instruments and techniques capable of detecting
contamination below the values specified in Appendix D of 10 CFR 835. To provide for
early warning of changes, a sample of smears taken from areas surrounding
contaminated areas should be analyzed for contamination at levels below the Appendix
D values;
documentation of survey results;
timely documented review of results for trends and changes and the need for further
action, such as decontamination, posting, changes in monitoring frequency, and access
controls; and
provision of results for use by individuals planning work in or entering the area.
Monitoring for removable contamination should be conducted using conventional smear
techniques for quantitative analyses and, where practicable, large-area smears for qualitative
analyses. The use of large-area smears, adhesive pads or adhesive rollers is also helpful in
identifying hot particles. Direct frisking is necessary for detecting fixed contamination;
however, the application of direct frisking may be limited by such items as: background
radiation levels, frisking surface characteristics (smooth/rough, wet/dry), frisking detector
capabilities, frisking speed and distance, and type and energy of radiation being detected.
Monitoring techniques should be developed and documented to ensure that the collected data
are representative of the entire surface, with special attention paid to likely points for collection
of contamination, such as leakage points, rough surface areas, areas that are infrequently
cleaned, current work areas, and high traffic areas.
Section 116
Conventional dry smear monitoring techniques may prove to be ineffective in the detection
of tritium contamination. If tritium contamination is likely, monitoring should be performed
using wet smears or direct frisking techniques or a combination of these methods. The
monitoring method should be selected with due consideration of the characteristics of the
radiation emitted by tritium. DOE-HDBK-1129-2008 provides guidance on monitoring for
tritiated water and tritium gas (DOE 2008k). DOE-STD-1129-2008, TRITIUM SAFE HANDLING AND
STORAGE, Appendix E: RADIOLOGICAL CONTROL PROGRAMS FOR SPECIAL TRITIUM
COMPOUNDS provides guidance for radiological controls, including monitoring, for special
tritium compounds.
Under certain conditions, radioactive contaminants may tend to penetrate the
contaminated surface and then return to the surface over an extended period of time. This
phenomenon is often encountered when dealing with tritium contamination (off-gassing) and
when handling items that are stored or used under water (leaching), such as high level waste
storage and shipping casks. When such conditions are likely, enhanced contamination
monitoring methods that are capable of detecting changes in contamination levels as a result of
leaching or off-gassing should be used.
DOE G 441.1-1C 142
5-19-08
Because of difficulties in implementing conventional removable contamination monitoring
techniques (e.g., smear surveys), the presence of radioactive contamination in or on soil or
other surfaces contaminated with granular solids may present significant challenges to the
contamination monitoring program. Although the measurement of contamination levels in the
granular solid (on a quantity of radioactive material per weight or volume basis) may be
relatively straightforward, it may be difficult to compare the results of such measurements to
the 10 CFR 835 Appendix D values, which are provided in units of contamination levels per unit
area. Such comparisons are necessary to ensure compliance with the 10 CFR 835 requirements
for posting and area and material control. DOE recognizes the difficulties associated with such
measures. To ensure compliance, an assessment should be performed to determine the
likelihood that radioactive contamination may be dispersed from the surface in question to
surrounding areas or to items or individuals who may come in contact with the surface. The
assessment may include a review of the operating history to determine whether significant
contamination dispersion has occurred in the past, calculations based on realistic dispersion
scenarios, performance of tests to determine the magnitude of contamination dispersion under
actual operating conditions, or other technically defensible measures. If the results of the
assessment indicate that contamination at levels exceeding the 10 CFR 835 Appendix D values is
likely to be dispersed from the contaminated surface to surrounding or contacting surfaces,
then the surface in question should be considered contaminated at levels exceeding the
Appendix D values. If the surface in question is considered contaminated at levels exceeding the
Appendix D values appropriate protective measures shall be implemented [10 CFR 835.1001(a)].
See the hierarchy of controls discussion in the introduction to Chapter 11.0.
Section 117
10 CFR 835.401(b) requires that instruments and equipment used for monitoring be
appropriate for the types, levels, and energies of the radiation(s) encountered. The
effectiveness of the contamination monitoring techniques discussed in this chapter may be
limited due to the physical conditions and specific characteristics (chemical and radiological) of
radionuclides present in some DOE facilities. For example, common frisking and smear counting
techniques and instruments may not be effective in detecting certain low-energy radiations.
Detailed technical guidance for performing monitoring under these conditions is outside the
scope of this Guide. Monitoring under these conditions should be conducted in accordance with
applicable DOE Technical Standards and other documents, including those referenced in Chapter
11 of this Guide.
Other scientific standards (e.g., ANSI or Health Physics Society Standards or International
Commission on Radiological Protection (ICRP) or National Council on Radiation Protection and
Measurement (NCRP) publications) should also be considered.
Additional information regarding requirements for instruments and documentation is
provided in Chapters 9 and 13 of this Guide, and in Chapters 5 and 7 of the RCS.
11.5.2 Control of Material and Equipment
Release of material and equipment from contaminated areas presents special challenges.
Many items have surfaces that are inaccessible, making adequate monitoring of surface
contamination difficult. Monitoring of large items and vehicles can be time consuming and
difficult in inclement weather. For these reasons, to the maximum extent practical, materials
and equipment that enter contaminated areas should be retained there.
DOE G 441.1-1C 143
5-19-08
Except as noted below, any material and equipment that enters contaminated areas shall be
retained there if [10 CFR 835.1101(a)]:
monitoring of accessible surfaces indicate the presence of removable surface
contamination at levels exceeding the removable surface contamination values
provided in Appendix D of 10 CFR 835; or
prior use of the material and equipment indicates that removable surface
contamination levels on inaccessible surfaces are likely to exceed these levels.
Material and equipment control programs should include features that:
provide for assessment of the likelihood of material and equipment contamination
through documentation of material and equipment location and use, monitoring of
material and equipment surfaces, or a combination of these techniques;
where monitoring is necessary, include monitoring for both fixed and removable
contamination;
for materials and equipment with inaccessible surfaces that are likely to be
contaminated, require disassembly to the extent necessary to perform monitoring on
those surfaces;
require reduction of surface contamination before release to levels that are as low as
reasonably achievable; and
require retention of materials and equipment having contamination levels in excess of
the values provided in Appendix D of 10 CFR 835.
A prospective and retrospective assessment of the likelihood of material and equipment
contamination should consider:
the nature of the material and equipment;
radiological conditions in the locations in which it will be or was stored and used;
controls established to reduce the likelihood of contamination transfer (wrapping or
taping);
the degree of assurance that exists regarding knowledge of the material’s and
equipment's storage and use; and
Section 118
material and equipment properties that are or were likely to preclude contamination
transfer or enhance the likelihood of contamination transfer (e.g., surface irregularities,
installed fans and air inlets).
Under certain circumstances, materials and equipment having removable surface
contamination levels in excess of the values provided in Appendix D of 10 CFR 835 may be
DOE G 441.1-1C 144
5-19-08
released to controlled areas. Materials and equipment having either removable or total
contamination levels in excess of these values may be released for movement to another
radiological area. Appropriate monitoring and controls shall be implemented
[10 CFR 835.1101(b)] and should include:
determining the contamination levels before movement;
wrapping or containing the material and equipment to prevent the spread of
contamination;
applying appropriate labels to the material and equipment and postings at the
destination;
selecting the transport path to minimize the potential for contamination spread; and
monitoring the transport path as necessary after movement to ensure that
contamination has not been spread
Materials and equipment having fixed contamination (in either accessible or inaccessible
locations) in excess of the total surface radioactivity values provided in Appendix D of
10 CFR 835 may be released for use in controlled areas. Release of such materials and
equipment shall require that [10 CFR 835.1101(c)]:
removable contamination levels be below the values provided in Appendix D.
Contamination levels should be assessed in accordance with the guidance provided in
this Guide;
routine monitoring be conducted. The monitoring should be adequate to ensure that
the radiological hazard resulting from the release is fully characterized and that
appropriate posting, labeling, and access control measures are implemented; and
the material and equipment is clearly marked or labeled. Guidance for material and
equipment labeling is provided in Chapter 12 of this Guide, and Chapter 4 of the RCS.
Written records of material and equipment release monitoring are required
[10 CFR 835.703(c)]. These records should include:
a description of the material and equipment. Where large quantities are involved, a
simple entry such as "box of nails" or "tool box full of hand tools" is adequate;
monitoring date;
identity of individual performing the monitoring;
survey meter type and identification number; and
monitoring results.
DOE G 441.1-1C 145
5-19-08
An acceptable approach to compliance with the record keeping requirements for release of
materials from radiological areas is to use a single record or entry that contains a general
description of a group of non-traceable items released from radiological areas. In addition to the
property description, such records must contain the information specified by 10 CFR
835.1101(d).
The provisions of 10 CFR 835 do not apply to release of materials and equipment from
controlled areas. Material, equipment, and real property which have been documented to
comply with the criteria for release from controlled areas set forth in an authorized limit which
has been approved by a Secretarial Officer in consultation with the Chief Health, Safety and
Security Officer are expressly excluded from the provisions 10 CFR 835 [10 CFR
835.1(b)(6)]. These activities are subject to DOE standards for protection of the environment.
The release of materials and equipment from DOE control requires following the process
specified in DOE O 458.1.
Section 119
11.5.3 Portal Monitors, Laundry Monitors, and Tool Monitors
DOE encourages the use of automated monitoring devices for evaluating material and
equipment for release to controlled areas. Automated monitoring devices are typically large gas
proportional or plastic scintillation detectors arranged in a shielded counting chamber into
which objects may be placed. The monitor counts the object using a count time sufficient to
achieve the desired confidence level and compares the net count rate from the object with a
pre-determined alarm set point.
Automated monitoring devices are appropriate for monitoring of the external surfaces of
non-porous, industrially clean objects. Objects with potential internal contamination should be
surveyed using portable survey instruments. In general, automated monitoring devices are not
appropriate for releasing porous material that has been contaminated in depth (e.g., wood,
concrete) or in volume (e.g., activated material, smelted contaminated material). However,
such devices may have limited application to monitoring of items contaminated in depth or
volume by radioisotopes that emit high energy gamma radiation.
DOE G 441.1-1C 146
5-19-08
12.0 POSTING AND LABELING FOR RADIOLOGICAL CONTROL
The goal of a radiological hazard posting and labeling program is to identify and effectively
communicate radiological hazards to individuals, allowing them to take the appropriate
protective actions. In pursuit of this goal, a radiological posting and labeling program works in
concert with other hazard communication programs, including programs for radiation safety
training, work authorizations, written procedures, and briefings.
10 CFR 835 requires that certain areas and items be posted or labeled to control personnel
exposure to radioactive material and ionizing radiation and to prevent the spread of
contamination. 10 CFR 835 also provides exceptions from the posting and labeling
requirements under certain circumstances; these exceptions apply to posting or labeling
requirements only. They do not apply to entry control or radiation safety training requirements.
12.1 Implementation Guidance
This chapter discusses the regulatory requirements for radiological hazard posting and
labeling and provides guidance for achieving compliance with those requirements. Postings for
other health and safety concerns, such as those for nuclear criticality and industrial safety
concerns should be in addition to the postings specified for radiological control.
12.2 General
10 CFR 835 establishes specific requirements for posting of controlled areas, radioactive
material areas (RMAs), and radiological areas. Controlled areas are established to warn
individuals that they are entering areas that, because of the presence of radiological areas
and/or RMAs, are controlled for radiation protection purposes. RMAs and radiological areas are
established within the controlled area to provide warning of specific hazards that may require
individual protective action for safe entry and egress.
10 CFR 835 also establishes specific requirements for labeling of items or containers of
radioactive material exceeding specified threshold activity levels. Radioactive material labels
are used to provide warning to individuals of the presence of radioactive material, particularly in
areas in which the radiological hazard does not warrant area posting in accordance with
10 CFR 835. Use of electronic means to label items or containers (e.g., bar codes) in conjunction
with human readable labels may help reduce human error rates and assist in tracking and
inventory of materials.
Section 120
10 CFR 835.104 requires that written procedures be developed and implemented as
necessary to ensure compliance, commensurate with the radiological hazards and consistent
with the education, training, and skills of the exposed individuals. With regard to the
radiological hazard posting and labeling program, written procedures should be developed to
address the program elements addressed in this Guide. The level of detail provided in these
procedures should be sufficient to provide assurance that the affected individuals can
implement the program in a manner that will achieve and maintain regulatory compliance.
10 CFR 835.104 provides flexibility for a site- or facility-specific determination of the appropriate
balance between individual education, training, skills, and specificity of the required written
procedures. As an example, if responsibility for posting radiological hazard signs is assigned to
DOE G 441.1-1C 147
5-19-08
radiological control technicians (RCTs) qualified in accordance with the RCS, then the written
procedures may be relatively brief, based upon the detailed knowledge possessed by the RCTs.
Conversely, if responsibility for posting radiological hazard signs is assigned to another work
group in the facility whose members have a less-detailed knowledge of the regulatory
requirements, then more detailed procedures should be developed and implemented, based on
the cognizant individuals’ presumably more rudimentary understanding of the specific
requirements of 10 CFR 835.
10 CFR 835.604 and 835.606 establish specific conditions under which radiological hazard
posting and radioactive material labeling are not required, generally due to the minimal hazards
present in certain areas or the implementation of other controls that are sufficient to limit
individual exposures to radiological hazards. Care should be exercised in implementing these
posting and labeling exceptions to ensure that both the specific and general requirements of
10 CFR 835 will be met in the absence of the area postings and material labeling. For example,
10 CFR 835.604 provides a posting exception for areas in which the radioactive material consists
solely of activated structures or installed components. Likewise, 10 CFR 835.606 provides a
labeling exception for radioactive material having an activity less than one tenth of the
10 CFR 835 Appendix E values and less than 0.1 Ci. See Appendix E of Chapter 16 of the Guide
for a listing of values. However, omission of postings and labels under these conditions may
affect the status of compliance with other requirements of 10 CFR 835, including the ALARA
requirements of 10 CFR 835.101 and 1001, the dose limit requirements of 10 CFR 835.207 and
835.208, and the maximum controlled area dose expectation of 10 CFR 835.602(a).
The 0.1 rem in a year dose expectation discussed in 10 CFR 835.602(a) is not a limit, but
represents DOE’s expectation for conditions within controlled areas, but outside of radiological
areas and RMAs. It does not require DOE’s operating entities to take specific actions to prevent
individuals who enter controlled areas, but who do not enter radiological areas, from receiving
more than 0.1 rem in a year. Individuals who enter the controlled area, but do not enter
radiological areas or RMAs are often, but not always, only incidentally exposed to radiation and
radioactive materials. While DOE’s expectation is that incidentally-exposed individuals will
receive less than 0.1 rem TED in a year, 10 CFR 835 does not require specific controls to limit
individual doses (other than doses to minors and members of the public) to this level.
Section 121
DOE’s operating entities are required to establish programs to limit individual dose
equivalents consistent with the dose limits established in Subpart C of 10 CFR 835 and the
ALARA process as required under 10 CFR 835.101 and 835.1001 - 835.1003. Subparts E, F, G, J,
and K of 10 CFR 835 establish requirements for individual monitoring, entry control, area
posting, radiation safety training, physical design features, and administrative controls that
support these requirements and provide flexibility for establishing controls that are
commensurate with the hazards. The requirements are complemented by guidance provided in
this Guide and the RCS. These requirements, when implemented as required by a documented
radiation protection program approved by DOE, fully satisfy DOE’s expectations for controlling
exposure in controlled areas, radiological areas, and RMAs.
Compliance with these requirements is generally achieved through implementation of a
comprehensive program that includes engineered controls, administrative controls, training,
area posting, and material labeling. Therefore, decisions regarding omission of area postings
and radioactive material labels should consider the full impact of such omissions and the ability
DOE G 441.1-1C 148
5-19-08
of the remaining program elements to ensure continued compliance. Such decisions should be
made on the basis of management-approved standards documented in the radiation protection
program, site-specific procedures, and/or the site-specific radiological control manual.
12.2.0 Design
Postings for controlled areas may be selected by the contractor to avoid conflict with local
security requirements [10 CFR 835.602(b)]. To the extent practicable, controlled area postings
should use the yellow and magenta radiological hazard warning color scheme, but the flexibility
provided in 10 CFR 835.602(b) extends to the shape, color scheme, and content of the
controlled area postings.
Postings for radiological areas and radioactive material areas and labels on radioactive items
and containers of radioactive material shall include the standard radiation warning trefoil in
black or magenta imposed upon a yellow background [10 CFR 835.601(a)]. Magenta is the
preferred color for the trefoil and any lettering on the posting. The standard radiation warning
trefoil is illustrated in Appendix A of this Guide. Unless circumstances do not permit, the
standard radiation warning trefoil should be oriented with one blade downward and centered
on the vertical axis. The standard radiation warning trefoil should be displayed as prominently
as is practicable.
Lettering should not be superimposed on the standard radiation warning trefoil, ANSI
N2.1-1971(R1989), Radiation Symbol, (ANSI 1989e). The size of lettering used on the sign should
not detract from the clarity of the standard radiation warning trefoil.
The background for the entire sign or label should be yellow. The lettering and standard
radiation warning trefoil should be proportional to the size of the sign or label. The color
scheme used for radiological postings and labels should be consistent throughout the site and
should be approved by the head of the cognizant radiation protection organization before use.
The color scheme used for radiological hazard posting and labeling should be reserved for
radiological hazards communication only.
Section 122
Signs and labels should be constructed of materials that can endure expected environmental
conditions without significant deterioration of color, legibility, strength, or other physical
characteristics. Although magenta is the preferred color for both the standard radiation
warning trefoil and the lettering, the magenta color tends to fade when exposed to sunlight.
Therefore, special consideration should be given to the selection of signs for outdoor postings to
ensure durability. If signs or labels will be used under conditions that are likely to result in
significant degradation, routine surveillances should be performed as necessary to verify
continued legibility. Signs and labels should not be altered or defaced in any way to change
their meaning. Inserts (on signs containing insert slots) may be changed, as appropriate.
12.2.1 Content
In addition to the standard radiation warning trefoil discussed above, postings and labels
required by 10 CFR 835 shall include the appropriate heading (“Caution,” “Danger,” or “Grave
Danger”) and wording describing the radiological hazard (10 CFR 835 hazard designation)
(10 CFR 835.603 and 835.605).
DOE G 441.1-1C 149
5-19-08
Signs required by 10 CFR 835 may include radiological protection instructions
[10 CFR 835.601(b)]. Supplemental wording describing additional warnings or directions should
be included on the postings or labels, as appropriate. Recommended supplemental wording on
potential and actual radiological conditions and specific controls is discussed in Chapters 2 and 4
of the RCS. 10 CFR 835 requires that each radiological area be posted. Therefore, if more than
one radiological condition exists in an area and requires posting, each condition shall be
identified (10 CFR 835.603). Multiple radiological conditions may be posted using one of two
common practices:
by posting each radiological condition on a separate sign with any appropriate
supplemental wording; or
by posting all radiological conditions on one or more signs (user-changeable signs using
inserts, for example) using the most stringent heading and listing the radiological areas
in decreasing order of importance. Any supplemental information should follow the
radiological area designations.
The second method is preferred because it reduces clutter and is more efficient.
Very high radiation area postings should be established on an exclusive sign without other
radiological area designations.
In recognition of the broad range of radiological conditions encompassed by the
10 CFR 835.2(a) definitions of the terms “airborne radioactivity area,” “high contamination
area,” and “high radiation area,” 10 CFR 835.603 allows use of either the "Caution" or "Danger"
heading on the required postings. This allows the hazard in the area to be more accurately
characterized. This is also an option for radioactive material labeling (see 10 CFR 835.605).
Accordingly, the "Caution" heading should be used for lower hazards and "Danger" for higher
hazards. With respect to radioactive material labeling, the amount, specific activity, and
chemical and physical characteristics of the radioactive material should be taken into
consideration. However, the use of only one heading for the entire range of conditions is also
acceptable.
Chapter 2 of the RCS provides guidance for posting of additional areas, including:
buffer areas surrounding radiological areas;
areas where soil contamination is present;
Section 123
areas where underground radioactive materials are present; and
access ports to enclosures having limited accessibility, such as glove bags and boxes.
While posting of these areas is not required to ensure compliance with the posting
requirements of 10 CFR 835, such postings may provide an additional regulatory margin and
degree of protection to affected individuals.
12.2.2 Visibility
DOE G 441.1-1C 150
5-19-08
Signs required by 10 CFR 835 shall be clearly and conspicuously posted [10 CFR 835.601(b)].
Each item or container of radioactive material that requires labeling shall bear a clearly visible
label (10 CFR 835.605).
When posting is required, appropriate signs should be placed intermittently along the
boundary (fences, barricades, ropes, tapes, etc.). The effect upon visibility of opening of doors
or other changes in configuration should be considered when posting radiological hazard
warning signs. At least one sign should be on each side of an area's boundary, and a sign should
be visible from any normal avenue of approach. A distance of 40 feet (12.2 m) between signs
along the area's boundary is considered acceptable. Radiological posting and labeling should be
securely affixed and located such that signs and labels can be expected to remain in place when
subjected to expected adverse conditions and environments.
When one radiological area is completely contained within another radiological area having
similar hazards (e.g., a high contamination area inside a contamination area) or individuals must
pass through one radiological area to enter another, it is not necessary to post the exits from
the inner area to indicate entry into the outer area.
12.2.3 Conditions
Radiological warnings are posted based upon actual or likely radiological conditions. Actual
conditions are determined through area monitoring. Likely conditions should be identified
based on professional judgment or experience regarding the probability that a radiological
condition will exist. When evaluating the likelihood of specified conditions, normal situations as
well as unique situations which can reasonably be expected to occur should be considered.
In many operations, the likelihood that a radiological condition will exist, rather than the
actual condition, will define the boundaries and posting of a radiological area. For example,
opening a contaminated ventilation system in a non-contaminated area may require a
contamination area to be established, or opening a radiological vacuum cleaner in a
contamination area may require that an airborne radioactivity area be established. Therefore,
past monitoring data, work-specific experience, and professional judgment should be included
in the decision on the correct posting of each area.
Radiological postings should be completed before work begins, updated periodically when
changes in radiological conditions occur or are expected, and removed as soon as is practicable
when no longer required.
Radiological posting and labeling should be used or displayed only to signify the actual or
likely radiological conditions. However, posting and labeling may also be used for illustrative
purposes in appropriate educational or informational matter. When used for this purpose, signs
and labels should be clearly marked to indicate that they are for training use only.
12.2.4 Accessibility
Radiological areas and radioactive material areas are defined based upon area accessibility.
An area is considered to be accessible to individuals when it contains entrance or access points
Section 124
DOE G 441.1-1C 151
5-19-08
of sufficient size to permit human entry, i.e., such that any portion of the body may be exposed
to the radiological hazard.
Areas with entrance or access points consisting of locked doors or other controls and
interlocks (including those specified under 10 CFR 835.502), should be considered accessible to
individuals. In contrast, areas with entrance or access points consisting of doors or portals, such
as man hole covers, that are bolted or otherwise more permanently sealed, may be considered
inaccessible, unless such doors or portals are opened on a routine basis. Likewise, areas in
which the radiological hazard is located underground, such that significant soil excavation,
drilling, natural forces, or other forms of intrusion would be required to gain access, may be
considered inaccessible. In general, areas with entrance or access points that require the use of
tools or lifting or excavation equipment to gain access may be considered inaccessible to
individuals. However, for ALARA purposes, these entrance or access points should be marked
indicating the radiological hazard that exists, or is likely to exist, behind the entrance or access
point and a warning not to open the barrier without authorization from the radiation protection
organization. In lieu of or in addition to such markings, physical controls (e.g., physical barriers,
entry alarms) and/or administrative controls (e.g., procedural controls, additional training)
should be implemented as necessary to prevent unauthorized or inadvertent entry to the area
or exposure of the hazard. Once the entrance point has been unsealed (or for underground
hazards, the covering soil has been disturbed or penetrated) such that individuals may be
exposed to the radiological hazard (whether or not such acts have been authorized), the area
should be considered to be accessible.
DOE G 441.1-1C 152
5-19-08
12.2.5 Boundaries and Barriers
Controlled areas, radioactive material areas, and radiological areas should be identified by
the use of a boundary identifier or a physical barrier and sufficient signs. The combination of
signs and boundary identifiers should be sufficient to warn approaching individuals that they are
entering an area controlled for radiation protection purposes. Boundary identifiers may consist
of ropes, chains, color-coded adhesive tape, or other materials sufficient to delineate the
boundary of the area. Because color-coded adhesive tape applied to floors may not be highly
visible and provides no impediment to entry, its use as a boundary identifier should be limited
to counter-top applications or to use in conjunction with other boundary identifiers.
Boundary identifiers and physical barriers should be clearly visible from all directions and
various elevations to prevent inadvertent access to areas. For example, rope barriers should be
approximately 24 to 40 inches (60 to 100 cm) in height. Area monitoring should be used to
determine the adequacy of boundary placement.
Existing physical barriers, such as fences or walls, may be used as boundary identifiers if the
posting is adequate to prevent inadvertent access to the area. For example, a wall that could be
crossed by ladder could suffice as a boundary identifier, but would not prevent an individual
from entering an area; thus posting would be required.
Section 125
10 CFR 835.501(b) requires that the degree of personnel entry control be commensurate
with the existing and potential radiological hazards within the area. There may be site-specific
situations where the use of boundary identifiers (ropes, chains, fence, etc.) may not be
appropriate. These might include large areas with minimal radiological hazards. For these types
of situations the time and expense of erecting and maintaining boundary identifiers may not be
warranted. Site-specific controls such as a gate and posting on the access road, supplemented
by postings at suitable intervals around the area may be adequate to provide appropriate
warning and minimize inadvertent intrusions.
12.3 Controlled Areas
Controlled areas are established and posted to warn individuals that they are entering areas
in which radiological areas and/or RMAs exist. All radiological areas and RMAs lie within the
boundaries of controlled areas (although the boundaries may be contiguous).
Each entrance or access point to a controlled area shall be posted if that area contains
radioactive materials or radiation fields that require posting under 10 CFR 835.603
[10 CFR 835.602(a)]. The sign should contain wording equivalent to "CONTROLLED AREA";
however, the actual wording, color scheme, and sign may be selected by the contractor to avoid
conflict with local security requirements [10 CFR 835.602(b)]. In the event that the boundaries
of the controlled area are contiguous with those of radiological areas or RMAs, the area should
be posted with both the controlled area and radiological area/RMA postings.
A controlled area may incorporate one or more radiological areas and/or radioactive
material areas. Controlled area borders should not be contiguous with the site boundary.
12.4 Posting for Control of Exposure to External Radiation
DOE G 441.1-1C 153
5-19-08
10 CFR 835 establishes requirements for three areas that shall be posted to provide warning
of external radiation fields - radiation areas, high radiation areas, and very high radiation areas
[10 CFR 835.603(a-c)]. The need to post these areas is contingent upon two factors:
area accessibility, as discussed in Section 4.1.5 of this Guide; and
the radiation field intensity and duration, such that an individual’s dose may exceed the
specified threshold in one hour.
The posting thresholds established in 10 CFR 835 are based on the radiation field intensity
measured at a specified distance from the radiation source or from any surface penetrated by
the radiation (30 centimeters (12 inches) for radiation and high radiation areas and 100 cm (39
inches) for very high radiation areas). To ensure continuing compliance with the posting
requirements, a degree of conservatism should be established in the local posting requirements.
The desired degree of conservatism may be established by:
posting affected areas at an exposure rate lower than that specified in 10 CFR 835 (i.e.,
requiring area posting when an individual is likely to exceed a specified fraction of the
10 CFR 835 posting threshold); or
measuring the exposure rate at a distance less than that specified in 10 CFR 835; or
both of the above.
The degree of conservatism established in the posting regimen for external radiation
hazards should be adequate to address issues of monitoring equipment variability and likely
variations in area radiological conditions.
12.5 Posting for Control of Contamination
12.5.0 Removable and Airborne Radioactive Contamination
Section 126
10 CFR 835 establishes requirements for three areas that shall be posted to provide warning
of the presence of radioactive contamination - contamination area and high contamination area
postings for removable surface contamination and airborne radioactivity area postings for
airborne contamination [10 CFR 835.603(d-f)]. The need to post contamination areas and high
contamination areas is contingent upon two factors:
area accessibility as discussed in Section 4.1.5 of this Guide; and
the presence of removable surface contamination at levels exceeding the specified
removable surface contamination values (1x the values provided in Appendix D of
10 CFR 835 for contamination areas, 100 x these values for high contamination areas).
For detailed guidance on contamination measurements and the use of the 10 CFR 835
Appendix D surface contamination values, see Chapter 11 of this Guide.
The need to post airborne radioactivity areas is contingent upon three factors:
DOE G 441.1-1C 154
5-19-08
area accessibility, as discussed previously in this Guide;
the concentration of airborne radioactive material in the area; and
the extent to which individuals will be in the area during the area during a week.
10 CFR 835 establishes two criteria requiring posting of airborne radioactivity areas. The
first criterion, based upon airborne radioactive material concentrations exceeding the derived
air concentration (DAC) value(s) provided in Appendices A and C of 10 CFR 835 is absolute. That
is, if the airborne radioactive material concentration exceeds or is likely to exceed the specified
value(s), then the area shall be considered an airborne radioactivity area [10 CFR 835.2(a),
Airborne radioactivity area]. The second criterion, based upon individual exposure to airborne
radioactive material, allows consideration of individual stay times. Under this criterion, an area
shall be considered to be an airborne radioactivity area if an individual could receive an intake
exceeding 12 DAC-hours in a week (i.e., if an individual was present in the area for 40 hours
during a week and the airborne radioactive material concentration exceeded 30% of the
specified DAC value(s); 40 hours multiplied by >0.30 DAC exceeds 12 DAC-hours)
[10 CFR 835.2(a) Airborne radioactivity area]. Note that this criterion requires consideration of
individual exposures without the benefit of respiratory protective devices, whether or not such
devices are required for entry. The definition of the term “week” provided in 10 CFR 835.2(a)
does not specify a starting day. A starting day for the week should be selected and maintained
constant, to the extent practicable. It is not necessary to track individual exposures in
DAC-hours over rolling seven day periods to ensure compliance with the airborne radioactivity
area posting requirements of 10 CFR 835.603(d).
To ensure continuing compliance with the posting requirements for removable and airborne
radioactive contamination hazards, a degree of conservatism should be established in the local
posting requirements. The desired degree of conservatism may be established by posting
affected areas at surface contamination/airborne radioactivity concentrations lower than those
specified (i.e., requiring area posting at a specified fraction of the applicable 10 CFR 835
Appendix value). The degree of conservatism established in the posting regimen for radioactive
contamination hazards should be adequate to address issues of monitoring equipment
variability, sample collection efficiency variations, and likely variations in area radiological
conditions.
Section 127
12.5.1 Areas of Fixed Contamination
10 CFR 835 establishes specific requirements for areas that have total contamination levels
greater than the Appendix D values, but removable contamination levels less than the Appendix
D values. 10 CFR 835 establishes no requirements for posting of these areas (although
10 CFR 835 does establish requirements for marking these areas, which may be satisfied
through area posting, surface stenciling, or other appropriate means); however, it does establish
requirements for control of these areas. These requirements are discussed in Chapter 11 of this
Guide.
12.6 Radioactive Material Posting
10 CFR 835 requires that certain areas in which radioactive material is used, handled, or
DOE G 441.1-1C 155
5-19-08
stored be posted as radioactive material areas. The need to post RMAs is contingent upon two
factors:
area accessibility, as discussed in Section 12.2.4 of this Guide; and
the presence of items or containers of radioactive material in the area in quantities
exceeding the applicable Appendix E value(s).
The RMA posting exists as a means of supporting the 10 CFR 835.602(a) controlled area
maximum total effective dose expectation of 0.1 rem (0.001 Sv) in a year and provides an
alternative to labeling of multiple radioactive items or containers of radioactive material.
Therefore, 10 CFR 835.604 allows for the use of radioactive material labeling in lieu of RMA
posting and 10 CFR 835.606 likewise allows for the use of the RMA posting in lieu of individual
item or container labeling. The flexibility provided under these provisions permits individual
DOE activities to tailor their programs to meet specific needs.
Under conditions commonly associated with DOE activities, determinations of the quantities
of radioactive materials in an area are not as straightforward as determinations of radiation and
contamination levels and airborne radioactive material concentrations. The process of making
accurate determinations of the quantities of radioactive materials present in some areas may be
relatively cumbersome and time-consuming relative to the benefits obtained. Because of the
relatively low hazards present in RMAs, such a designation carries no additional regulatory
burden in terms of required entry controls. Reliable, good faith measures should be
implemented to assess the quantities of radioactive material present in all areas. Such
measures may include provisions for inventory tracking, exposure rate-to-activity,
concentration-to-activity, or contamination level-to-activity calculations, activation analyses, or
other technically-justified means for determining the activity of containers of radioactive
material or radioactive items. If there is doubt about whether or not the quantity of radioactive
material in an area exceeds the applicable Appendix E value(s), the area should be posted as a
radioactive material area to ensure compliance.
Another difficulty that may arise in identifying RMAs is in determining the location of the
RMA boundaries. While the boundaries of the radiological areas are readily identified through
the conduct of area monitoring, the boundaries of a radioactive material are more nebulous.
While it may be apparent that the quantity of radioactive material in a specified room or
enclosure does not exceed that level defining an RMA, the sum of the quantities of radioactive
material in a series of adjoining rooms or enclosures may exceed the threshold level. Such a
condition will necessarily lead to questions regarding whether or not an RMA exists and, if so,
regarding the logical RMA boundaries.
Section 128
Two acceptable approaches to defining the boundaries of RMAs are provided in this Guide;
the approach selected will be determined based predominantly on considerations of the nature
of the operations taking place, the education, training, and skills of the affected individuals, and
convenience. Under the first acceptable approach, the quantity of radioactive material in
individually identifiable rooms or enclosures may be considered. Note that the footnote to
Appendix E of 10 CFR 835 requires summing of the fractions of all radionuclides present in the
designated room or area. If there are multiple radioactive items or containers, then the activity
of each radionuclide present in all of the items and containers should be summed, divided by
DOE G 441.1-1C 156
5-19-08
the appropriate Appendix E value and then added to the similarly determined ratios for all other
radionuclides present to determine the activity-to-threshold value ratio for the designated room
or area. The postings, if necessary, should be erected at the individual room or enclosure entry
or access point(s) or, if there is a common access point to the rooms or enclosures, then the
posting may be erected at that point. Under the second acceptable approach, the quantity of
radioactive material present in a group of rooms or enclosures may be considered (using the
sum-of-the-fractions rule as discussed above) and the postings, if necessary, should be erected
at the common entry or access points. The decision regarding the appropriate location for the
posting(s) will be based largely on considerations of convenience (i.e., the establishment of
radiological hazard postings and associated entry controls at the common entrance point(s) may
disrupt or impede the activities of individuals who must enter the area or create the need for
additional radiation safety training for these individuals).
The use, handling, or storage of items or containers of radioactive material in outside areas
may pose special challenges in identifying areas requiring posting as RMAs, particularly when
the items or containers are spread over a wide area. These challenges result from the absence
of identifiable rooms or enclosures, thus making the identification of the identified “area”
problematic. To the extent practicable and consistent with ALARA principles, such items or
containers should be consolidated in a localized area to facilitate activity determinations,
posting, and control. Piles or areas of radioactive rubble or granular solids, such as soil or sand,
would not normally be considered “items” or “containers.” Therefore, areas in which the
radioactive material consists solely of such piles or areas would not be subject to posting as an
RMA. However, appropriate controls may be required to ensure compliance with other
requirements of 10 CFR 835, including the ALARA requirements of 10 CFR 835.101 and
835.1001, the dose limits of 10 CFR 835.207 and 835.208, and the controlled area maximum
dose expectation of 835.602(a).
12.7 Exceptions from Posting Requirements
Section 129
Accessible areas may be excepted from the radiological area and radioactive material area
posting requirements for periods of <8 continuous hours duration when the area is placed
under the observation and control of individuals who are knowledgeable of and empowered to
implement required access and exposure control measures [10 CFR 835.604(a)]. The
observing/controlling individual(s) should be stationed to provide line of sight surveillance of the
area boundaries and verbal warnings. For situations that require only simple access control
measures, such as entry prevention, a minimally-trained individual would suffice. For situations
that require more complicated access and exposure control measures, a radiological control
technician should be used. A sufficient number of individuals should be used to provide for
adequate access and exposure control.
The following accessible areas are excepted from the radioactive material area posting
requirements [10 CFR 835.604(b)]:
radiological areas posted in accordance with 10 CFR 835.603(a) - (f). In this case, the
radiological area posting provides adequate warning of the area hazards;
areas in which each item or container of radioactive material is clearly and adequately
labeled in accordance with Subpart G of 10 CFR 835 such that individuals entering the
DOE G 441.1-1C 157
5-19-08
area are made aware of the hazard. In this case, the radioactive material labels provide
adequate warning of the area hazards; and
areas in which the radioactive material of concern consists solely of structures or
installed components which have been activated (i.e., such as by being exposed to
neutron radiation or particles produced in an accelerator).
Areas containing only packages received from transportation need not be posted in
accordance with 10 CFR 835.603 until the packages are monitored in accordance with
10 CFR 835.405 [10 CFR 835.604(c)]. For ALARA purposes, the time between package receipt
and monitoring should be minimized.
Even though certain areas may be excepted from posting in accordance with the conditions
provided in 10 CFR 835, appropriate controls should be established over these areas as
necessary to limit exposures consistent with the ALARA controls required under
10 CFR 835.1001. Decisions regarding the omission of radiological hazard postings should be
made in full consideration of the information provided in Section 12.2 of this Guide.
The exceptions discussed above apply only to radiological area and/or radioactive material
area posting requirements and do not apply to the entry control requirements established in
10 CFR 835.501 and 10 CFR 835.502 or to the radiation safety training requirements established
in 10 CFR 835.901. Decisions regarding omission of postings should be made in full
consideration of the guidance provided in Section 12.2 of this Guide.
12.8 Radioactive Material Labeling
12.8.0 Radioactive Material Labeling
Each item or container of radioactive material shall be labeled (10 CFR 835.605). The label
shall contain the standard radiation warning trefoil and the words "CAUTION, RADIOACTIVE
MATERIAL" or "DANGER, RADIOACTIVE MATERIAL" (10 CFR 835.605). The label shall also
provide sufficient information to permit individuals handling or using the containers or working
in the vicinity of the containers to take precautions to avoid or minimize exposures
(10 CFR 835.605).
The following information should be included on the labels, as appropriate:
Section 130
radiological hazard (e.g., radiation and/or contamination levels);
an estimate of the quantity of radioactivity;
radioisotope(s) and activity;
dates monitored;
any special handling instructions necessary to permit individuals to implement
appropriate protective measures;
name of the individual performing the monitoring; and
DOE G 441.1-1C 158
5-19-08
a description of the material, as appropriate.
If the item is too small to accommodate a label, then the label should be applied to the
container or storage location.
The label shall be clearly visible on the item or container (10 CFR 835.605). If a label applied
to the items will not be clearly visible, then the label should be placed on the exterior of
containers holding the radioactive material.
12.8.1 Exceptions from Labeling Requirements
Containers and items are excepted from the radioactive material labeling requirements of
10 CFR 835.605 under any one of the following circumstances:
the items or containers are used, handled, or stored in areas posted and controlled in
accordance with Subpart G of 10 CFR 835 and sufficient information is provided to
permit individuals to take appropriate protective actions [10 CFR 835.606(a)(1)]. This
information may be provided on or in conjunction with the area postings, radiation
safety training, written procedures, controlling work authorization for that area, or
other suitable means.
the quantity of radioactive material is less than one tenth of the values specified in
Appendix E of 10 CFR 835 and less than 0.1 Ci [10 CFR 835.606(a)(2)]. For containers
that contain numerous items of radioactive material, the determination of the need for
labeling should be based upon the sum of the activities of the individual items. Section
4.5 of this Guide provides guidance on determining the activity of radioactive items and
containers of radioactive material and on determining the sum of the fractions of the
activities of the items in question.
the items or containers are packaged and labeled in accordance with Department of
Transportation regulations or corresponding DOE Orders [10 CFR 835.606(a)(3)]. When
such labels are used as an alternative to the labeling required by 10 CFR 835, measures
should be implemented to ensure that affected individuals are familiar with the labels
and the hazards and precautions associated with the labeled materials.
the items or containers are inaccessible or accessible only to individuals authorized to
handle or use them, or to work in the vicinity [10 CFR 835.606(a)(4)]. In such situations,
the individuals should be trained in accordance with 10 CFR 835.901(b) and
knowledgeable of the types and quantities of radioactive material present in the area.
Chapter 14 of this Guide provides guidance on developing appropriate radiation safety
training programs.
the items or containers are installed in manufacturing or process equipment, such as
reactor components, piping, and tanks [10 CFR 835.606(a)(5)].
the radioactive material consists solely of nuclear weapons or their components
[10 CFR 835.606(a)(6)].
DOE G 441.1-1C 159
5-19-08
Even though items and containers of radioactive material may be excepted from labeling in
accordance with the conditions provided in 10 CFR 835, appropriate controls should be
established over the storage, movement, and use of unlabeled items and containers as
necessary to limit exposures consistent with the ALARA controls required under
10 CFR 835.1001. Decisions regarding the omission of radioactive material labels should be
made in full consideration of the information provided in Section 12.2 of this Guide.
Section 131
Although 10 CFR 835.606(a)(1) provides a labeling exception for radioactive material that is
used, handled, or stored in areas posted and controlled in accordance with Subpart G of
10 CFR 835, caution should be exercised in applying this exception to ensure that the
radiological area posting or associated information will be sufficient to inform affected
individuals of the area hazards and required protective actions. For example, a trained
individual’s response to a “Contamination Area” posting (i.e., protective clothing, personnel
frisking) may not be sufficient to protect that individual from the hazards associated with an
unlabeled radioactive item or container in the area. Similarly, a trained individual’s response to
a “Radiation Area” posting may not be sufficient to protect that individual from the hazards
arising from the opening of a wrapped, but unlabeled, contaminated item in that area. In such
cases, the exception provided in 10 CFR 835.606(a)(1) requires that sufficient information be
provided to permit individuals to take appropriate protective actions. As discussed above, this
information may be provided in conjunction with the area postings, radiation safety training,
written procedures, controlling work authorizations or other suitable means.
DOE G 441.1-1C 160
5-19-08
Appendix 12.A – Standard Radiation Warning Trefoil
The standard radiation warning trefoil should be proportioned as shown below (ANSI N2.1). The
trefoil color shall be either magenta or black on a yellow background [10 CFR 835.601(a)].
DOE G 441.1-1C 161
5-19-08
13.0 OCCUPATIONAL RADIATION PROTECTION RECORD-KEEPING
AND REPORTING
This Guide provides instructions for implementing a program that will meet DOE
requirements for generating, administering, and retaining occupational radiation protection
records and reports. Complete and accurate radiation protection records are necessary to:
provide information used to protect individuals from radiation exposure;
evaluate the effectiveness of the radiation protection program;
demonstrate compliance with regulations and requirements; and
defend the radiation protection program against unwarranted litigation.
Supporting guidance useful in developing and implementing occupational radiation
protection record-keeping programs is provided in N13.6, Practice for Radiation Exposure
Records Systems (ANSI/HPS 1999) and NCRP Report No. 114, Maintaining Radiation Protection
Records (NCRP 1992). These documents should be used in concert with this Guide and
10 CFR 835 because they may not address every DOE-specific occupational radiation protection
record-keeping requirement.
The RCS provides detailed information concerning various aspects of records management
programs, including record-keeping standards. The RCS provides detailed technical guidance
concerning employee records, radiological control procedures, area monitoring, and
instrumentation and control. The information provided by the RCS, used in conjunction with
this Guide, will assure that a records management program will meet the record-keeping
requirements and relevant DOE contractual requirements.
13.1 Implementation Guidance
This chapter describes acceptable methods for conducting a functional and effective
program for generating and administering occupational radiation protection program records
and reports. An acceptable radiation protection records program should:
Section 132
be implemented by individuals who are knowledgeable of the record-keeping
requirements. Guidance on appropriate education, training, and skills is provided in the
RCS and in Chapter 3 of this Guide;
have documented policies and procedures for record and report generation and
administration;
demonstrate accuracy, completeness, timely record and report generation, and retrieval
capability; and
maintain documents that are traceable, trackable, verifiable, and retrievable, to
substantiate historical events.
DOE G 441.1-1C 162
5-19-08
Unless otherwise specified, all radiation protection program records and reports shall use
the special radiological units of curie, rad, roentgen, and rem, including their multiples and
subunits or other conventional units, such as, dpm, dpm/100 cm2 or mass units (10 CFR 835.4).
Units such as counts per minute should not be used without the additional detailing of
supplemental information (such as counting efficiencies) needed to evaluate the units. The
international system of units may be used to facilitate calculations (e.g., Becquerel, Gray,
Sievert) but final records and reports should always be provided in the required units.
13.2 Records to be Generated and Maintained
Required records include individual monitoring and dose, workplace monitoring and control,
and administrative records
13.2.0 Individual Monitoring and Dose Records
10 CFR 835.702(a) and (b) require maintenance of monitoring results to document doses
received by:
all individuals monitored pursuant to 10 CFR 835.402;
all individuals who received unplanned doses exceeding the monitoring threshold; all
individuals who receive doses as a result of planned special exposures and authorized
emergency exposures; and
all individuals for whom monitoring was provided, but not required under
10 CFR 835.402.
Individual monitoring records shall be sufficient to evaluate compliance with the regulatory
provisions for internal and external exposures [10 CFR 835.702(c)(1)]. An acceptable approach
for meeting this requirement is for a site to maintain records of all occupational doses received
during the year for any monitored (internal or external exposure) individual at that site. The
records would include doses received at other sites prior to being monitored at the site in
question. These records shall be sufficient to provide dose information necessary to complete
mandated reports to individuals [10 CFR 835.702(c)(2)].
10 CFR 835.702(d) requires that documentation of all occupational doses received during
the current year be obtained to assure individuals do not exceed the dose limits provided in
10 CFR 835.202(a). A written estimate signed by the individual may be accepted if complete
records documenting previous occupational dose during the year cannot be obtained.
10 CFR 835.702(e) requires that reasonable efforts be made to obtain complete records of the
prior year’s occupational internal and external doses. An acceptable approach to obtain such
records includes making at least three written requests to each prior employer. Doses from
planned special exposures conducted in accordance with 10 CFR 835.204 and emergency
exposures authorized in accordance with 10 CFR 835.1302(d) are not included when
determining compliance with the occupational dose limits.
DOE G 441.1-1C 163
5-19-08
Section 133
Individual monitoring records identified with a specific individual shall be readily available to
that individual [10 CFR 835.702(f)]. Individuals should be informed as to how they may access
their records. Guidance on reports to individuals is provided in section 13.3.0 of this Guide. See
Section 13.8 for Privacy Act considerations.
Frequently, for individuals who had previously been monitored during the year, the process
of obtaining exposure records may be too time consuming to allow the individual to commence
scheduled work. In these situations, an acceptable approach would be to obtain a written
estimate of the current year dose from the individual and implement appropriate administrative
control levels for these individuals. This approach will allow these individuals to receive
occupational exposure during the time period when efforts are being made to obtain complete
records documenting previous occupational dose during the year. Administrative control levels
implemented for this situation should consider the individuals’ current year work history and
the potential magnitude of occupational dose received (e.g., had they been involved in any
radiological incidents, are they knowledgeable of the radiological conditions in areas where they
worked, do they have any estimated exposure information from self reading dosimeters).
For members of the public being monitored per 10 CFR 835.402 and granted access to
Controlled Areas, a written statement that they had not been monitored for, or received
exposure to, ionizing radiation in a Controlled Area during the current year would typically be
sufficient to ensure compliance with the dose limits in 10 CFR 835 subpart C. If a member of the
public were to indicate that they had been monitored for or received exposure to ionizing
radiation in a Controlled Area and could not provide adequate documentation of any
subsequent exposure, implementation of the above guidance for occupational exposures would
be an acceptable approach (i.e., a written estimate and appropriate administrative controls).
Each individual’s dose records should be identified by the following information, as
appropriate:
full name;
social security number, employee or other unique identifying number;
date of birth;
sex;
employment status;
occupation code;
facility type or building number; and
organization code.
13.2.0.0 Internal Doses
DOE G 441.1-1C 164
5-19-08
10 CFR 835.702(c)(4) requires that individual internal dose records include the committed
effective dose, the committed equivalent dose to any organ or tissue of concern (e.g., any organ
or tissue receiving a dose approaching the threshold for required monitoring), and the identity
of the radionuclide(s). These records should also typically include the estimated intake to
facilitate future reassessments of doses [see 10 CFR 835.702(g)]; however, the estimated intake
is not needed for determination of dose from certain forms of some radionuclides, such as
tritiated water vapor or elemental tritium. In these cases, the intake need not be recorded. In
cases where intakes are detected or confirmed in a year subsequent to the year of the intake,
the committed effective dose should be attributed to the known or assumed year of the intake,
and all records and reports for that year should be amended as appropriate. Records of the
results of air monitoring when used to determine individual occupational dose shall be
documented and maintained [10 CFR 835.703(b)].
Section 134
In the 2007 amendment to 10 CFR 835 DOE made a revision to allow some relief from the
need to perform a dose assessment and to record very small internal doses. Recording of
internal dose (committed effective dose or committed equivalent dose) is not required for any
result estimated to correspond to an individual receiving less than 0.01 rem (0.1 mSv)
committed effective dose. The bioassay or air monitoring result used to make the estimate shall
be maintained in accordance with § 835.703(b) and the unrecorded internal dose estimated for
any individual in a year shall not exceed the applicable monitoring threshold at § 835.402(c) [10
CFR 835.702(b)].
This relief will be most useful for internal exposure assessments where it is possible to
detect and assess doses at a small fraction of the internal dose monitoring threshold (e.g.,
tritium or certain uranium exposures). The relief most easily can be achieved through the
development and use of default values, below which no further dose assessment or recording
would be required. However, the bioassay or air monitoring data used in making the
assessment must still be maintained. This practice is consistent with nationally accepted
standards as discussed in “American National Standard for Design of Internal Dosimetry
Programs” (ANSI/HPS 2000).
Internal dosimetry technical basis documentation should be developed and should include
technical methods, supporting evidence, and reference information used to provide the
technical foundation for the internal dosimetry program. The technical basis documentation
should be controlled and retained as a radiation protection program record. Guidance for
determining individual internal doses is provided in Chapter 5 of this Guide.
Special radiobioassay measurements should be performed following suspected or confirmed
intakes. The extent of the investigation and the number and frequency of these radiobioassays
should be determined and documented on an individual, case-specific basis, taking into account
the potential magnitude of the intake, the effective clearance half-time, the health of the
worker, and the number of measurements needed to evaluate the internal dose.
Additional guidance for recording and reporting internal doses and related information is
provided in Section 9, of DOE-STD-1121-2008. Record-keeping and reporting of internal doses
and related information should be in accordance with this standard.
DOE G 441.1-1C 165
5-19-08
13.2.0.1 External Doses
10 CFR 835.702(c)(3) requires that individual external dose records include the effective
dose, equivalent dose to the lens of the eye, equivalent dose to the skin and the extremities.
When the lens of the eye is not specifically monitored, the skin dose may be used to determine
regulatory compliance. When the extremities are not specifically monitored, the dose to the
skin of the whole body may be used for determination of regulatory compliance.
When the extremities are specifically monitored, the dose should be recorded as equivalent
dose to 1) hands and arms below the elbows and, separately, 2) feet and legs below the knees.
When both left and right extremities are monitored, the higher equivalent dose should be
recorded.
When an individual is provided multiple dosimeters, the dose measured by the highest
responding dosimeter on the whole body should be assigned as the whole body dose of record
(see Chapter 6 for special considerations). When multiple dosimeters are employed more than
Section 135
once during the year, dosimeter results may be summed by location and the highest total
assigned as the whole body dose of record. However, sufficient records should exist to
demonstrate that the dose to portions of the whole body between the monitoring locations did
not exceed that recorded for the monitoring location.
When personnel dosimeter measurements are not available, a dose evaluation should be
performed for that period, if necessary. These estimated or assigned doses shall be clearly
recorded and maintained as such [10 CFR 835.702(a) and (g)]. When area monitoring results are
used to estimate individual dose, the results of surveys, measurements and calculations used to
determine individual occupational exposure from external sources shall be recorded
[10 CFR 835.703(b)].
A technical basis document should be developed for the external dosimetry program to
provide (or provide reference to) the regulatory, scientific, and technical foundation of the
program. The technical basis document should be handled as a controlled document and
retained as a RPP record. Guidance to determine individual external doses is provided in
Chapter 6.
The number of fixed nuclear accident dosimeter units, their locations, the effect of
intervening shielding, and an analysis demonstrating these performance criteria should be
documented in the technical basis document.
13.2.0.2 Summation of Internal and External Doses
10 CFR 835.702(c)(5) requires that individual dose records include the total effective dose,
for any organ or tissue assigned an internal dose during the year, the sum of the whole body
equivalent dose from external exposures and the committed equivalent dose to that organ or
tissue, and the cumulative total effective dose (see guidance regarding lifetime occupational
DOE G 441.1-1C 166
5-19-08
dose, below). When only internal or external dose has been monitored, then the summed doses
will be equivalent to the component of the dose (internal or external) that has been monitored.
13.2.0.3 Lifetime Occupational Dose
For each radiological worker monitored in accordance with 10 CFR 835.402 [i.e., the
radiological worker’s dose is expected to exceed the monitoring threshold(s)], efforts shall be
made to obtain records of prior years’ occupational dose *10 CFR 835.702(e)]. Efforts to obtain
such records should include at least three written requests to each prior employer. If the prior
employer is non-responsive or complete records cannot be obtained for any reason, a written
estimate signed by the worker may be accepted.
10 CFR 835.204(b) requires that an individual's dose from all previous planned special
exposures and all doses in excess of the occupational dose limits be determined prior to
requesting the individual to participate in a planned special exposure. For this situation,
estimates of dose from previous planned special exposures and estimates of doses in excess of
the limits are not permitted for meeting the requirements of 10 CFR 835.204(b). The records of
prior years exposure required by 10 CFR 835.204(b) need only be obtained for radiological
workers who are chosen and elect to participate in a planned special exposure.
On the basis of available dose records and written estimates, records of each radiological
worker’s cumulative total effective dose shall be maintained [10 CFR 835.702(c)(5)(iii)] and
efforts should be made to determine the lifetime occupational dose of each radiological worker
who is monitored in accordance with 10 CFR 835.402.
Section 136
The adoption of the revised dosimetric quantities and units in the 2007 amendment to 10
CFR 835 requires summation of dosimetric values from pre and post 2007 10 CFR 835
amendment. Similar to DOE’s approach to applying the rule to individuals who conduct multiple
activities involving both activities under 10 CFR 835.1(b)(1) and excluded activities (e.g.,
activities involving NRC licensed activities), for the purpose of compliance with 10 CFR
835.702(c)(5)(iii), DOE considers the following terms to be equivalent:
Dosimetric Term as Defined by Excluded
Activity Cognizant Regulator DOE Amended Dosimetric Term
Committed effective dose equivalent
Committed effective dose
Committed dose equivalent
Committed equivalent dose
Cumulative total effective dose equivalent
Cumulative total effective dose
Deep dose equivalent
Equivalent dose to the whole body
Dose equivalent
Equivalent dose
DOE G 441.1-1C 167
5-19-08
Effective dose equivalent
Effective dose
Lens of the eye dose equivalent
Equivalent dose to the lens of the eye
Quality factor
Radiation weighting factor
Shallow dose equivalent
Equivalent dose to the skin or
Equivalent dose to any extremity
Weighting factor
Tissue weighting factor
Total effective dose equivalent
Total effective dose
The contribution to an individual’s lifetime occupational dose since January 1, 1989,
should be recorded as CTED. DOE did not require determination of CEDE or committed
effective dose prior to January 1, 1989; consequently, annual TEDE or TED information may
not be available. While determination of CEDE or committed effective dose for internal
exposures received prior to January 1, 1989, is recommended to improve the consistency of
available information, such conversion may not be possible due to resource or data
limitations. If conversion to committed effective dose is not possible or practical, all
available dose and intake data should be recorded.
DOE G 441.1-1C 168
5-19-08
13.2.0.4 Non-Uniform Exposure to the Skin
Non-uniform exposures to the skin (such as from non-penetrating radiation or skin
contamination) shall be recorded in the individual’s dose record and included in the dose
equivalent to the skin for the year if the area of skin exposure equals or exceeds 10 cm2 and
the dose equals or exceeds 1 rem (0.01 Sv) [10 CFR 835.205(b)(1) and (2) and
10 CFR 835.702(b)]. If the dose does not exceed 1 rem, the dose may be included in the
individual’s dose records as equivalent dose to the skin, but in any case, records of the dose
assessment should be maintained. If the dose exceeds 1 rem (0.01 Sv) and the area of the skin
exposure is less than 10 cm2, the dose shall be recorded as a special entry in the individual's
dose record, but shall not be included in the equivalent dose to the skin for the year
[10 CFR 835.205(b)(3)].
If the exposure to the skin is to the hands or arms below the elbows or feet and legs
below the knees, the dose should be included in the equivalent dose to the extremity for the
year. Otherwise the dose should be recorded as equivalent dose to the skin.
13.2.0.5 Planned Special Exposures (PSEs)
The dose resulting from PSEs shall not be considered in controlling future occupational dose
to the individual under 10 CFR 835.202(a), but shall be included in the records and reports
required by 10 CFR 835 [10 CFR 835.204(f)]. Doses resulting from PSEs should be included in the
determination of the individual’s yearly doses, CTED, and lifetime dose. For the purpose of
compliance with the planned special exposure requirements in 10 CFR 835.204, DOE considers
the terms as listed in the table in section 13.2.0.3 to be equivalent.
Section 137
These doses are not considered in the individual’s yearly dose when demonstrating
compliance with the dose limits in 10 CFR 835.202(a). Doses resulting from PSEs should be
recorded and treated separately, even if the dose does not exceed the value of the dose limits
provided in 10 CFR 835.202(a).
13.2.0.6 Doses Resulting from Emergency or Accidental Exposures
The dose received from an authorized emergency exposure or unplanned exposure
exceeding the applicable monitoring threshold shall be documented in each individual's dose
record [10 CFR 835.702(a)]. Doses resulting from accidents shall be included in assessments
with compliance with the dose limits provided in 10 CFR 835 [10 CFR 835.2(a), Occupational
dose]. Doses resulting from authorized emergency exposures shall not be considered in
assessments of compliance with the regulatory dose limits and should not be considered in
controlling the affected individual’s future routine occupational exposure under
10 CFR 835.202(a).
DOE G 441.1-1C 169
5-19-08
13.2.0.7 Records of Embryo/Fetus Dose and Declared Pregnant Workers
Records pertaining to the embryo/fetus and the declared pregnant worker shall include:
the equivalent dose to the embryo/fetus of a declared pregnant worker
[10 CFR 835.702(c)(6)];
the written declarations of pregnancy for the individual, including estimated
conception date [10 CFR 835.704(d)]; and
the written revocations of declarations of pregnancy for the individual, if any
[10 CFR 835.704(d)].
Other records that should be maintained include:
any work restrictions imposed;
any counseling performed;
monitoring performed (e.g., dosimeter placement, bioassay frequency, supporting
workplace monitoring); and
records of reports provided.
Guidance for determining dose to the embryo/fetus may be found in Chapter 8 of this
Guide.
13.2.0.8 Individual Monitoring Program Records
Data that are necessary to support or recalculate doses at a later date shall be retained
[10 CFR 835.702(g)]. Records that should be retained include the following:
the monitoring program technical basis documents and any changes;
decisions to include or exclude program participants and the monitoring results
(individual and workplace) supporting these decisions;
calculations of dose based on workplace monitoring data, when performed;
sample collection dates, times, volumes, analysis results, and dose assessment;
models used (i.e., individual specific parameters versus Reference Man, etc.);
records of program accreditation, exceptions from accreditation, or other approvals;
contractual arrangements for contractor dosimetry services;
program cross-checks;
DOE G 441.1-1C 170
5-19-08
instrument capability, calibration and functional tests;
workplace monitoring results;
results of trend analyses;
monitoring device issue, return, readings, dose assessment, inter-device agreement,
and investigations;
dosimeter relocation or multi-badge issue, as appropriate;
field correction factors used;
calculations of external dose from airborne radionuclides and surface, skin, or clothing
contamination; and
employee radiological safety concerns that have been formally investigated.
13.2.0.9 Equipment Capabilities
Section 138
The capabilities of radiation monitoring instruments, including individually worn
dosimeters, should be documented. Recorded information should include the identification,
description, and functional specifications and the results and date of any acceptance or
performance tests that are performed to demonstrate equipment capabilities with regard to
sensitivity, range, and energy dependence (ANSI/HPS N13.6). Additionally, records of
computer program capabilities, limitations, and validation and verification should be
maintained.
13.2.1 Monitoring and Workplace Records
This chapter applies to the records that may be required to establish the conditions under
which individuals were exposed to radiation or radioactive material. These records
supplement the individual dose records that are based on individual monitoring. In some
cases, workplace records provide the only means for estimating individual doses. These
records are also helpful in assessing the overall quality and effectiveness of the radiation
protection program. ANSI/HPS N13.49-2001, Performance and Documentation of Radiological
Surveys, provides guidance on documentation of radiological surveys (ANSI/HPS 2001b). The
following information shall be documented and maintained:
results of monitoring for radiation and radioactive material as required by Subparts E
and L of 10 CFR 835 [except for that monitoring required by 10 CFR 835.1102(d)]
[10 CFR 835.703(a)];
results of monitoring used to determine individual occupational dose from external
and internal sources [10 CFR 835.703(b)];
results of monitoring for the release and control of material and equipment as
required by 10 CFR 835.1101 [10 CFR 835.703(c)]; and
DOE G 441.1-1C 171
5-19-08
results of maintenance and calibration performed on instruments and equipment as
required by 10 CFR 835.401(b) [10 CFR 835.703(d)].
13.2.1.0 Radiation Safety Analysis and Evaluation Records
Reports of initial evaluations and periodic re-evaluations of the long-term radiation
protection aspects of a work area, equipment, or specific location should be retained. These
evaluations may be used to supplement the monitoring that is required for transient conditions.
The details and content of the evaluation reports depend upon the purpose of the report, the
nature of the operation, and the associated potential hazards. The evaluation report should
include or make reference to:
descriptions of the facility, equipment, and nature of the operation, including
modifications to any facilities, equipment or operations;
design criteria for systems, components, and structures;
identification of potential hazards, including the types and magnitude of the sources of
radiation allowed in the facility, and the nature and magnitude of those found during
the review;
training and experience requirements for individuals employed in the operation;
probability of occurrence and predicted consequences of hazards expressed in
quantitative terms where feasible;
engineered controls and administrative controls provided to prevent or mitigate
potential accidents;
the scope of the periodic surveillance program and the radiation instrumentation
required;
the appropriate emergency actions to be taken in the event of accidents;
operational limitations; and
identification of the individual(s) who made the evaluation.
DOE G 441.1-1C 172
5-19-08
13.2.1.1 Work Authorizations
Written authorizations shall be required to control entry into and perform work within
Section 139
radiological areas [10 CFR 835.501(d)]. Records of these authorizations shall be maintained
[10 CFR 835.701(a)] and should include the information provided in Chapter 3, Part 2 of the RCS
pertaining to preparation of RWPs. The RCS also provides guidance regarding the preparation
and use of written work authorizations, such as RWPs and technical work documents. The
supporting records, such as monitoring records used to prepare work authorizations, should be
linked so that reference can be made to the data when required.
13.2.1.2 Area and Material/Equipment Monitoring Records
Results of area and material/equipment monitoring activities should be recorded on
appropriate standard forms (to the extent practicable) and include the following common
elements:
date, time, and purpose of the monitoring activity;
general and specific location monitored;
name and signature of the individual performing the monitoring;
pertinent information needed to interpret the monitoring results;
reference to a specific work authorization if the monitoring is performed to support the
authorization;
model and serial number of the instrument (locations of fixed instruments may be used
as identifiers where the model and serial numbers are not available).
The value of some types of area monitoring is enhanced by the use of sketches of building,
room, or equipment layouts to clearly define the areas monitored and results observed.
Monitoring of certain items however, may be adequately documented by simply describing the
item and its radiological status. Additional records that should be maintained include:
the technical bases for assumptions on which the monitoring program is based,
including radionuclide inventories, system functions, specific activities involving
radioactive materials, and air flow studies;
records of alarms and alarm responses;
placement of fixed dosimeters and nuclear accident dosimeters;
results of samples, including location, time, occupancy, volume, radionuclides,
concentrations, counting equipment data, etc.;
field analysis and follow-up analysis results;
DOE G 441.1-1C 173
5-19-08
pertinent facility conditions when monitoring is performed;
corrective actions resulting from performance of monitoring;
personnel and area decontamination records; and
times and dates as necessary to assess compliance with time sensitive requirements,
such as receipt of material from radioactive material transportation.
Many facilities employ area monitoring instrumentation that records on charts the radiation
levels in work locations. The record on the chart should include, or be directly linked to, the
information described in ANSI/HPS N13.6.
See Chapter 7, Part 5 of the RCS for additional guidance concerning radiation and
contamination monitoring records.
13.2.1.3 Airborne Radioactivity Monitoring Records
In addition to the guidance provided in section 4.1.2.3, the results of monitoring for
airborne radioactivity shall be documented and maintained [10 CFR 835.703(a)] and should
include:
measured airborne radioactivity concentrations in general areas and breathing zones;
supporting parameters, including collection efficiency, flow rate, duration of sampling,
correction factors, and filter medium;
individual DAC-hour calculations, when performed; and
linkage of air sample results to individuals in the area, when monitoring results will be
used for individual dose assessment or exposure control.
Section 140
Airborne monitoring program records should include:
the technical basis for alarm set points for real-time monitors;
the technical basis for air sampling and real-time air monitoring equipment selection,
placement, and operation; and
any adjustments to DACs.
When air monitors with chart recorders are used, the following additional information
should be recorded on the chart or be directly linked to the chart:
type of instrument, e.g., fixed filter or moving tape;
tape and chart speed;
DOE G 441.1-1C 174
5-19-08
identity of scale or range of operation; and
specific calibration and relationship between the chart divisions and the concentration
of the airborne radioactive material depending on the tape speed and flow rate of a
moving filter unit or the flow rate of a fixed filter unit.
13.2.1.4 Records of Releases of Materials and Equipment from Radiological Areas
Records of monitoring for the release and control of material and equipment as required by
10 CFR 835.1101 shall be documented and maintained [10 CFR 835.703(c)]. These records
should contain the following:
description of the material or equipment;
date on which the material or equipment was monitored;
type and identification number of the survey instrument used;
results of the monitoring; and
identification of the individual(s) who performed the monitoring.
When the material to be released consists of many small or identical items, then the
material may be described in a general manner (e.g., “box of tools” or “pallet of lumber”). Large
or unique items should be specifically identified by identification number, if available.
13.2.2 Administrative Records
This section applies to the administrative records that describe various elements of the
radiation protection program.
The following records shall be maintained:
training records, as necessary, to demonstrate compliance with 10 CFR 835.901
[10 CFR 835.704(a)].
actions taken to maintain occupational exposures ALARA, including the actions
required for this purpose by 10 CFR 835.101, as well as facility design and control
actions required by Subpart K of 10 CFR 835 [10 CFR 835.704(b)];
results of internal audits and other reviews of program content and implementation
[10 CFR 835.704(c)]; and
changes in equipment, techniques, and procedures used for monitoring
[10 CFR 835.704(e)].
13.2.2.0 Radiation Safety Training
DOE G 441.1-1C 175
5-19-08
Records of radiation safety training are essential to show that each individual received
appropriate training. Records shall be maintained, as necessary, to demonstrate compliance
with 10 CFR 835.901 [10 CFR 835.704(a)]. These records should include documentation of
on-the-job and practical factor training as well as formal classroom training. Training and
qualifications records should be readily available to first-line supervision and management to aid
in work assignment.
Course-related items, including all revisions and dates used, should be retained include the
following:
the course title and outline or syllabus;
copies of handouts distributed to the attendees;
instructor's manuals and lesson plans;
copies or transcriptions of any video and audio training that is provided;
attendance sheets showing dates, attendees’ names and signatures, and names of
instructors;
documentation of job-specific training, such as radiological procedures, RWP procedure,
and special training requirements, pre-job briefings, and mockup training;
Section 141
documentation of exceptions to training requirements and extension of qualifications;
on-the-job training records;
records demonstrating the practical application of a learned skill;
copies of any certificates issued;
the basis for decisions to alter standard course content for specific candidates due to
prior education, experience, escort provided, etc.;
program accreditation records;
effectiveness evaluations and actions in response;
training/briefings provided between full training cycles;
basis for site/facility-specific materials;
individual tests, or if a test bank is used, the test series number and a copy of the
bank and the series code; and
confirmation of satisfactory completion of training.
DOE G 441.1-1C 176
5-19-08
If training or qualifications received at other locations are to be accepted in place of
training, documentation should be obtained and placed in the individuals’ training
records. Additional guidance on training records may be found in the RCS.
13.2.2.1 ALARA Records
Actions taken to maintain occupational exposures ALARA, including actions required
by the RPP, as well as facility design and control actions shall be documented
[10 CFR 835.704(b)]. As discussed in Chapter 4, this documentation includes formal plans
and measures for applying the ALARA process to occupational doses. This documentation
should include the following, to the extent the programmatic elements are used in the
specific program:
the ALARA committee charter, membership, and meeting minutes;
implementation of administrative control levels;
forms demonstrating approval to exceed administrative control levels;
dose, intake, and personnel contamination investigation forms;
radiological performance goals, status, and annual performance records;
pre-job briefing, with content and attendance;
post-job reviews, with dose estimates, and actual doses received;
collective doses received by the total facility, by specific work groups, and for
specific high dose jobs;
annual or special ALARA reports, e.g., dose/dosimetry trend data;
records of ALARA design review;
results of optimization analysis;
work planning, including procedures and technical work documents;
work authorizations, including RWPs;
records of ALARA job/experiment review; and
ALARA training records.
Formally documented optimization methodologies should be developed for ALARA
reviews and decisions on implementation of ALARA efforts. The degree of formality
should be commensurate with the radioactive material contamination and dose potential.
Chapter 1 of the RCS provides additional guidance on the degree of program formality.
DOE G 441.1-1C 177
5-19-08
All documents and legal records used to demonstrate compliance with the
requirements for an ALARA program should be reviewed and approved by supervisory or
line management.
13.2.2.2 Facility Design
Records necessary to evaluate compliance with the design and control requirements
of Subpart K of 10 CFR 835 shall be maintained [10 CFR 835.701(a)]. These records should
include the following:
the design and control considerations documenting the rationale for selecting
physical controls or administrative controls, when necessary;
the design criteria used and technical basis for these criteria;
the optimization methodology employed for facility design and modifications;
the technical basis for design objectives;
Section 142
the results of design reviews, including features that facilitate operations,
maintenance, decontamination, and decommissioning; and
the technical basis for workplace controls used.
13.2.2.3 Entry and Access Control Records
Records necessary to evaluate compliance with 10 CFR 835.501 shall be maintained
[10 CFR 835.701(a)]. These records should include the following:
system/device design, test criteria, and data;
system/device failure and corrective actions;
assessments of adequacy for actual and design conditions; and
administrative controls used in lieu of physical controls.
13.2.2.4 Sealed Radioactive Sources
Records shall be maintained as necessary to evaluate compliance with the requirements of
10 CFR 835.1201 and 10 CFR 835.1202 for sealed radioactive source control, inventory, and
source leak tests [10 CFR 835.704(f)].
Records that should be maintained include:
source acquisition, monitoring, leak tests, inventories, loss;
storage and use locations;
DOE G 441.1-1C 178
5-19-08
investigations conducted; and
exceptions taken due to source inaccessibility or sources taken out of service.
See Chapter 7, Part 5 of the RCS for additional guidance concerning sealed radioactive
source leak tests and inventories records.
13.2.2.5 Radiation Protection Program, Policies and Procedures
Documentation supplementing the approved RPP should be developed and maintained to
demonstrate that an RPP can be effectively managed and administered to achieve compliance
with 10 CFR 835. This documentation should include a site radiological control manual, detailed
implementing procedures, appropriate management policy statements, and technical basis
documentation. While this documentation need not be part of the RPP, it should be clearly
linked to the compliance commitments contained in the RPP. Records of this documentation
should be recorded in accordance with ANSI/HPS N13.6. All policies and procedures should
have effective dates.
Documentation of changes made to the RPP without prior DOE approval should include the
rationale applied to such changes and should be retained for future reference and
demonstration of compliance.
Programmatic documentation should be developed to document the organizational and
administrative aspects of the RPP.
Records shall be maintained, as necessary, to demonstrate that individuals who are
responsible for the development and implementation of measures necessary to ensure
compliance with 10 CFR 835 have the appropriate education training, and skills to execute these
responsibilities [10 CFR 835.103 and 701(a)]. These records should include records of the
training provided in accordance with Chapter 6, Parts 4 and 5 of the RCS.
If the provisions of 10 CFR 835.3(e) are exercised, documentation of the schedule deviation
should be developed and include a discussion of the specific activity involved and the reason for
the schedule deviation.
Revisions to procedures, policies, or methods of evaluation used for monitoring shall be
documented [10 CFR 835.704(e)]. The original document and all approved revisions of subject
documents should also be retained.
13.2.2.6 Audits and Programmatic Reviews
Assessments of radiation protection programs by external agencies and internal groups are
valuable in determining the adequacy of the program. Records shall be maintained to
document the results of internal audits and other reviews of program content and
implementation [10 CFR 835.704(c)]. These records should include records of corrective actions
and audit procedures.
Section 143
13.2.2.7 Posting and Labeling
DOE G 441.1-1C 179
5-19-08
Records necessary to evaluate compliance with the posting and labeling requirements of
10 CFR 835 shall be maintained [10 CFR 835.701(a)]. These records should include the
following:
documentation of area postings on area monitoring records. These records need not
show the placement of each sign, but should be adequate to demonstrate that areas are
posted consistent with the radiological conditions recorded on the monitoring record;
variance from facility design parameters;
documentation of compensatory measures implemented to obviate the need for
posting; and
long term changes in postings.
13.2.2.8 Calibration, Functional Tests, and Maintenance Records
Calibration and maintenance procedures, criteria, and schedules for dosimeters and
radiation protection instruments are important to demonstrate their dependability, reliability,
and accuracy. The results of maintenance and calibration performed on instruments and
equipment used for monitoring shall be recorded [10 CFR 835.703(d)]. These records should
include equipment, sources, and fields used, results of initial (as found) tests and
post-adjustment tests, and corrective actions taken for instruments found to be out of
calibration or inoperable.
The calibration laboratory should maintain the following sets of documentation: (1) the
laboratory protocol; (2) the laboratory records; and (3) the calibration records. Historical
records should be maintained to detail any changes or revisions in procedures or protocols.
The performance of functional tests during use of portable monitoring instruments in the
field should be appropriately documented. This may be as simple as a check-list on the survey
sheet.
13.3 Reports
Many reports are prepared for a variety of purposes by the radiation protection program.
This chapter describes the reports required by the previously cited references.
13.3.0 Reports to Individuals
Each individual monitored in accordance with 10 CFR 835.402 shall be provided an annual
report of his/her dose [10 CFR 835.801(c)]. The report shall include, at a minimum the data
required under 10 CFR 835.702(c), and the following additional information [10 CFR 835.801(a)
& (c)]:
--The DOE site or facility name;
--the name of the individual, and;
DOE G 441.1-1C 180
5-19-08
--the individual’s social security number, employee number, or other unique identification
number.
Individuals who were not monitored in accordance with 10 CFR 835.402 but who were
determined to have received an occupational dose in excess of any of the monitoring thresholds
of 10 CFR 835.402 should also be provided an annual report of his/her dose. This report should
also include the information discussed above. Radiation exposure reports sent to individuals in
accordance with 10 CFR 835 subpart I only need to include exposure data for the dose received
at that site or facility. 10 CFR 835.702(c)(5)(iii) requires that records include cumulative total
effective dose (CTED). CTED is the sum of the total effective dose values recorded for an
individual plus, for occupational exposures received before the implementation date of the June
8, 2007 amendment to 10 CFR 835, the cumulative total effective dose equivalent (as defined in
the November 4, 1998 amendment to 10 CFR 835) values recorded for an individual, where
available, for each year occupational dose was received, beginning January 1, 1989.
Section 144
DOE O 231.1A, Environment, Safety and Health Reporting (DOE 2004b), and DOE M
231.1-1A, Environment, Safety and Health Reporting Manual (DOE 2004c), provide additional
detailed information with respect to occupational dose reporting requirements.
Whenever a report concerning radiation protection matters is written about or to an
individual, a copy of the report should be placed in the individual's dose records.
13.3.0.0 Records Requested by Monitored Individuals
Detailed information on any individual's exposure shall be made available to him/her upon
request, consistent with the provisions of the Privacy Act (PA 1974) [10 CFR 835.801(d)]. See
section 13.4 of this Guide for Privacy Act considerations. Requests for exposure information
should be answered as soon as possible. At a minimum, the response should provide the
information supplied on the termination report. Other data that may be requested by the
individual should be supplied if available.
13.3.0.1 Termination Dose Reports
10 CFR 835.801(b) requires that a termination dose report be provided only upon request of
the individual terminating employment. This requirement includes visiting scientists and
transient workers, such as technicians, and specialists who perform work at a facility and then
leave to work elsewhere. The termination dose report shall be provided to the requesting
individual as soon as data are available, but not later than 90 days after termination.
10 CFR 835.801(b) also requires that a written estimate of the radiation dose received by the
individual based on available information shall be provided at the time of termination, if
requested. The provisions for termination dose reports and written estimates only apply if the
individual requests this information on or before the individual’s last day of employment. If the
request is made after the termination date, then the request should be handled in accordance
with 10 CFR 801(d). When a termination dose report is provided to an individual, then an
annual report to that individual, under 10 CFR 801(c), is not necessary. Each facility's radiation
protection program should document how the request should be made and to whom the
request should be made. This topic should also be addressed in the appropriate radiological
training courses.
DOE G 441.1-1C 181
5-19-08
13.3.0.2 Reports to DOE
Reports identifying a specific individual and his or her exposure data may be required to be
sent to DOE. These reports include occurrences reported under DOE O 231.1A, Environment,
Safety and Health Reporting, of exposure of an individual to radiation and/or radioactive
material, or planned special exposures conducted in accordance with 10 CFR 835.204(e). Under
10 CFR 835.801(e), each individual specifically identified in such reports shall be provided a
report on his or her exposure data included in the report to DOE at a time not later than the
transmittal to DOE. A separate report should be provided to each affected individual discussing
the nature and content of the report to DOE and his or her exposure data contained in the DOE
report. Alternatively, a copy of the report sent to DOE may be sent to each affected individual
to satisfy this requirement. Privacy Act (PA 1974) restrictions shall be considered since DOE
report may contain personal information concerning other affected individuals.
13.3.1 Reports of Planned Special Exposures
Section 145
A written report of the conduct of a planned special exposure shall be submitted to the
cognizant Program Office and the Secretarial Officer responsible for environment, safety and
health matters (i.e., the Chief Health, Safety and Security Officer) within 30 days after the
exposure [10 CFR 835.204(e)]. This written report is required even though the actual doses may
not have exceeded the values of occupational dose limits established in 10 CFR 835.202.
The report should address, but need not be limited to:
a description of the circumstances requiring the use of a planned special exposure;
identification of involved individuals, including exposed individuals, supervisors,
approving management and DOE personnel;
date(s) on which the exposure(s) occurred;
estimated and actual personnel doses, including doses received by affected individuals
before the planned special exposure; and
records of ALARA plans, work authorizations, briefings, approvals, and other work
documentation.
13.4 Privacy Act Considerations
Any system of records that retrieves information concerning individuals by personal
identifiers, such as name, any identifying numbers (e.g., Social Security Number or payroll
number), symbol, or other identifying particulars assigned to the individual, is subject to the
Privacy Act. The principal records that would apply in this Guide are the individual radiation
dose records. Other records, such as program records, are subject to the FOIA (FOIA 1986).
No information on an individual shall be revealed to anyone other than the individual, DOE,
or DOE contractor personnel who have a need to know without prior written consent of the
individual, unless authorized by the Privacy Act or for routine uses as published periodically in
DOE G 441.1-1C 182
5-19-08
the Federal Register. Records of deceased individuals are not covered by the Privacy Act, but
are subject to the FOIA.
The following subsections discuss applicable parts of the Privacy Act as implemented by DOE
through 10 CFR 1008 (DOE 1980).
13.4.0 Informing Individuals
Individuals about whom information will be collected should be informed of the authority
for collection of the information, the principal and routine uses of the information, and the
effects of not furnishing the information.
13.4.1 Identifying Individuals
10 CFR 1008.4 sets forth procedures for identifying the individual making a request for
access to, information from, or amendment of his/her records. Identification of the individual
should be established by one of the following three methods:
if making a request by mail, a photocopy of two identifying documents bearing his/her
name and signature must be submitted, one of which should bear his/her current home
or business address and date of birth;
if appearing in person, the individual must present either one identifying document
bearing his/her photograph and signature or two identifying documents bearing his/her
name and signature, one of which should bear his/her birth date and current home or
business address; or
the individual can provide other proof of identity that the Privacy Act Officer deems
satisfactory in the particular circumstances.
13.4.2 Requesting Correction or Amendment of a Record
If an individual requests a correction or amendment to his/her records, the record shall be
changed or the Privacy Act Officer shall inform the requestor that the change has been denied.
The denial should include the record system manager's name and title, the reasons for the
denial, notification of the individual's right to appeal the denial, and the individual's right to
submit a statement of disagreement.
Section 146
13.4.3 Responding to Requests
Every reasonable effort should be made to respond with the requested material, correction,
or amendment within 10 days. Response should be made within 20 days unless unusual
circumstances prevail. If a response cannot be made within 10 days, an interim response should
be made providing information on the status of the request and an estimate of when the
response will be made.
13.4.4 Accounting for Disclosures
DOE G 441.1-1C 183
5-19-08
An accounting of all disclosures of information, except those to DOE and DOE contractor
personnel with a need to know or those required by the FOIA, should be maintained as
prescribed by the Privacy Act.
13.5 Record – Keeping Standards
Records shall be retained until final disposition is authorized by DOE [10 CFR 835.701(b)].
Individual dose records shall be transferred to DOE upon cessation of activities at the site that
could cause exposure to individuals [10 CFR 835.702(h)].
General standards for maintenance and retention of radiation protection records, including
media, media conversion, corrections, retention, and retrievability, are provided in the RCS.
DOE G 441.1-1C 184
5-19-08
14.0 RADIATION SAFETY TRAINING
While there are significant differences in the missions of various DOE and DOE-contractor
operations, and thus significant differences in the content of radiation safety training programs
necessary for adequate protection of employees, the basics of radiation safety for DOE activities
can be taught using core course material augmented by site-specific material.
Different levels of radiation safety training are used to ensure the safe and efficient conduct
of work. Training courses, such as Radiological Worker Training (RWT) (DOE 2007e), take into
account different levels of risk associated with various job functions and duty locations. Training
shall be commensurate with the level of potential radiological hazards [10 CFR 835.901(c)].
A training program that evaluates the knowledge and skills that a worker needs for safe job
performance, in conjunction with core course material for teaching the fundamentals of
radiation safety, should be implemented to ensure that individuals can perform their assigned
duties safely and respond appropriately to both normal and abnormal situations they may
encounter.
14.1 Implementation Guidance
14.1.0 General Information
Radiation safety training shall be provided to all individuals before:
being permitted unescorted access to controlled areas; and
receiving occupational dose (i.e., the exposure resulted from the individual’s work
assignment) during access to controlled areas [10 CFR 835.901(a)]. This requirement
applies whether or not the individual is escorted.
10 CFR 835 requires that radiation safety training shall include certain topics (discussed in
detail in Section 14.3) to the extent appropriate to the individual's prior training, work
assignments, and degree of exposure to potential radiological hazards [10 CFR 835.901(c)].
Radiation safety training program requirements should be established in specific procedures
that address, at a minimum, the issues discussed in this Guide.
In addition to the radiation safety training requirements discussed in this Guide,
10 CFR 835.103 establishes requirements for the education, training, and skills of individuals
who are responsible for developing and implementing measures required to ensure compliance
with 10 CFR 835. Chapter 3 provides guidance for achieving compliance with these
requirements.
Section 147
To ensure that appropriate radiation safety training is provided to all individuals entering
controlled areas, DOE has sponsored development of radiation safety training core course
material for General Employee Radiological Training (GERT) (DOE 2007f) and Radiological
Worker Training (RWT) (DOE 2007e). RWT has been developed in a modular format to support
two distinct core courses, RWT-I and RWT-II. RWT-II includes the material provided in RWT-I,
augmented by additional modules on more complex radiation protection issues, such as high
DOE G 441.1-1C 185
5-19-08
radiation area and contaminated area entry and exit controls. Detailed guidance for use of the
DOE core course material is provided in the associated Program Management Guides.
DOE developed and implemented the core course material to enhance the content of
radiation safety and other training programs across the DOE complex and to bring these training
programs up to a standard consistent with similar programs implemented in the commercial
nuclear industry. DOE recommends the use of the radiation safety training core course
material, updated as necessary to reflect recent changes in regulatory requirements and other
applicable standards, to satisfy the corresponding requirements of 10 CFR 835. Use of the
radiation safety training core course material is no longer mandatory; however, the core course
material for GERT and RWT should be strongly considered as a basis for developing and
implementing radiation safety training programs.
A radiation safety training program sufficient to meet the requirements of 10 CFR 835.901
should include:
course materials from the DOE core training materials applicable to the radiological
hazards and controls associated with the specific DOE activity;
site- and activity-specific content and instruction;
performance demonstrations and examinations as appropriate to demonstrate
understanding of key concepts and practices; and
an evaluation of other applicable DOE requirements.
A satisfactory training program for radiation safety should also include training evaluations
and provisions for maintaining training records. Detailed requirements and guidance for
maintenance of radiation safety training records are provided in Subpart H of 10 CFR 835 and
Chapter 13 of this Guide.
14.2 Determination of Required Training
10 CFR 835.901(a) and (b) establish requirements for distinct levels of radiation safety
training. If an individual will be permitted unescorted access to controlled areas or receive
occupational exposure to ionizing radiation during escorted or unescorted access to controlled
areas, a determination must be made regarding the appropriate level of knowledge and the type
of training to be provided. This determination should be based on:
the nature of the radiological hazards in area(s) to which the individual will be granted
access and the nature of the work to be performed. This determination may be made
on an individual basis, but is most commonly made in accordance with standardized
procedures on a group basis, such as work group affiliation, level of access to certain
areas, or type of work to be performed. If an individual determination is needed to
meet special needs (such as for a dignitary or technical representative), the supervisor
responsible for the individual's activities should establish and document this
information. Based upon the information provided by the cognizant supervisor, the
DOE G 441.1-1C 186
Section 148
5-19-08
radiological control organization, training organization, or other cognizant organization
should determine the appropriate level of training;
the type and complexity of protective actions that the individual might be expected to
undertake in the areas to be entered. This should include an assessment of both
routine and emergency actions;
a determination with regard to whether or not the individual will be under constant
escort or supervision; and
the individual's previous education, training, and experience in working with radioactive
materials and in the vicinity of radiological hazards. This determination may be made by
review of available training records, provision of a challenge examination, knowledge of
individual experience and capabilities, personal documented interviews conducted by
cognizant radiation protection or training personnel, documented working agreements
with the individual's sponsoring organization (e.g., International Atomic Energy Agency
or Defense Nuclear Facilities Safety Board), or a combination of these activities.
Challenge examinations may be given based on the individual’s prior experience, education,
and/or training. The radiological control organization should determine appropriate criteria for
allowing challenge examinations. Challenge examinations should be based on the objectives
stated for the training program, and are an approved form of proficiency testing. Challenge
examinations should cover the entire applicable core training program.
Challenge examinations should address learning objectives from each topic or subject area
of the training to ensure that workers not benefiting from classroom instruction have the
requisite knowledge. With successful completion of the challenge examination, the student
should be granted an exemption from the appropriate core training course or lesson. DOE
5480.20A requires DOE nuclear facilities to prepare and submit for approval procedures
governing the processes used to grant exceptions from training or qualification requirements.
Such procedures should be developed to govern radiation safety training for all DOE activities.
DOE encourages the establishment of reciprocity agreements to facilitate the acceptance of
training provided at other sites. It is particularly beneficial to implement a practice of accepting
training provided by other sites and facilities having similar hazards, processes, and facilities.
Such agreements require some assurance that the training provided by the member sites
provide a level of training acceptable to all signatory parties. In general, completion of the
applicable sections of the DOE core course material within the past two years in accordance
with the Program Management Guides should be considered reasonable grounds for acceptance
of previously completed core training (see Section 14.6.). In addition, consideration may be
given for completion of training from other (non-DOE) nuclear facilities, formal education
applicable to radiation safety, and previous experience working in facilities with similar hazards
and controls. Whenever the full radiation safety training core course is not provided, the
justification for any omissions (i.e., identification of any previous education, training, or
experience accepted in lieu of providing radiation safety training) should be documented.
14.3 Training Course Content
DOE G 441.1-1C 187
5-19-08
GERT provides the appropriate level of training for individuals who:
Section 149
enter controlled areas unescorted; or
receive occupational exposure during controlled area entry (whether escorted or not).
These are the individuals addressed in 10 CFR 835.901(a). GERT does not provide the
appropriate level of training for individuals who enter radiological areas unescorted or for those
individuals who perform unescorted duties as a radiological worker.
RWT-I provides the appropriate level of training for individuals who:
enter non-contaminated radiation areas (but not high or very high radiation areas) or
areas in which they are likely to receive doses exceeding 0.1 rem (0.001 Sv) in a year
(e.g., certain radioactive material areas and areas surrounding radiological areas);
work with sealed or fixed radioactive material that does not produce high radiation
fields (i.e., fields exceeding 0.1 rem (0.001 Sv) in an hour); or
work with radiation producing devices that do not produce high radiation fields (i.e.,
fields exceeding 0.1 rem (0.001 Sv) in an hour).
RWT-I is not appropriate for individuals who enter contaminated areas or high radiation
areas unescorted. However, RWT-I may be augmented by the specific High/Very High Radiation
Area Entry Training module to prepare RWT-I trained individuals for safe entry into high or very
high radiation areas.
RWT-II has been developed to provide the appropriate level of training for individuals who,
in addition to the above criteria:
are expected to enter high radiation areas;
are expected to enter contaminated areas; or
are otherwise expected to work with unsealed quantities of radioactive materials.
10 CFR 835 establishes provisions allowing the use of escorts in lieu of providing radiation
safety training. Guidance on implementing these provisions is provided in Section 14.8 of this
Guide.
RWT uses a modular format to allow training to be customized to be commensurate with
the hazard present in the area. This format facilitates upgrading of an individuals' status from
RWT-I to RWT-I with High/Very High Radiation Area Training or RWT-II by simply completing the
necessary additional modules.
Employment status (i.e., permanent, contract, temporary) should not be used to determine
the appropriate level of training. As stated above, the type and level of training may be
adjusted to be commensurate with the individual's level of access, assigned duties, and type of
previous training and experience.
DOE G 441.1-1C 188
5-19-08
Radiation safety training shall include the following topics, to the extent appropriate to each
individual's prior training, work assignments, and degree of exposure to potential radiological
hazards [10 CFR 835.901(c)]:
basic radiological fundamentals and radiation protection concepts;
risks of exposure to radiation and radioactive materials, including prenatal radiation
exposure;
engineered controls, administrative controls, limits, policies, procedures, alarms, and
other measures implemented to control exposures to radiation and radioactive
materials, including both routine and emergency actions;
individual rights and responsibilities as related to implementation of the radiation
protection program;
individual responsibilities for implementing as low as is reasonably achievable (ALARA)
measures required by 10 CFR 835.101; and
individual exposure reports that may be requested in accordance with 10 CFR 835.801.
Section 150
The DOE core course material provides this type of information to the level of detail that is
broadly applicable to all DOE activities, but do not address site-specific information that
individuals may need to conduct work safely.
DOE G 441.1-1C 189
5-19-08
14.4 Facility-Specific Materials
To implement an effective radiation safety training program, the core courses should be
augmented with facility-specific information as necessary to adequately address the course
content requirements of 10 CFR 835.901(c). The following information should be considered in
developing facility-specific training materials:
procedures for entering and exiting the authorized areas, including use of work
authorizations;
controls on radiation exposures, including administrative control levels and fetal
exposure control;
measures for use of protective equipment, including protective clothing and respiratory
protective devices;
alarms, warning signals, and response actions;
ALARA measures implemented at the facility;
requirements for interfacing with the radiation protection organization;
skills required by the worker to execute his radiation safety responsibilities;
worker responsibilities for self and coworker protection, including exercise of stop work
authority; and
measures for requesting personal dose records and reports.
Following assessment of all of the necessary facility-specific information, the facility-specific
portion of the training courses should be developed to augment the DOE core course material.
The final radiation safety training materials should receive the concurrence of the Radiological
Control Manager or his designee.
Although a systematic approach to training is currently required only at DOE facilities under
the requirements of DOE 5480.20A, all DOE activities should, as much as practicable, use this
approach in developing specific training. Suggested learning objectives and examples for
different target audiences and types of facilities, such as accelerators, radiation generating
devices, plutonium, uranium, and tritium facilities, are provided in the additional radiation
safety courses developed by DOE. DOE encourages use of these materials, revised as
appropriate to reflect recent changes in applicable requirements and standards, to identify
learning objectives appropriate for the specific target audiences and facilities.
(See http://www.hss.energy.gov/HealthSafety/WSHP/radiation/RST/rst.htm.)
14.5 Conduct of Radiation Safety Training
DOE G 441.1-1C 190
5-19-08
Radiation safety training should be conducted in an appropriate training facility, such as a
classroom or computer-based training facility, augmented by suitable mock-up and/or
laboratory facilities and on-the-job training and evaluation for RWT. Training media, such as
handouts, slides, and video presentations, should be appropriate to the subject matter and the
audience. Computer-based training may be used as appropriate to ensure consistent and
reliable presentation of the course materials. Chapter 6 of the RCS and the Program
Management Guides provide detailed guidance regarding instructor qualifications and
recommended performance demonstrations.
14.6 Completion of Radiation Safety Training
Due to the limited access granted to individuals who complete only GERT, examinations are
not required.
Successful completion of RWT shall be demonstrated by completion of an examination
[10 CFR 835.901(b)]. Examinations should be written, but other measures may be implemented
to accommodate those with special needs.
Section 151
When measures other than written examinations are used, an evaluation should be made to
ensure that all individuals will be able to execute their responsibilities safely. For example,
individuals with reading comprehension impairments may take an oral examination, but an
evaluation should be performed to ensure that the student:
can read and understand any radiological warning signs and labels, work authorizations,
and procedures affecting their work; or
will always be provided the same level of assistance during area access and work
performance as was provided during the examination.
Computer-based examinations, using automated examination composition and scoring, may
be used as appropriate. The minimum passing score for examinations, including challenge
examinations, should be established at or above 80 percent. When using computer-based
examinations, care must be taken to ensure that the testing process provides the same degree
of fidelity as class room training. Reference material should not be allowed and the computer-
based examination should not allow the trainee to pass the examination based on trial and
error. Permitting a trainee to pass a computer-based examination by trial and error would be
inconsistent with the requirement that individuals demonstrate an acceptable baseline
knowledge level of radiation protection fundamentals and practices. Chapter 6 of the RCS and
the core course Program Management Guides provide detailed guidance for conducting
examinations.
The RCS recommends use of DOE developed training material, supplemented by site-specific
training materials, be used to the extent practicable to satisfy the training requirements of 10
CFR 835.901 and 10 CFR 835.103. DOE has continued to provide copies of the DOE example test
questions to DOE contractors and subcontractors. To help keep some degree of confidentiality
on the DOE example test questions, DOE has marked the Radiological Control Technician
Training Exam Bank as Official Use Only and requests the contractors and subcontractors to
DOE G 441.1-1C 191
5-19-08
certify that they are only using the exam banks for conducting radiation safety training
purposes.
DOE’s radiation training handbooks provide guidance on implementing a radiation safety
training program, including guidance on use of the DOE developed example test questions. The
DOE example test questions may be used as a basis for developing the facility exam bank.
However, sites should not rely solely on the use of the DOE developed example test questions.
In developing a facility exam bank, sites may selectively choose some of the DOE example test
questions as written. This should be a small fraction of the total examination. They should also
modify some of the DOE example test questions (i.e., reorder the answers and change numerical
values) and develop facility specific exam questions for the remainder (i.e., the majority) of the
examination. If a facility decides to use some of the DOE example test questions as a study aid
(regardless of DOE’s recommendation), it is suggested that any questions provided to the
student as a study aid not be used verbatim in the final examination.
DOE recognizes that, other than asking contractors and subcontractors to keep the example
test confidential, DOE Headquarters has no mechanism to maintain the DOE example test as a
controlled document. The document that should be kept as a controlled document is the facility
exam bank.
Section 152
In addition to an examination, students in RWT classes shall be required to complete
performance demonstrations commensurate with their duties [10 CFR 835.901(b)].
Performance demonstrations typically involve such activities as safely entering and exiting
simulated radiological areas, donning and removing protective clothing, and performing whole
body frisking. Sites should periodically evaluate individuals’ abilities to perform acceptable
radiological work practices (such as donning and doffing protective clothing) including
evaluation of performance demonstrations commensurate with their duties, similar to those
activities evaluated as part of their initial qualification. Chapter 6 of the RCS and the RWT core
course material provide detailed guidance for conducting performance demonstrations.
Proof of successful course completion, such as a certificate, wallet-sized card or access
control or other database entry, should be provided to indicate the successful completion of
DOE core radiation safety training. To be acceptable as proof of training at other DOE activities,
the proof of completion should include the:
individual's name;
date of training;
modules covered; and
name of certifying official (such as the instructor or examination evaluator).
To allow reciprocity for completion of the core courses, the proof of completion should
provide the course title (i.e., GERT, RW I, RW II) and, if the entire core course was completed, a
statement to that effect.
DOE G 441.1-1C 192
5-19-08
For sites planning frequent use of training reciprocity, DOE encourages close prior
coordination to establish inter-facility (or inter-site) working agreements that define
mutually-acceptable standards for acceptable training program implementation. Regardless of
such agreements, each site should retain the discretion to evaluate incoming workers
individually and to require challenge examinations or retraining as necessary to ensure
compliance. Consideration must still be given to the provisions for facility-specific training
discussed above.
Individuals who do not pass all required examinations and performance demonstration
requirements should not be allowed to proceed with unescorted tasks involving exposure to
radioactive materials or radiation until they have completed remedial actions. Remedial actions
for failure to pass a written examination or meet performance demonstration requirements
should include remedial instruction and re-examination, repetition of the training program, or
restriction from job duties. Because challenge examinations are designed to provide credit
toward required training, the remedial action for failure of a challenge examination should be to
deny credit for that examination toward the required training. The choice and extent of
remedial actions should be determined based upon the extent of the knowledge or skill
deficiencies demonstrated by the individual.
14.7 Periodic Radiation Safety Training
In addition to the initial training provided before an individual is granted access to the
specified areas, radiation safety training shall be conducted at least once every 24 months and
whenever significant changes are implemented that might affect the individual
[10 CFR 835.901(e)]. This periodic training should not simply repeat the initial training, but
should review key principles, provide more detailed knowledge of the subject matter required in
10 CFR 835.901(c), and stress new program requirements and seldom-used knowledge and
skills. Periodic radiation safety training should be conducted in accordance with the guidance
provided in Section 14.5.
Section 153
Although many possible program changes may affect individual workers, the assessment of
their need for periodic radiation safety training at intervals of less than 24 months should at
least consider the factors discussed in Section 14.4 of this Guide. If the program change is
judged to be significant, then training should be completed either before the change is
implemented or the individuals should be restricted from their duties until training has been
completed.
The requirements for periodic radiation safety training are not intended to deter cognizant
management from providing routine updates to workers on radiation safety requirements.
Updates may be necessary to alert workers to radiation protection program changes that are
judged to be non-significant and whose impact does not warrant formal training or
examinations. These updates are typically provided in the form of memoranda or posted
notices. DOE encourages the use of such communication devices.
Periodic radiation safety training for RWT shall include successful completion of an
examination [10 CFR 835.901(e)]. Examinations should be conducted in accordance with the
guidance provided in Section 14.6 of this Guide. If challenge examinations are used to satisfy all
DOE G 441.1-1C 193
5-19-08
or part of the requirements for periodic radiation safety training, those examinations should be
developed and conducted in accordance with Section 14.6.
14.8 Use of Escorts in Lieu of Training
As indicated in Section 14.2, constant escort of an individual may affect the extent of
required training. The use of constant escort may obviate the need for certain types of training
by making the escort responsible for the protection and actions of the affected individual. This
approach should only be used when:
the individual will enter the area for a short period of time (i.e., a few hours);
provision of an escort will provide for an adequate level of safety; and
provision of an escort will not result in significant adverse dose effects (ALARA
considerations). This determination should be based upon consideration of the
resources (including collective dose) that must be expended to escort the individual
versus those necessary to provide the appropriate training.
Use of an escort is also helpful when an individual has completed portions of the required
training and would benefit from on-the-job experience. In these cases, a fully qualified
individual should directly oversee the trainee’s performance of tasks for which the appropriate
training, examinations, and performance demonstrations have not been completed.
The assigned escort shall have completed the requisite training and shall ensure that the
untrained individual complies with the documented radiation protection program
[10 CFR 835.901(d)]. For instance, an individual assigned to escort an untrained individual in
a contaminated area shall have completed RWT-II or equivalent training. In addition, the
untrained individual, if occupationally exposed in a controlled area at a DOE site or facility,
shall complete at least those portions of the training related to the risks of exposure to
radiation and radioactive materials, including prenatal radiation exposure and individual
exposure reports that may be requested [10 CFR 835.901(a)].
For individuals who are expected to remain in the controlled area for an extended period
(i.e., more than a few hours) or to make repeated entries, the full training course should be
completed, as appropriate to the individual's prior training, experience, and potential exposure
risks.
Section 154
14.9 Refresher Training
The RCS recommends and provides guidance for the conduct of radiation safety refresher
training every other year when biennial radiation safety training is not required.
14.10 Other Training Programs
In addition to the radiation safety training requirements discussed in this Guide,
10 CFR 835.103 establishes requirements for the education, training, and skills of individuals
who are responsible for developing and implementing measures required to ensure compliance
DOE G 441.1-1C 194
5-19-08
with 10 CFR 835. Chapter 3 provides guidance for achieving compliance with these
requirements.
14.11 Training Effectiveness Evaluations
Training effectiveness evaluations are quality assurance measures used to determine
whether qualified workers have retained all the required knowledge and skills and that are
applying them properly. Feedback is an important form of evaluation that encourages
improvements and upgrades to the training programs. Comments from supervisors, instructors,
and trainees should be used to enhance course effectiveness. Although other means of
evaluating training programs are currently in place (such as industry and facility exchanges,
instructor evaluations, and routine assessments), they are not addressed in this Guide.
The effectiveness of radiation safety training should be verified in accordance with the
applicable training course program management guide. DOE has issued guidance for evaluating
the effectiveness of radiation safety training in Evaluating the Effectiveness of Radiological
Training. This document is also included as an attachment to the DOE-developed Radiological
Worker Training and General Employee Radiological Training Handbooks. In addition, DOE
5480.20A requires that evaluations of training and qualification programs be conducted in
accordance with DOE-STD-1070-94, GUIDELINES FOR EVALUATION OF NUCLEAR FACILITY
TRAINING PROGRAMS (DOE 1994).
DOE G 441.1-1C 195
5-19-08
15.0 SEALED RADIOACTIVE SOURCE ACCOUNTABILITY AND
CONTROL
A program to control sealed radioactive sources is necessary to prevent unplanned
exposures and loss of sources. DOE has codified a general requirement indicating that all sealed
radioactive sources (both accountable and exempt) shall be used, handled, and stored in a
manner commensurate with the hazards associated with operations involving the sources
(10 CFR 835.1201). For accountable sealed radioactive sources, specific measures, including
inventories and source leak tests, shall be implemented (10 CFR 835.1202).
Exempt sealed radioactive sources need not be inventoried and leak tested. However,
exempt sealed radioactive sources and the individuals using them are still subject to all other
applicable requirements of 10 CFR 835 (e.g., radioactive material control, posting and labeling,
radiation safety training, etc).
If a sealed radioactive source contains more than one radionuclide, the sum-of-the-fractions
rule (i.e., A1/Q1 + A2/Q2 + ... 1; where A is source activity and Q is the accountability value
for the radionuclide) shall be used to determine if the source is accountable (10 CFR 835,
Appendix E, Footnote 1). For radionuclides that are not listed in Appendix E, 10 CFR 835
provides values of 10 microcuries for alpha emitters and 100 microcuries for all other
radionuclides. The values provided in Appendix E of 10 CFR 835 are not material release values
and should not be used to determine the acceptability of releasing materials from radiological
controls either within or outside of the controlled area.
Section 155
10 CFR 835.3(e) establishes provisions allowing for extensions of the intervals between
mandatory sealed radioactive source inventories and source leak tests. Chapter 3 provides
guidance for implementing necessary extensions of the required intervals.
15.1 Implementation Guidance
This chapter provides guidance for establishing and operating a sealed radioactive source
accountability and control program. Key components of a sealed radioactive source
accountability and control program should include:
organization and responsibilities;
receipt;
labeling and storage;
inventory;
source leak testing; and
handling and disposal.
DOE G 441.1-1C 196
5-19-08
Responsibilities of the organizational components, including line management, the
radiological control organization (hereinafter referred to as the RCO), the source custodian, and
the source user are presented.
15.2 Organization and Responsibilities
The responsibilities of the RCO for a sealed radioactive source accountability and control
program should include the following:
establishing the program;
maintaining records related to the accountability and control of sealed radioactive
sources;
providing each source custodian with an inventory list of accountable sealed radioactive
sources; and
assisting the source custodian in training source users.
Some of these responsibilities may be delegated to another contractor group, for example,
the safeguards and security group may be given the responsibility for maintaining accountability
records. Non-delegatable responsibilities of the RCO should include:
approving procurement of all sealed radioactive sources with the source custodian or
user;
performing receipt monitoring;
performing source leak tests; and
monitoring storage and use areas.
Sealed radioactive source custodians and source users are generally expected to work
directly with radioactive materials and therefore would meet the 10 CFR 835.2(a) definition of
the term “radiological worker.” Such individuals would therefore be subject to the radiation
safety training requirements of 10 CFR 835.901(b). An individual shall be trained in accordance
with 10 CFR 835.901(b) prior to performing unescorted assignments as a radiological worker.
10 CFR 835.103 establishes additional requirements for the education, training, and skills of
those individuals who are responsible for developing and implementing measures necessary for
ensuring regulatory compliance. That training should include site-specific source accountability
and control measures discussed in this Guide. See Chapters 3 and 14 for additional guidance.
The source custodian should notify and obtain approval of the RCO prior to:
any significant change in the use of a sealed radioactive source;
transfer of a sealed radioactive source to a new permanent storage location or to a new
source custodian;
DOE G 441.1-1C 197
5-19-08
modification of a device containing a sealed radioactive source;
disposal or off-site transfer of a sealed radioactive source; and
any procurement or acquisition of additional sealed radioactive sources.
The source custodian should notify the RCO in the event of the loss of, or suspected or
actual damage to, any sealed radioactive source. The source custodian should ensure that
source leak tests are conducted and inventory checks are performed for accountable sealed
radioactive sources at least every 6 months. The RCO should actually perform the source leak
tests. The source custodian should maintain records of the storage and use locations of all
assigned sealed radioactive sources.
Section 156
Prior to taking possession of the sealed radioactive source, the source user should receive
authorization from the RCO and the source custodian. Source users should use, handle, and
store assigned sealed radioactive sources consistent with the training provided and in
accordance with the programmatic requirements established by the RCO.
15.3 Receipt
Prior to receipt of sealed radioactive sources, the RCO should assign the sources to the
proper source custodians. Immediately upon receipt of sealed radioactive sources, the RCO
should be notified. The packaging shall be inspected for damage and contamination and
radiation monitoring performed in accordance with 10 CFR 835.405. Monitoring pursuant to §
835.405(b) is not required for packages transported on a DOE site which have remained under
the continuous observation and control of a DOE employee or DOE contractor employee who is
knowledgeable of and implements required exposure control measures [10 CFR 835.405(e)].
Except for gaseous sealed radioactive sources and tritium, a source leak test shall be performed
upon receipt of all accountable sealed radioactive sources [10 CFR 835.1202(b)]. The receipt
monitoring and source leak test should be performed by the RCO. The source leak test should
be performed in accordance with Section 15.6 of this Guide. The source custodian should be
notified of the arrival of the sealed radioactive sources to ensure that proper accountability and
controls are initiated. The sources should be placed into storage or into the device in which
they will be used. The source custodian’s and site's records should be updated to include the
new sealed radioactive sources.
When receiving radioactive material from NRC-licensed facilities, DOE activities are required
to ensure that the ensuing storage, usage, and control of the material are consistent with the
requirements of 10 CFR 835. Because of differences between DOE and NRC requirements for
radioactive material labeling and control, radioactive material received from NRC licensees may
or may not be received in a condition that is in compliance with DOE requirements, particularly
the labeling requirements found in Subpart G of 10 CFR 835. Therefore, DOE activities should
carefully assess the radiological characteristics of any received material and implement the
controls required by 10 CFR 835. If the material is received with a label, consideration should be
given to retaining the label; and if the material will be transferred frequently between DOE-
regulated and NRC-licensed activities, consideration should be given to implementing and
maintaining the most stringent requirements applicable to ensure ongoing compliance.
DOE G 441.1-1C 198
5-19-08
15.4 Labeling and Storage
Unless specifically excepted under 10 CFR 835.606, all sealed radioactive sources having an
activity exceeding 10% of the applicable 10 CFR 835 Appendix E values or 0.1 or greater Ci
content shall be labeled (10 CFR 835.605). Labels should be applied to all sealed radioactive
sources, regardless of the activity of the source, to minimize the likelihood of loss or
unauthorized usage. In recognition of the differing labels permanently applied to certain sealed
radioactive sources by their manufacturers, labels applied to sealed radioactive sources may be
excepted from the color specifications of 10 CFR 835.601(a) [10 CFR 835.606(b)(6)]. However,
standard colors and designs should be used to the extent practicable to foster instant
recognition by affected individuals.
Section 157
Appropriate designs for radioactive material labels applied to sealed radioactive sources are
described in Chapter 12. Labels should be applied directly to the sealed radioactive source or, if
that is not practicable, the labels should be applied to the storage containers and devices
containing sealed radioactive sources. The label should identify the radionuclide, source
activity, date of assay, model and serial number of the source and container or device, and a
method for identifying the source custodian.
In addition, labels should include the contact radiation levels, removable contamination
levels, dates monitored, and name of the individual performing the monitoring. The label
should be sufficiently durable to remain legible for the useful life of the device or storage
container and should be located in a readily visible place. Another method of labeling makes
use of electronic means such as bar codes along with human-readable labels. These will
minimize human errors and compensate for the small size of some sources.
Ideally, all the labeling information should be on a label affixed to the source; however, due
to the extensive list of information and the small size of many sealed radioactive sources, this is
not always possible. If the source is too small to label, then either its source container (unless it
is also too small) or its radioactive material storage location should be labeled. A method of
tracing a source to its label should be implemented if the label is affixed to the source container
or radioactive material storage location. Commercially manufactured sources should have a
serial number on the source itself which should be traceable to the serial number on the label.
For sources without serial numbers, the contractor should permanently mark the source, such
that the integrity of the source is not violated, with a unique identification, and should use the
same identification mark on the label.
If the radiation intensity around the sealed radioactive source container will change
significantly upon opening the container or changing the position of the source in the container,
that information should be provided on a label so that it is easily observable by the operator.
The storage location should also be marked in order to ease location identification during
inventory. Storage locations, containers, and devices should be appropriate for the specific
sources, and should only be used to contain radioactive materials. Storage rooms or cabinets
selected to contain accountable sealed radioactive sources should either be isolated from
occupied areas or located in radiological areas, be of a design which would minimize damage
from fire, and be free of flammable or combustible substances. Storage rooms or cabinets
containing sealed radioactive sources should be locked, monitored routinely, and posted.
DOE G 441.1-1C 199
5-19-08
Radiation and contamination monitoring of the sealed radioactive source storage area or
facility should be performed before its initial use and periodically thereafter. Monitoring shall be
performed whenever changes in status (e.g., receipt of a new sealed radioactive source,
modification to shielding) are made that may significantly affect radiological conditions
[10 CFR 835.401(a)(3)].
Proper storage practices should be used to limit unauthorized use of a sealed radioactive
source and to minimize the potential for sealed radioactive source rupture, excessive personnel
exposure, or loss of the sealed radioactive source.
Section 158
15.5 Inventory
Except for certain circumstances discussed below, all accountable sealed radioactive
sources shall be inventoried at intervals not to exceed six months. These inventories shall
accomplish the following:
establish the physical location of each source;
verify the presence and adequacy of associated postings and labels; and
establish the adequacy of storage locations, containers, and devices
[10 CFR 835.1202(a)].
The presence and adequacy of postings and labels and adequacy of storage locations may
be assured through verification that these features have been established and maintained
consistent with the guidance provided in this Guide. Upon determination that an accountable
sealed radioactive source has been lost or is not stored, posted, and labeled consistent with
10 CFR 835, the RCO should be notified.
Although exempt sealed radioactive sources are not required to be inventoried, steps
should be taken to prevent the loss of these sources, regardless of activity, as required by
10 CFR 835.1201. Measures should be implemented to restrict the removal of sources from
specified locations and, when sources are moved, to administratively track source locations.
Appendices 15.A and 15.B are examples of typical accountable sealed radioactive source
accountability forms. A form similar to Appendix 15.A should be completed for each new
source. This form should cover initial receipt and registration of the source, changes in source
status (e.g., disposal, new use, failure of a leak test), custodian information, and initial/receipt
leak testing information. As changes occur in the source status or the source custodian,
applicable portions of the form should be updated as necessary. For example, if the source is
transferred, that portion of the form should be revised by the source custodian and the updated
form sent to the responsible RCO.
The site organization responsible for sealed radioactive source accountability (i.e., the RCO
or delegated organization) should maintain an individual form similar to the one in Appendix
15.A for each accountable sealed radioactive source at each facility. Each source custodian
should also maintain a form for each accountable sealed radioactive source under their
responsibility.
DOE G 441.1-1C 200
5-19-08
A form similar to the one in Appendix 15.B should be provided to the source custodian
when inventory checks and/or leak tests are scheduled. This form should be completed and a
copy sent to the responsible RCO to update the accountability records. It is recommended
that the source custodian schedule the conduct of the periodic leak tests for all of the sealed
radioactive sources under his or her responsibility. The inventories may be done by the
source custodian or the RCO (at the time of the leak testing).
Most accountable sealed radioactive sources are used in a location near their radioactive
material storage location. Some portable survey instruments and fixed-location detection
systems have check sources with activities high enough to classify them as accountable sealed
radioactive sources. The source custodian is not required to know the exact location of each
check source affixed to a portable survey instrument because radiological control technicians
frequently carry such instruments from facility to facility. Notifying the source custodian each
time a portable survey instrument with an accountable check source is moved is not required.
Therefore, the source custodian for check sources in portable survey instruments and
fixed-location detection systems should be an individual in the calibration facility who can
perform the inventory check and get the leak test performed.
Section 159
Similarly, notification of the RCO should not be required for the movement of any
accountable sealed radioactive source as long as it is being used according to approved
operations (e.g., according to a procedure or radiological work permit) as long as the source
will be returned to its original storage location.
15.6 Leak Testing
Except for those sources consisting solely of gaseous radioactive material or tritium,
accountable sealed radioactive sources shall undergo a source leak test upon receipt, when
damage is suspected, and at least every six months [10 CFR 835.1202(b)]. A leak test should
be performed prior to initial use of an accountable sealed radioactive source and when any
measurable contamination is detected on handling or storage equipment (unless the
contamination is known to be from another source).
The integrity of an accountable sealed radioactive source should be established by a wipe
test or other leak test method as recommended in ISO/DIS Report 9978, Radiation Protection
Sealed Radioactive Sources Leakage Test Methods (ISO 1990); ISO/TR Report 4826, Sealed
Radioactive Sources - Leak Test Methods (ISO 1979); ISO Report 1677, Sealed Radioactive
Sources - General (ISO 1977); NCRP Report No. 40, Protection Against Radiation from
Brachytherapy Sources (NCRP 1972); and ANSI/HPS N43.6-1997, Sealed Radioactive Sources,
Classification (ANSI/HPS 1997b). Appendix V of NUREG-1556, Volume 11, Consolidated
Guidance About Materials Licenses (NRC 1998), provides an acceptable procedure for
performing source leak tests.
Electroplated sources should not be tested for leakage by wiping the foil directly. An
indication of leakage can be obtained by checking the storage container for radioactivity or by
checking the exhaust ports of items such as gas chromatography devices (ICRP 1977). The
integrity of an accountable sealed radioactive source contained within a shield or device may
be checked by wiping the area where contamination is most likely to occur from a failure of
source integrity. If it is necessary to provide direct access to such a source to perform an
DOE G 441.1-1C 201
5-19-08
adequate leak test, then appropriate controls should be established in accordance with
10 CFR 835, the RCS, and the manufacturer’s directions. Due to the high whole body or
extremity doses that can result, leak tests on high activity sources should never be performed
by direct contact. Remote handling devices or indirect monitoring techniques, such as
monitoring of exhaust ports or accessible areas likely to be contaminated by a leaking source,
should be used.
If analysis of the leak test sample (e.g., smear) indicates that the sample has removed less
than 0.005 microcurie (185 Bq) from the area wiped, then the leakage may be considered to
be less than the 10 CFR 835.1202(b) maximum leakage criterion of 0.005 microcurie (185 Bq).
For indirect monitoring techniques, the presence of any detectable removable contamination
should be evaluated to determine if the source leakage is greater than the 10 CFR 835.1202(b)
maximum leakage criterion of 0.005 microcurie (185 Bq).
An accountable sealed radioactive source is not subject to periodic source leak testing if
that source has been removed from service. However, unless leak testing is precluded by
other radiological safety considerations, these sources should be leak tested periodically to
determine the condition of the source. Such sources shall be stored in a controlled location,
subject to periodic inventory, and subject to source leak testing prior to being returned to
service [10 CFR 835.1202(c)]. Additionally, a documented and updated accountable sealed
radioactive source form similar to Appendix 15.A should be maintained for each accountable
sealed radioactive source, recording the last known leak test.
Section 160
An accountable sealed radioactive source is not subject to periodic inventory and source
leak testing if that source is located in an area that is unsafe for human entry or otherwise
inaccessible, e.g., oxygen deficient or very high radiation areas [10 CFR 835.1202(d)]. If a
source is removed from the unsafe area or otherwise becomes accessible, then this exception
would no longer apply. This provision is not applicable to sources that are located in
instruments or other devices located in accessible areas, nor should it be applied to sources
that may be considered inaccessible due to radiological conditions created by the presence of
the source itself; leak tests may be performed on these sources by wiping the instrument or
device consistent with the guidance provided above. If a source is determined to be
inaccessible for inventory and source leak testing, then appropriate measures should be
implemented to control access to the affected area and to monitor for the presence of
contamination that may be spread as a result of source failure (See Chapter 11). When the
conditions that resulted in the area being inaccessible have been eliminated, the required
inventories and source leak tests should be completed prior to rescinding these measures.
The source custodian should be responsible for ensuring that source leak tests of
accountable sealed radioactive sources are conducted at least every six months. If a sealed
radioactive source cannot be leak tested at the proper time, the source should be removed
from service until the leak test is performed. If a source is installed in an inaccessible area, the
device should not be used until the source has been leak tested.
A test result that reveals the presence of removable radioactivity on the non-radioactive
surfaces is an indication that the sealed radioactive source has lost its integrity. The leaking
source shall be controlled in a manner that minimizes the spread of radioactive contamination
[10 CFR 835.1202(e)]. Any sealed radioactive source that fails a leak test should be
DOE G 441.1-1C 202
5-19-08
immediately removed from service and controlled in accordance with contamination control
practices defined in 10 CFR 835. The source should be placed in a separate container to
prevent the spread of contamination. All personnel and equipment that were in contact with
the leaking source should be checked for contamination; this includes transportation vehicles
and the work site. The source custodian, working with the RCO, should either return the
leaking source to the manufacturer or send it to other qualified personnel for repair or
disposal. Refer to Chapter 7 for additional guidance.
15.7 Handling and Disposal
Certain sealed radioactive sources may create significant localized radiation fields under
both normal and abnormal operating conditions. Receipt, storage, use, and disposal of sealed
radioactive sources should be conducted in accordance with 10 CFR 835, applicable DOE
Orders, consensus standards, and the following guidance:
For specific guidance on maintenance of records, see Chapter 13;
For ALARA practices, see Chapter 4;
For posting and labeling practices, see Chapter 12;
For specific guidance regarding external dosimetry considerations, see Chapter 6; and
For specific contamination controls that should be considered for leaking sealed
radioactive sources, see Chapter 11.
Section 161
Off-site sealed radioactive sources, including radiography sources, should not be brought
on-site by external organizations without the prior written approval of the RCO.
Radiation protection precautions, dose reduction methods, and special dosimetry and
monitoring requirements should be specifically identified in procedures for use of accountable
sealed radioactive sources capable of generating external radiation fields in excess of 100
millirem/hour (1 mSv/hour) at 30 cm. Radiation monitoring should be performed during and
after use of such sources to verify the adequacy of controls, posting of immediate and
adjacent areas, and return of the source to a safe condition.
Immediately upon determination of the loss of a sealed radioactive source, the user
should notify the source custodian who in turn should notify the RCO. A formal search of all
designated use locations, likely transfer paths, and possible collection points for the source
should be performed. In addition, an investigation should be conducted by facility
management to determine the root cause of the loss.
Obsolete, excess, or leaking sealed radioactive sources should be disposed of according to
RCO instructions. The source inventory requirements of 10 CFR 835 Subpart M are still
applicable while the sealed radioactive sources are awaiting disposition.
DOE G 441.1-1C 203
5-19-08
Appendix 15.A Example Individual Accountable Sealed Radioactive Source Form
Individual Accountable Sealed Radioactive Source Form
SOURCE DESCRIPTION
Source Model and Serial Number: ______________________
Electronic Label (as applicable): _______________________
Manufacturer: _____________________________________
Radionuclide(s): ___________________________________ Radiation Type:
_____________________________
Chemical Formula: _________________________________ Physical Form:_______________________
Original Activity:___________________________________ Date of Original Assay: ________________
Physical Description:
___________________________________________________________________________
Radiation Reading at Reference Distance:
___________________________________________________________
SOURCE STATUS
Date of Receipt:____________________________________ Date of Update: _____________________
Status Change: Active - in use Source integrity failed New Source - Initial Entry
Lost In storage Awaiting disposal Transferred to new location
Disposed Returned to manuf. Decayed below accountability threshold
SHIPPING RECORDS (if transferred to off-site location)
Shipping Order Number: -
________________________________________________________________________
Shipping Organization:
_________________________________________________________________________
Individual Receiving Source:
____________________________________________________________________
SOURCE CUSTODIAN
Custodian's Name: __________________________________ Badge
Number:_____________________________
Mailing Address: ___________________________________ Phone
Number:_____________________________
SOURCE LOCATION
Facility: __________________________________________ Room:
Location Within Room: _____________________________
Device Model and Serial Number: ______________________
INITIAL/RECEIPT LEAK TEST
DOE G 441.1-1C 204
5-19-08
Date of Test: _______________________________________
Type of Instrument Used:_____________________________ Instrument ID
Number:________________________
Section 162
Surveyor's Name and Badge
Number:_______________________________________________________________
Test Results:
__________________________________________________________________________________
DOE G 441.1-1C 205
5-19-08
Appendix 15.B – Example Sealed Radioactive Source Accountability Form
Sealed Radioactive Source Accountability Form
Date:__________________ Surveyor's Name and Badge Number (Print):
______________________
Instrument Type Identification
Number Date Calibrated Minimum
Detectable Activity Background (cpm)
A.
B.
C.
Source
Model
&
Serial
Number
Radionu
clide
&
Activity
Date of
Last Leak Test
Instrum
ent(s) Used
Total
Counts
Net
Counts
Net
Activity
Posting
/ Labeling
Check
Signature: ______________________________________
DOE G 441.1-1C 206
5-19-08
16.0 TECHNICAL TABLES FOR OCCUPATIONAL RADIATION
PROTECTION
Appendix A
Derived Air Concentrations (DAC) For Controlling Radiation Exposure To Workers At
DOE Facilities
The data presented in appendix A are to be used for controlling individual internal doses in
accordance with § 835.209, identifying the need for air monitoring in accordance with
§ 835.403, and identifying and posting airborne radioactivity areas in accordance with
§ 835.603(d).
The DAC values are given for individual radionuclides. For known mixtures of radionuclides,
determine the sum of the ratio of the observed concentration of a particular radionuclide
and its corresponding DAC for all radionuclides in the mixture. If this sum exceeds unity (1),
then the DAC has been exceeded. For unknown radionuclides, the most restrictive DAC
(lowest value) for those isotopes not known to be absent shall be used. For any single
radionuclide not listed in appendix A with decay mode other than alpha emission or
spontaneous fission and with radioactive half-life greater than two hours, the DAC value
shall be 4 E−11 µCi/mL (1 Bq/m3). For any single radionuclide not listed in appendix A that
decays by alpha emission or spontaneous fission the DAC value shall be 2 E−13 µCi/mL (8
E−03 Bq/m3).
The DACs for limiting radiation exposures through inhalation of radionuclides by workers are
listed in this appendix. The values are based on either a stochastic (committed effective
dose) dose limit of 5 rems (0.05 Sv) or a deterministic (organ or tissue) dose limit of 50 rems
(0.5 Sv) per year, whichever is more limiting.
Note: the 15 rems (0.15 Sv) dose limit for the lens of the eye does not appear as a critical
organ dose limit.
The columns in this appendix contain the following information: (1) Radionuclide; (2)
inhaled air DAC for type F (fast), type M (moderate), and type S (slow) materials in units of
µCi/mL; (3) inhaled air DAC for type F (fast), type M (moderate), and type S (slow) materials
in units of Bq/m3; (4) an indication of whether or not the DAC for each class is controlled by
the stochastic (effective dose) or deterministic (organ or tissue) dose. The absorption types
(F, M, and S) have been established to describe the absorption type of the materials from
the respiratory tract into the blood. The range of half-times for the absorption types
correspond to: Type F, 100% at 10 minutes; Type M, 10% at 10 minutes and 90% at 140
days; and Type S 0.1% at 10 minutes and 99.9% at 7000 days. The DACs are listed by
radionuclide, in order of increasing atomic mass, and are based on the assumption that the
particle size distribution of 5 micrometers AMAD is used. For situations where the particle
size distribution is known to differ significantly from 5 micrometers AMAD, appropriate
corrections may be made to both the estimated dose to workers and the DACs.
Section 163
DOE G 441.1-1C 207
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
H-3 (Water)
2
2
E−05
2
E−05
2
E−05
7
E+05
7
E+05
7
E+05
St/St/
St
H-3 (Elemental)
2
2
E−01
2
E−01
2
E−01
9
E+9
9
E+9
9
E+9
St/St/
St
STC
(Insoluble)
4
1
E−05
6
E−06
2
E−06
3
E+05
2
E+05
8
E+04
St/St/
St
STC (Soluble)
1
E−05
1
E−05
1
E−05
5
E+05
5
E+05
5
E+05
St/St/
St
Be-7
-
1
E−05
1
E−05
-
4
E+05
4
E+05
/St/St
Be-10
-
8
E−08
2
E−08
-
3
E+03
1
E+03
/St/St
C-11(Vapor)
2
-
1
E−04
-
-
6
E+06
-
/St/
C-11 (CO)
2
4
E−04
4
E−04
4
E−04
1
E+07
1
E+07
1
E+07
St/St/
St
C-11 (CO2)
2
2
E−04
2
E−04
2
E−04
9
E+06
9
E+06
9
E+06
St/St/
St
C-14(Vapor)
2
-
9
E−07
-
-
3
E+04
-
/St/
C-14 (CO)
2
7
E−04
7
E−04
7
E−04
2
E+07
2
E+07
2
E+07
St/St/
St
C-14 (CO2)
2
8
E−05
8
E−05
8
E−05
3
E+06
3
E+06
3
E+06
St/St/
St
F-18
4
E−06
3
E−06
3
E−06
1
E+05
1
E+05
1
E+05
ET/ET
/ET
Na-22
2
E−07
-
-
1
E+04
-
-
E/ /
Na-24
4
E−07
-
-
1
E+04
-
-
ET/ /
DOE G 441.1-1C 208
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Mg-28
3
E−07
3
E−07
-
1
E+04
1
E+04
-
ET/St
/
Al-26
4
E−08
4
E−08
-
1
E+03
1
E+03
-
St/St/
Si-31
9
E−06
5
E−06
5
E−06
3
E+05
1
E+05
1
E+05
ET/St
/St
Si-32
1
E−07
5
E−08
1
E−08
5
E+03
2
E+03
3
E+02
St/St/
St
P-32
5
E−07
1
E−07
-
1
E+04
7
E+03
-
St/St/
P-33
4
E−06
4
E−07
-
1
E+05
1
E+04
-
St/St/
S-35 (Vapor)
-
4
E−06
-
-
1
E+05
-
/St/
S-35
7
E−06
5
E−07
-
2
E+05
1
E+04
-
St/St/
Cl-36
1
E−06
1
E−07
-
4
E+04
4
E+03
-
St/St/
Cl-38
7
E−06
5
E−06
-
2
E+05
2
E+05
-
ET/ET
/
Cl-39
2
E−06
4
E−06
-
1
E+05
1
E+05
-
ET/ET
/
K-40
1
E−07
-
-
6
E+03
-
-
St/ /
K-42
2
E−06
-
-
1
E+05
-
-
E/ /
K-43
9
E−07
-
-
3
E+04
-
-
ET/ /
K-44
8
E−06
-
-
2
E+05
-
-
ET/ /
DOE G 441.1-1C 209
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
K-45
9
E−06
-
-
3
E+05
-
-
ET/ /
Ca-41
-
2
E−06
-
-
8
E+04
-
/BS/
Ca-45
-
2
E−07
-
-
9
E+03
-
/St/
Ca-47
-
2
E−07
-
-
9
E+03
-
/St/
Sc-43
-
-
2
E−06
-
-
7
E+04
/
/ET
Sc-44m
-
-
2
E−07
-
-
1
E+04
/
/St
Sc-44
-
-
1
E−06
-
-
4
E+04
/
/ET
Sc-46
-
-
1
E−07
-
-
4
E+03
/
/St
Sc-47
-
-
7
E−07
-
-
2
E+04
/
/St
Sc-48
-
-
2
E−07
-
-
1
E+04
/
/ET
Sc-49
-
-
8
E−06
-
-
3
E+05
/
/ET
Ti-44
7
E−09
2
E−08
9
E−09
2
E+02
7
E+02
3
E+02
St/St/
St
Ti-45
3
E−06
2
E−06
2
E−06
1
E+05
1
E+05
1
E+05
ET/ET
/ET
V-47
8
E−06
6
E−06
-
3
E+05
2
E+05
-
ET/ET
/
V-48
2
E−07
2
E−07
-
9
E+03
7
E+03
-
ET/St
/
DOE G 441.1-1C 210
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
V-49
1
E−05
2
E−05
-
7
E+05
9
E+05
-
BS/St
/
Cr-48
2
E−06
2
E−06
2
E−06
8
E+04
8
E+04
8
E+04
ET/ET
/ET
Cr-49
7
E−06
5
E−06
5
E−06
2
E+05
2
E+05
2
Section 164
E+05
ET/ET
/ET
Cr-51
1
E−05
1
E−05
1
E−05
6
E+05
6
E+05
5
E+05
St/St/
St
Mn-51
7
E−06
5
E−06
-
2
E+05
2
E+05
-
ET/ET
/
Mn-52m
7
E−06
5
E−06
-
2
E+05
2
E+05
-
ET/ET
/
Mn-52
2
E−07
2
E−07
-
8
E+03
8
E+03
-
ET/ET
/
Mn-53
5
E−06
1
E−05
-
2
E+05
5
E+05
-
BS/St
/
Mn-54
5
E−07
4
E−07
-
1
E+04
1
E+04
-
St/St/
Mn-56
2
E−06
2
E−06
-
9
E+04
8
E+04
-
ET/ET
/
Fe–52
6
E−07
5
E−07
-
2
E+04
2
E+04
-
ET/E/
Fe-55
6
E−07
1
E−06
-
2
E+04
6
E+04
-
St/St/
Fe-59
1
E−07
1
E−07
-
6
E+03
6
E+03
-
St/St/
Fe-60
1
E−09
4
E−09
-
6
E+01
1
E+02
-
St/St/
Co-55
-
5
E−07
5
E−07
-
2
E+04
2
E+04
/ET/ET
DOE G 441.1-1C 211
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Co-56
-
1
E−07
1
E−07
-
5
E+03
4
E+03
/St/St
Co-57
-
1
E−06
9
E−07
-
5
E+04
3
E+04
/St/St
Co-58m
-
3
E−05
3
E−05
-
1
E+06
1
E+06
/St/St
Co-58
-
4
E−07
3
E−07
-
1
E+04
1
E+04
/St/St
Co-60m
-
4
E−04
4
E−04
-
1
E+07
1
E+07
/St/St
Co-60
-
7
E−08
3
E−08
-
2
E+03
1
E+03
/St/St
Co-61
-
6
E−06
6
E−06
-
2
E+05
2
E+05
/ET/ET
Co-62m
-
7
E−06
6
E−06
-
2
E+05
2
E+05
/ET/ET
Ni-56 (Inorg)
4
E−07
4
E−07
-
1
E+04
1
E+04
-
ET/ET/
Ni-56 (Carbonyl)
-
4
E−07
-
-
1
E+04
-
/St/
Ni-57 (Inorg)
5
E−07
5
E−07
-
2
E+04
2
E+04
-
ET/ET
/
Ni-57 (Carbonyl)
-
7
E−07
-
-
2
E+04
-
/ET/
Ni-59 (Inorg)
2
E−06
5
E−06
-
9
E+04
2
E+05
-
St/St/
Ni-59 (Carbonyl)
-
6
E−07
-
-
2
E+04
-
/St/
Ni-63 (Inorg)
1
E−06
1
E−06
-
4
E+04
6
E+04
-
St/St/
DOE G 441.1-1C 212
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Ni-63 (Carbonyl)
-
2
E−07
-
-
1
E+04
-
/St/
Ni-65 (Inorg)
5
E−06
4
E−06
-
1
E+05
1
E+05
-
ET/ET
/
Ni-65 (Carbonyl)
-
8
E−07
-
-
3
E+04
-
/ET/
Ni-66 (Inorg)
7
E−07
2
E−07
-
2
E+04
1
E+04
-
St/St/
Ni-66 (Carbonyl)
-
2
E−07
-
-
1
E+04
-
/ET/
Cu-60
5
E−06
4
E−06
4
E−06
1
E+05
1
E+05
1
E+05
ET/ET
/ET
Cu-61
3
E−06
3
E−06
3
E−06
1
E+05
1
E+05
1
E+05
ET/ET
/ET
Cu-64
4
E−06
3
E−06
3
E−06
1
E+05
1
E+05
1
E+05
ET/E/
E
Cu-67
2
E−06
1
E−06
9
E−07
8
E+04
3
E+04
3
E+04
ET/St
/St
Zn-62
-
-
8
E−07
-
-
3
E+04
/
/St
Zn-63
-
-
5
E−06
-
-
2
E+05
/
/ET
Zn-65
-
-
2
E−07
-
-
7
E+03
/
/St
Zn-69m
-
-
1
E−06
-
-
6
E+04
/
/St
Zn-69
-
-
7
E−06
-
-
2
E+05
/
/ET
Zn-71m
-
-
1
E−06
-
-
5
E+04
/
/ET
DOE G 441.1-1C 213
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Zn-72
-
-
3
E−07
-
-
1
E+04
/
/St
Ga-65
1
E−05
9
E−06
-
4
E+05
3
E+05
-
ET/ET
/
Ga-66
8
E−07
7
E−07
-
3
E+04
2
E+04
-
ET/St
/
Ga-67
3
E−06
2
E−06
-
1
E+05
7
E+04
-
ET/St
/
Ga-68
6
E−06
4
E−06
-
2
E+05
1
E+05
-
ET/ET
/
Ga-70
1
E−05
1
E−05
-
6
E+05
4
E+05
-
ET/ET
/
Ga-72
5
E−07
5
E−07
-
2
E+04
2
E+04
-
ET/ET
/
Ga-73
4
E−06
2
E−06
-
1
E+05
1
E+05
-
ET/St
/
Ge-66
2
E−06
2
E−06
-
9
E+04
Section 165
9
E+04
-
ET/ET
/
Ge-67
1
E−05
7
E−06
-
3
E+05
2
E+05
-
ET/ET
/
Ge-68
6
E−07
7
E−08
-
2
E+04
2
E+03
-
ET/St
/
Ge-69
1
E−06
1
E−06
-
3
E+04
3
E+04
-
ET/ET
/
Ge-71
5
E−05
5
E−05
-
2
E+06
1
E+06
-
ET/E/
Ge-75
1
E−05
7
E−06
-
4
E+05
2
E+05
-
ET/ET
/
Ge-77
1
E−06
1
E−06
-
4
E+04
4
E+04
-
ET/ET
/
DOE G 441.1-1C 214
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Ge-78
3
E−06
3
E−06
-
1
E+05
1
E+05
-
ET/ET
/
As-69
-
9
E−06
-
-
3
E+05
-
/ET/
As-70
-
2
E−06
-
-
8
E+04
-
/ET/
As-71
-
1
E−06
-
-
4
E+04
-
/St/
As-72
-
4
E−07
-
-
1
E+04
-
/St/
As-73
-
8
E−07
-
-
3
E+04
-
/St/
As-74
-
3
E−07
-
-
1
E+04
-
/St/
As-76
-
6
E−07
-
-
2
E+04
-
/St/
As-77
-
1
E−06
-
-
4
E+04
-
/St/
As-78
-
3
E−06
-
-
1
E+05
-
/ET/
Se-70
2
E−06
2
E−06
-
1
E+05
9
E+04
-
ET/ET
/
Se-73m
1
E−05
1
E−05
-
5
E+05
4
E+05
-
ET/ET
/
Se-73
1
E−06
1
E−06
-
6
E+04
5
E+04
-
ET/ET
/
Se-75
4
E−07
3
E−07
-
1
E+04
1
E+04
-
St/St/
Se-79
3
E−07
1
E−07
-
1
E+04
6
E+03
-
K/St/
DOE G 441.1-1C 215
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Se-81m
1
E−05
6
E−06
-
3
E+05
2
E+05
-
ET/ET
/
Se-81
1
E−05
1
E−05
-
6
E+05
4
E+05
-
ET/ET
/
Se-83
6
E−06
5
E−06
-
2
E+05
1
E+05
-
ET/ET
/
Br-74m
3
E−06
2
E−06
-
1
E+05
1
E+05
-
ET/ET
/
Br-74
4
E−06
4
E−06
-
1
E+05
1
E+05
-
ET/ET
/
Br-75
4
E−06
3
E−06
-
1
E+05
1
E+05
-
ET/ET
/
Br-76
5
E−07
5
E−07
-
2
E+04
2
E+04
-
ET/ET
/
Br-77
2
E−06
2
E−06
-
7
E+04
7
E+04
-
ET/ET
/
Br-80m
6
E−06
5
E−06
-
2
E+05
2
E+05
-
ET/St
/
Br-80
3
E−05
2
E−05
-
1
E+06
7
E+05
-
ET/ET
/
Br-82
3
E−07
3
E−07
-
1
E+04
1
E+04
-
ET/ET
/
Br-83
9
E−06
6
E−06
-
3
E+05
2
E+05
-
ET/ET
/
Br-84
7
E−06
5
E−06
-
2
E+05
2
E+05
-
ET/ET
/
Rb-79
8
E−06
-
-
2
E+05
-
-
ET/ /
Rb-81m
1
E−05
-
-
6
E+05
-
-
ET/ /
DOE G 441.1-1C 216
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Rb-81
2
E−06
-
-
1
E+05
-
-
ET/ /
Rb-82m
8
E−07
-
-
3
E+04
-
-
ET/ /
Rb-83
5
E−07
-
-
2
E+04
-
-
St/ /
Rb-84
3
E−07
-
-
1
E+04
-
-
St/ /
Rb-86
4
E−07
-
-
1
E+04
-
-
St/ /
Rb-87
7
E−07
-
-
2
E+04
-
-
St/ /
Rb-88
1
E−05
-
-
5
E+05
-
-
ET/ /
Rb-89
1
E−05
-
-
3
E+05
-
-
ET/ /
Sr-80
3
E−06
-
2
E−06
1
E+05
-
9
E+04
ET/
/St
Sr-81
7
E−06
-
5
E−06
2
E+05
-
2
E+05
ET/
/ET
Sr-82
1
E−07
-
7
E−08
6
E+03
-
2
E+03
St/
/St
Sr-83
1
E−06
-
9
E−07
3
E+04
-
3
E+04
ET/
/ET
Sr-85m
4
E−05
-
3
E−05
1
E+06
-
1
E+06
ET/
/ET
Sr-85
1
E−06
-
8
E−07
3
E+04
-
3
E+04
St/
/St
Sr-87m
1
E−05
-
9
E−06
4
E+05
-
3
E+05
ET/
/ET
DOE G 441.1-1C 217
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Sr-89
4
E−07
-
1
E−07
1
E+04
-
3
E+03
St/
/St
Section 166
Sr-90
1
E−08
-
7
E−09
4
E+02
-
2
E+02
BS/
/St
Sr-91
1
E−06
-
9
E−07
5
E+04
-
3
E+04
ET/
/St
Sr-92
2
E−06
-
1
E−06
8
E+04
-
6
E+04
ET/
/St
Y-86m
-
7
E−06
6
E−06
-
2
E+05
2
E+05
/ET/ET
Y-86
-
4
E−07
4
E−07
-
1
E+04
1
E+04
/ET/ET
Y-87
-
9
E−07
8
E−07
-
3
E+04
3
E+04
/ET/ET
Y-88
-
1
E−07
1
E−07
-
6
E+03
6
E+03
/St/St
Y-90m
-
4
E−06
4
E−06
-
1
E+05
1
E+05
/St/St
Y-90
-
3
E−07
3
E−07
-
1
E+04
1
E+04
/St/St
Y-91m
-
2
E−05
2
E−05
-
7
E+05
7
E+05
/ET/ET
Y-91
-
1
E−07
9
E−08
-
4
E+03
3
E+03
/St/St
Y-92
-
2
E−06
2
E−06
-
7
E+04
7
E+04
/St/St
Y-93
-
9
E−07
9
E−07
-
3
E+04
3
E+04
/St/St
Y-94
-
8
E−06
8
E−06
-
3
E+05
3
E+05
/ET/ET
DOE G 441.1-1C 218
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Y-95
-
1
E−05
1
E−05
-
4
E+05
4
E+05
/ET/ET
Zr-86
5
E−07
5
E−07
5
E−07
2
E+04
2
E+04
2
E+04
ET/ET
/ET
Zr-88
1
E−07
3
E−07
3
E−07
5
E+03
1
E+04
1
E+04
St/St/
St
Zr-89
6
E−07
6
E−07
6
E−07
2
E+04
2
E+04
2
E+04
ET/ET
/ET
Zr-93
3
E−09
1
E−08
1
E−07
1
E+02
6
E+02
5
E+03
BS/BS
/BS
Zr-95
9
E−08
1
E−07
1
E−07
3
E+03
5
E+03
4
E+03
BS/St
/St
Zr-97
7
E−07
4
E−07
4
E−07
2
E+04
1
E+04
1
E+04
ET/St
/St
Nb-88
-
5
E−06
5
E−06
-
1
E+05
1
E+05
/ET/ET
Nb-89 (66 min)
-
3
E−06
3
E−06
-
1
E+05
1
E+05
/ET/ET
Nb-89 (122 min)
-
2
E−06
2
E−06
-
1
E+05
1
E+05
/ET/ET
Nb-90
-
3
E−07
3
E−07
-
1
E+04
1
E+04
/ET/ET
Nb-93m
-
1
E−06
6
E−07
-
7
E+04
2
E+04
/St/St
Nb-94
-
7
E−08
2
E−08
-
2
E+03
8
E+02
/St/St
Nb-95m
-
7
E−07
6
E−07
-
2
E+04
2
E+04
/St/St
Nb-95
-
4
E−07
4
E−07
-
1
E+04
1
E+04
/St/St
DOE G 441.1-1C 219
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Nb-96
-
4
E−07
4
E−07
-
1
E+04
1
E+04
/ET/ET
Nb-97
-
5
E−06
5
E−06
-
1
E+05
1
E+05
/ET/ET
Nb-98
-
3
E−06
3
E−06
-
1
E+05
1
E+05
/ET/ET
Mo-90
8
E−07
-
7
E−07
3
E+04
-
2
E+04
ET/
/ET
Mo-93m
1
E−06
-
1
E−06
3
E+04
-
3
E+04
ET/
/ET
Mo-93
2
E−07
-
4
E−07
7
E+03
-
1
E+04
BS/
/St
Mo-99
1
E−06
-
5
E−07
5
E+04
-
1
E+04
E/
/St
Mo-101
8
E−06
-
6
E−06
3
E+05
-
2
E+05
ET/
/ET
Tc-93m
8
E−06
7
E−06
-
3
E+05
2
E+05
-
ET/ET
/
Tc-93
3
E−06
3
E−06
-
1
E+05
1
E+05
-
ET/ET
/
Tc-94m
5
E−06
4
E−06
-
1
E+05
1
E+05
-
ET/ET
/
Tc-94
1
E−06
1
E−06
-
4
E+04
3
E+04
-
ET/ET
/
Tc-95m
8
E−07
6
E−07
-
3
E+04
2
E+04
-
ET/St
/
Tc-95
1
E−06
1
E−06
-
5
E+04
5
E+04
-
ET/ET
/
Tc-96m
2
E−05
2
E−05
-
1
E+06
1
E+06
-
ET/ET
/
DOE G 441.1-1C 220
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Tc-96
3
E−07
3
E−07
-
1
E+04
1
E+04
-
ET/ET
/
Tc-97m
1
E−06
2
E−07
-
5
E+04
7
E+03
-
St/St/
Tc-97
4
E−06
3
E−06
-
1
E+05
1
E+05
-
ET/St
/
Tc-98
3
E−07
9
E−08
-
1
E+04
3
E+03
-
St/St/
Tc-99m
1
E−05
1
E−05
-
5
E+05
4
E+05
-
ET/ET
/
Tc-99
1
E−06
1
E−07
-
5
E+04
6
E+03
-
St/St/
Section 167
Tc-101
1
E−05
1
E−05
-
6
E+05
4
E+05
-
ET/ET
/
Tc-104
9
E−06
7
E−06
-
3
E+05
2
E+05
-
ET/ET
/
Ru-94
5
E−06
5
E−06
5
E−06
2
E+05
1
E+05
1
E+05
ET/ET
/ET
Ru-97
2
E−06
2
E−06
2
E−06
8
E+04
8
E+04
8
E+04
ET/ET
/ET
Ru-103
8
E−07
2
E−07
2
E−07
3
E+04
1
E+04
9
E+03
St/St/
St
Ru-105
2
E−06
2
E−06
2
E−06
9
E+04
8
E+04
8
E+04
ET/ET
/ET
Ru-106
5
E−08
3
E−08
1
E−08
2
E+03
1
E+03
5
E+02
St/St/
St
Rh-99m
3
E−06
3
E−06
3
E−06
1
E+05
1
E+05
1
E+05
ET/ET
/ET
Rh-99
8
E−07
6
E−07
6
E−07
3
E+04
2
E+04
2
E+04
ET/St
/St
DOE G 441.1-1C 221
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Rh-100
5
E−07
5
E−07
5
E−07
1
E+04
1
E+04
1
E+04
ET/ET
/ET
Rh-101m
1
E−06
1
E−06
1
E−06
6
E+04
6
E+04
6
E+04
ET/ET
/ET
Rh-101
3
E−07
3
E−07
1
E−07
1
E+04
1
E+04
6
E+03
St/St/
St
Rh-102m
2
E−07
2
E−07
1
E−07
1
E+04
7
E+03
4
E+03
St/St/
St
Rh-102
6
E−08
1
E−07
6
E−08
2
E+03
4
E+03
2
E+03
St/St/
St
Rh-103m
4
E−04
2
E−04
2
E−04
1
E+07
8
E+06
8
E+06
St/St/
St
Rh-105
3
E−06
1
E−06
1
E−06
1
E+05
5
E+04
4
E+04
ET/St
/St
Rh-106m
1
E−06
1
E−06
1
E−06
6
E+04
5
E+04
5
E+04
ET/ET
/ET
Rh-107
1
E−05
9
E−06
9
E−06
5
E+05
3
E+05
3
E+05
ET/ET
/ET
Pd-100
5
E−07
5
E−07
5
E−07
2
E+04
2
E+04
2
E+04
ET/ET
/ET
Pd-101
3
E−06
3
E−06
3
E−06
1
E+05
1
E+05
1
E+05
ET/ET
/ET
Pd-103
4
E−06
1
E−06
1
E−06
1
E+05
6
E+04
7
E+04
E/St/
St
Pd-107
1
E−05
1
E−05
1
E−06
5
E+05
4
E+05
7
E+04
K/St/
St
Pd-109
2
E−06
1
E−06
1
E−06
9
E+04
4
E+04
4
E+04
St/St/
St
Ag-102
9
E−06
7
E−06
7
E−06
3
E+05
2
E+05
2
E+05
ET/ET
/ET
DOE G 441.1-1C 222
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Ag-103
8
E−06
7
E−06
7
E−06
3
E+05
2
E+05
2
E+05
ET/ET
/ET
Ag-104m
8
E−06
6
E−06
6
E−06
2
E+05
2
E+05
2
E+05
ET/ET
/ET
Ag-104
3
E−06
3
E−06
3
E−06
1
E+05
1
E+05
1
E+05
ET/ET
/ET
Ag-105
7
E−07
8
E−07
7
E−07
2
E+04
2
E+04
2
E+04
St/St/
St
Ag-106m
2
E−07
2
E−07
2
E−07
9
E+03
9
E+03
9
E+03
ET/ET
/ET
Ag-106
1
E−05
1
E−05
1
E−05
5
E+05
4
E+05
4
E+05
ET/ET
/ET
Ag-108m
7
E−08
1
E−07
2
E−08
2
E+03
4
E+03
1
E+03
St/St/
St
Ag-110m
8
E−08
9
E−08
7
E−08
3
E+03
3
E+03
2
E+03
St/St/
St
Ag-111
9
E−07
3
E−07
3
E−07
3
E+04
1
E+04
1
E+04
St/St/
St
Ag-112
4
E−06
2
E−06
2
E−06
1
E+05
8
E+04
8
E+04
E/St/
St
Ag-115
1
E−05
8
E−06
8
E−06
4
E+05
3
E+05
3
E+05
ET/ET
/ET
Cd-104
4
E−06
4
E−06
4
E−06
1
E+05
1
E+05
1
E+05
ET/ET
/ET
Cd-107
5
E−06
5
E−06
4
E−06
2
E+05
1
E+05
1
E+05
ET/ET
/ET
Cd-109
2
E−08
9
E−08
1
E−07
9
E+02
3
E+03
4
E+03
K/K/S
t
Cd-113m
1
E−09
6
E−09
1
E−08
6
E+01
2
E+02
6
E+02
K/K/K
DOE G 441.1-1C 223
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Cd-113
1
E−09
5
E−09
1
E−08
5
E+01
2
E+02
5
E+02
K/K/K
Cd-115m
3
E−08
1
E−07
1
E−07
1
E+03
3
E+03
3
E+03
K/St/
St
Cd-115
Section 168
9
E−07
4
E−07
4
E−07
3
E+04
1
E+04
1
E+04
K/St/
St
Cd-117m
1
E−06
1
E−06
1
E−06
4
E+04
4
E+04
4
E+04
ET/ET
/ET
Cd-117
2
E−06
2
E−06
2
E−06
8
E+04
7
E+04
7
E+04
ET/ET
/ET
In-109
4
E−06
4
E−06
-
1
E+05
1
E+05
-
ET/ET
/
In-110 (69 min)
5
E−06
4
E−06
-
1
E+05
1
E+05
-
ET/ET
/
In-110 (5 h)
9
E−07
9
E−07
-
3
E+04
3
E+04
-
ET/ET
/
In-111
1
E−06
1
E−06
-
5
E+04
5
E+04
-
ET/ET
/
In-112
2
E−05
1
E−05
-
9
E+05
6
E+05
-
ET/ET
/
In-113m
1
E−05
1
E−05
-
4
E+05
3
E+05
-
ET/ET
/
In-114m
5
E−08
9
E−08
-
1
E+03
3
E+03
-
St/St/
In-115m
6
E−06
5
E−06
-
2
E+05
2
E+05
-
ET/ET
/
In-115
1
E−09
5
E−09
-
4
E+01
1
E+02
-
St/St/
In-116m
4
E−06
3
E−06
-
1
E+05
1
E+05
-
ET/ET
/
DOE G 441.1-1C 224
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
In-117m
5
E−06
4
E−06
-
2
E+05
1
E+05
-
ET/ET
/
In-117
7
E−06
5
E−06
-
2
E+05
2
E+05
-
ET/ET
/
In-119m
1
E−05
1
E−05
-
6
E+05
4
E+05
-
ET/ET
/
Sn-110
1
E−06
1
E−06
-
6
E+04
6
E+04
-
ET/ET
/
Sn-111
1
E−05
1
E−05
-
6
E+05
5
E+05
-
ET/ET
/
Sn-113
7
E−07
2
E−07
-
2
E+04
1
E+04
-
St/St/
Sn-117m
8
E−07
2
E−07
-
3
E+04
9
E+03
-
BS/St
/
Sn-119m
1
E−06
3
E−07
-
5
E+04
1
E+04
-
St/St/
Sn-121m
5
E−07
1
E−07
-
2
E+04
6
E+03
-
St/St/
Sn-121
4
E−06
2
E−06
-
1
E+05
7
E+04
-
ET/St
/
Sn-123m
1
E−05
7
E−06
-
4
E+05
2
E+05
-
ET/ET
/
Sn-123
3
E−07
1
E−07
-
1
E+04
3
E+03
-
St/St/
Sn-125
4
E−07
2
E−07
-
1
E+04
7
E+03
-
St/St/
Sn-126
4
E−08
3
E−08
-
1
E+03
1
E+03
-
St/St/
Sn-127
2
E−06
2
E−06
-
9
E+04
7
E+04
-
ET/ET
/
DOE G 441.1-1C 225
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Sn-128
2
E−06
2
E−06
-
1
E+05
8
E+04
-
ET/ET
/
Sb-115
1
E−05
1
E−05
-
5
E+05
4
E+05
-
ET/ET
/
Sb-116m
3
E−06
2
E−06
-
1
E+05
1
E+05
-
ET/ET
/
Sb-116
1
E−05
1
E−05
-
4
E+05
3
E+05
-
ET/ET
/
Sb-117
1
E−05
1
E−05
-
4
E+05
3
E+05
-
ET/ET
/
Sb-118m
1
E−06
1
E−06
-
4
E+04
4
E+04
-
ET/ET
/
Sb-119
6
E−06
6
E−06
-
2
E+05
2
E+05
-
ET/ET
/
Sb-120 (16 min)
2
E−05
2
E−05
-
1
E+06
7
E+05
-
ET/ET
/
Sb-120 (6 d)
3
E−07
3
E−07
-
1
E+04
1
E+04
-
ET/ET
/
Sb-122
8
E−07
4
E−07
-
3
E+04
1
E+04
-
St/St/
Sb-124m
4
E−05
3
E−05
-
1
E+06
1
E+06
-
ET/ET
/
Sb-124
2
E−07
1
E−07
-
1
E+04
4
E+03
-
St/St/
Sb-125
2
E−07
1
E−07
-
7
E+03
6
E+03
-
BS/St
/
Sb-126m
1
E−05
7
E−06
-
3
E+05
2
E+05
-
ET/ET
/
Sb-126
2
E−07
1
E−07
-
9
E+03
6
E+03
-
ET/St
/
DOE G 441.1-1C 226
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Sb-127
7
E−07
3
E−07
-
2
E+04
1
E+04
-
E/St/
Sb-128 (9 h)
5
E−07
5
E−07
-
2
E+04
2
E+04
-
ET/ET
/
Sb-128 (10 min)
1
E−05
9
E−06
-
4
E+05
3
E+05
-
ET/ET
/
Sb-129
1
E−06
1
E−06
-
6
E+04
5
E+04
-
ET/ET
/
Sb-130
3
E−06
2
E−06
-
1
E+05
1
E+05
-
ET/ET
/
Sb-131
6
E−06
4
E−06
-
2
E+05
1
E+05
-
ET/ET
/
Te-116 (Vapor)
Section 169
-
6
E−06
-
-
2
E+05
-
/St /
Te-116
2
E−06
2
E−06
-
8
E+04
7
E+04
-
ET/ET
/
Te-121m (Vapor)
-
4
E−08
-
-
1
E+03
-
/BS/
Te-121m
1
E−07
1
E−07
-
4
E+03
5
E+03
-
BS/St
/
Te-121 (Vapor)
-
1
E−06
-
-
4
E+04
-
/St /
Te-121
1
E−06
1
E−06
-
3
E+04
3
E+04
-
ET/ET
/
Te-123m (Vapor)
-
5
E−08
-
-
2
E+03
-
/BS/
Te-123m
1
E−07
1
E−07
-
4
E+03
6
E+03
-
BS/St
/
Te-123 (Vapor)
-
1
E−08
-
-
4
E+02
-
/BS/
DOE G 441.1-1C 227
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Te-123
2
E−08
5
E−08
-
1
E+03
1
E+03
-
BS/BS
/
Te-125m (Vapor)
-
1
E−07
-
-
3
E+03
-
/BS/
Te-125m
2
E−07
1
E−07
-
9
E+03
7
E+03
-
BS/St
/
Te-127m (Vapor)
-
6
E−08
-
-
2
E+03
-
/BS/
Te-127m
1
E−07
9
E−08
-
5
E+03
3
E+03
-
BS/St
/
Te-127 (Vapor)
-
7
E−06
-
-
2
E+05
-
/St/
Te-127
5
E−06
3
E−06
-
2
E+05
1
E+05
-
ET/St
/
Te-129m (Vapor)
-
1
E−07
-
-
5
E+03
-
/St/
Te-129m
3
E−07
1
E−07
-
1
E+04
3
E+03
-
St/St/
Te-129 (Vapor)
-
1
E−05
-
-
5
E+05
-
/St/
Te-129
1
E−05
7
E−06
-
4
E+05
2
E+05
-
ET/ET
/
Te-131m (Vapor)
-
1
E−07
-
-
5
E+03
-
/T/
Te-131m
3
E−07
3
E−07
-
1
E+04
1
E+04
-
T/St/
Te-131 (Vapor)
-
6
E−06
-
-
2
E+05
-
/T/
Te-131
1
E−05
7
E−06
-
4
E+05
2
E+05
-
ET/ET
/
DOE G 441.1-1C 228
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Te-132 (Vapor)
-
7
E−08
-
-
2
E+03
-
/T/
Te-132
1
E−07
1
E−07
-
6
E+03
6
E+03
-
T/St/
Te-133m (Vapor)
-
1
E−06
-
-
6
E+04
-
/T/
Te-133m
3
E−06
2
E−06
-
1
E+05
1
E+05
-
T/ET/
Te-133 (Vapor)
-
7
E−06
-
-
2
E+05
-
/T/
Te-133
1
E−05
9
E−06
-
4
E+05
3
E+05
-
ET/ET
/
Te-134 (Vapor)
-
6
E−06
-
-
2
E+05
-
/St/
Te-134
3
E−06
2
E−06
-
1
E+05
1
E+05
-
ET/ET
/
I-120m (Methyl)
4
E−06
-
-
1
E+05
-
-
T/ /
I-120m (Vapor)
-
3
E−06
-
-
1
E+05
-
/St /
I-120m
2
E−06
-
-
8
E+04
-
-
ET/ /
I-120 (Methyl)
1
E−06
-
-
6
E+04
-
-
T/ /
I-120 (Vapor)
-
1
E−06
-
-
5
E+04
-
/T/
I-120
2
E−06
-
-
1
E+05
-
-
E/ /
I-121 (Methyl)
5
E−06
-
-
2
E+05
-
-
T/ /
DOE G 441.1-1C 229
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
I-121 (Vapor)
-
4
E−06
-
-
1
E+05
-
/T/
I-121
8
E−06
-
-
3
E+05
-
-
T/ /
I-123 (Methyl)
1
E−06
-
-
7
E+04
-
-
T/ /
I-123 (Vapor)
-
1
E−06
-
-
5
E+04
-
/T/
I-123
2
E−06
-
-
1
E+05
-
-
T/ /
I-124 (Methyl)
3
E−08
-
-
1
E+03
-
-
T/ /
I-124 (Vapor)
-
2
E−08
-
-
9
E+02
-
/T/
I-124
4
E−08
-
-
1
E+03
-
-
T/ /
I-125 (Methyl)
2
E−08
-
-
9
E+02
-
-
T/ /
I-125 (Vapor)
-
2
E−08
-
-
7
E+02
-
/T/
I-125
3
E−08
-
-
1
E+03
-
-
T/ /
I-126 (Methyl)
1
E−08
-
-
5
E+02
-
-
T/ /
I-126 (Vapor)
-
1
E−08
-
-
4
E+02
-
/T/
I-126
2
E−08
-
-
7
E+02
-
-
T/ /
I-128 (Methyl)
3
E−05
-
-
1
E+06
-
-
T/ /
DOE G 441.1-1C 230
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
Section 170
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
I-128 (Vapor)
-
8
E−06
-
-
3
E+05
-
/St/
I-128
1
E−05
-
-
6
E+05
-
-
ET/ /
I-129 (Methyl)
3
E−09
-
-
1
E+02
-
-
T/ /
I-129 (Vapor)
-
2
E−09
-
-
1
E+02
-
/T/
I-129
5
E−09
-
-
2
E+02
-
-
T/ /
I-130 (Methyl)
2
E−07
-
-
7
E+03
-
-
T/ /
I-130 (Vapor)
-
1
E−07
-
-
6
E+03
-
/T/
I-130
3
E−07
-
-
1
E+04
-
-
T/ /
I-131 (Methyl)
1
E−08
-
-
6
E+02
-
-
T/ /
I-131 (Vapor)
-
1
E−08
-
-
5
E+02
-
/T/
I-131
2
E−08
-
-
9
E+02
-
-
T/ /
I-132m (Methyl)
1
E−06
-
-
7
E+04
-
-
T/ /
I-132m (Vapor)
-
1
E−06
-
-
6
E+04
-
/T/
I-132m
3
E−06
-
-
1
E+05
-
-
T/ /
I-132 (Methyl)
1
E−06
-
-
6
E+04
-
-
T/ /
DOE G 441.1-1C 231
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
I-132 (Vapor)
-
1
E−06
-
-
5
E+04
-
/T/
I-132
2
E−06
-
-
7
E+04
-
-
T/ /
I-133 (Methyl)
9
E−08
-
-
3
E+03
-
-
T/ /
I-133 (Vapor)
-
7
E−08
-
-
2
E+03
-
/T/
I-133
1
E−07
-
-
5
E+03
-
-
T/ /
I-134 (Methyl)
8
E−06
-
-
2
E+05
-
-
T/ /
I-134 (Vapor)
-
3
E−06
-
-
1
E+05
-
/St/
I-134
3
E−06
-
-
1
E+05
-
-
ET/ /
I-135 (Methyl)
4
E−07
-
-
1
E+04
-
-
T/ /
I-135 (Vapor)
-
3
E−07
-
-
1
E+04
-
/T/
I-135
6
E−07
-
-
2
E+04
-
-
T/ /
Cs-125
1
E−05
-
-
4
E+05
-
-
ET/ /
Cs-127
4
E−06
-
-
1
E+05
-
-
ET/ /
Cs-129
2
E−06
-
-
9
E+04
-
-
ET/ /
Cs-130
1
E−05
-
-
6
E+05
-
-
ET/ /
DOE G 441.1-1C 232
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Cs-131
7
E−06
-
-
2
E+05
-
-
ET/ /
Cs-132
9
E−07
-
-
3
E+04
-
-
ET/ /
Cs-134m
8
E−06
-
-
2
E+05
-
-
ET/ /
Cs-134
5
E−08
-
-
2
E+03
-
-
St/ /
Cs-135m
8
E−06
-
-
2
E+05
-
-
ET/ /
Cs-135
5
E−07
-
-
2
E+04
-
-
St/ /
Cs-136
2
E−07
-
-
1
E+04
-
-
E/ /
Cs-137
8
E−08
-
-
3
E+03
-
-
St/ /
Cs-138
5
E−06
-
-
2
E+05
-
-
ET/ /
Ba-126
4
E−06
-
-
1
E+05
-
-
ET/ /
Ba-128
4
E−07
-
-
1
E+04
-
-
St/ /
Ba-131m
4
E−05
-
-
1
E+06
-
-
ET/ /
Ba-131
1
E−06
-
-
4
E+04
-
-
ET/ /
Ba-133m
2
E−06
-
-
7
E+04
-
-
St/ /
Ba-133
3
E−07
-
-
1
E+04
-
-
St/ /
DOE G 441.1-1C 233
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Ba-135m
2
E−06
-
-
9
E+04
--
-
St/ /
Ba-139
1
E−05
-
-
3
E+05
-
-
St/ /
Ba-140
3
E−07
-
-
1
E+04
-
-
St/ /
Ba-141
1
E−05
-
-
4
E+05
-
-
ET/ /
Ba-142
9
E−06
-
-
3
E+05
-
-
ET/ /
La-131
1
E−05
8
E−06
-
4
E+05
3
E+05
-
ET/ET
/
La-132
1
E−06
1
E−06
-
5
E+04
5
E+04
-
ET/ET
/
La-135
1
E−05
1
E−05
-
4
E+05
4
E+05
-
ET/ET
/
La-137
4
E−08
2
E−07
-
1
E+03
8
E+03
-
L/L/
La-138
3
E−09
1
E−08
-
1
E+02
4
E+02
-
St/St/
La-140
4
E−07
3
E−07
-
1
E+04
1
E+04
-
ET/St
/
La-141
5
E−06
2
E−06
-
1
E+05
9
E+04
-
St/St/
La-142
2
E−06
2
E−06
-
9
E+04
8
E+04
-
ET/ET
/
La-143
1
E−05
1
E−05
-
6
E+05
4
Section 171
E+05
-
ET/ET
/
Ce-134
-
3
E−07
3
E−07
-
1
E+04
1
E+04
/St/St
DOE G 441.1-1C 234
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Ce-135
-
5
E−07
5
E−07
-
2
E+04
2
E+04
/ET/ET
Ce-137m
-
1
E−06
9
E−07
-
3
E+04
3
E+04
/St/St
Ce-137
-
1
E−05
1
E−05
-
7
E+05
7
E+05
/ET/ET
Ce-139
-
4
E−07
4
E−07
-
1
E+04
1
E+04
/St/St
Ce-141
-
2
E−07
1
E−07
-
7
E+03
6
E+03
/St/St
Ce-143
-
5
E−07
5
E−07
-
2
E+04
2
E+04
/St/St
Ce-144
-
2
E−08
1
E−08
-
9
E+02
7
E+02
/St/St
Pr-136
-
1
E−05
1
E−05
-
3
E+05
3
E+05
/ET/ET
Pr-137
-
9
E−06
9
E−06
-
3
E+05
3
E+05
/ET/ET
Pr-138m
-
2
E−06
2
E−06
-
7
E+04
7
E+04
/ET/ET
Pr-139
-
1
E−05
1
E−05
-
5
E+05
5
E+05
/ET/ET
Pr-142m
-
6
E−05
5
E−05
-
2
E+06
2
E+06
/St/St
Pr-142
-
8
E−07
7
E−07
-
2
E+04
2
E+04
/St/St
Pr-143
-
2
E−07
2
E−07
-
1
E+04
9
E+03
/St/St
Pr-144
-
1
E−05
1
E−05
-
4
E+05
4
E+05
/ET/ET
DOE G 441.1-1C 235
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Pr-145
-
2
E−06
2
E−06
-
8
E+04
8
E+04
/St/St
Pr-147
-
9
E−06
9
E−06
-
3
E+05
3
E+05
/ET/ET
Nd-136
-
4
E−06
4
E−06
-
1
E+05
1
E+05
/ET/ET
Nd-138
-
1
E−06
1
E−06
-
5
E+04
5
E+04
/St/St
Nd-139m
-
1
E−06
1
E−06
-
5
E+04
5
E+04
/ET/ET
Nd-139
-
1
E−05
1
E−05
-
6
E+05
6
E+05
/ET/ET
Nd-141
-
3
E−05
3
E−05
-
1
E+06
1
E+06
/ET/ET
Nd-147
-
2
E−07
2
E−07
-
1
E+04
9
E+03
/St/St
Nd-149
-
4
E−06
4
E−06
-
1
E+05
1
E+05
/ET/ET
Nd-151
-
9
E−06
9
E−06
-
3
E+05
3
E+05
/ET/ET
Pm-141
-
1
E−05
1E−
05
-
4
E+05
4
E+05
/ET/ET
Pm-143
-
5
E−07
6
E−07
-
2
E+04
2
E+04
/St/St
Pm-144
-
1
E−07
1
E−07
-
3
E+03
5
E+03
/St/St
Pm-145
-
1
E−07
4
E−07
-
5
E+03
1
E+04
/BS/St
Pm-146
-
4
E−08
6
E−08
-
1
E+03
2
E+03
/St/St
DOE G 441.1-1C 236
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Pm-147
-
1
E−07
1
E−07
-
4
E+03
6
E+03
/BS/St
Pm-148m
-
1
E−07
1
E−07
-
5
E+03
4
E+03
/St/St
Pm-148
-
2
E−07
2
E−07
-
9
E+03
9
E+03
/St/St
Pm-149
-
7
E−07
6
E−07
-
2
E+04
2
E+04
/St/St
Pm-150
-
2
E−06
2
E−06
-
8
E+04
8
E+04
/ET/ET
Pm-151
-
9
E−07
8
E−07
-
3
E+04
3
E+04
/St/St
Sm-141m
-
5
E−06
-
-
2
E+05
-
/ET/
Sm-141
-
1
E−05
-
-
4
E+05
-
/ET/
Sm-142
-
4
E−06
-
-
1
E+05
-
/ET/
Sm-145
-
4
E−07
-
-
1
E+04
-
/BS/
Sm-146
-
2
E−11
-
-
1
E+00
-
/BS/
Sm-147
-
2
E−11
-
-
1
E+00
-
/BS/
Sm-151
-
7
E−08
-
-
2
E+03
-
/BS/
Sm-153
-
8
E−07
-
-
3
E+04
-
/St/
Sm-155
-
1
E−05
-
-
3
E+05
-
/ET/
DOE G 441.1-1C 237
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Sm-156
-
2
E−06
-
-
7
E+04
-
/St/
Eu-145
-
5
E−07
-
-
2
E+04
-
/ET/
Eu-146
-
3
E−07
-
-
1
E+04
-
/ET/
Eu-147
-
5
E−07
-
-
2
E+04
-
/St/
Eu-148
-
2
E−07
-
-
9
E+03
-
Section 172
/St/
Eu-149
-
2
E−06
-
-
9
E+04
-
/St/
Eu-150 (12 h)
-
2
E−06
-
-
7
E+04
-
/St/
Eu-150 (34 yr)
-
1
E−08
-
-
6
E+02
-
/St/
Eu-152m
-
1
E−06
-
-
6
E+04
-
/St/
Eu-152
-
2
E−08
-
-
7
E+02
-
/St/
Eu-154
-
1
E−08
-
-
5
E+02
-
/St/
Eu-155
-
7
E−08
-
-
2
E+03
-
/BS/
Eu-156
-
1
E−07
-
-
6
E+03
-
/St/
Eu-157
-
1
E−06
-
-
4
E+04
-
/St/
Eu-158
-
5
E−6
-
-
1
E+05
-
/ET/
DOE G 441.1-1C 238
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Gd-145
9
E−06
7
E−06
-
3
E+05
2
E+05
-
ET/ET
/
Gd-146
1
E−07
1
E−07
-
4
E+03
4
E+03
-
St/St/
Gd-147
7
E−07
6
E−07
-
2
E+04
2
E+04
-
ET/ET
/
Gd-148
5
E−12
2
E−11
-
2
E−01
9
E−01
-
BS/BS
/
Gd-149
1
E−06
7
E−07
-
4
E+04
2
E+04
-
ET/ET
/
Gd-151
2
E−07
8
E−07
-
9
E+03
3
E+04
-
BS/St
/
Gd-152
7
E−12
3
E−11
-
2
E−01
1
E+00
-
BS/BS
/
Gd-153
9
E−08
4
E−07
-
3
E+03
1
E+04
-
BS/St
/
Gd-159
3
E−06
1
E−06
-
1
E+05
5
E+04
-
St/St/
Tb-147
-
2
E−06
-
-
1
E+05
-
/ET/
Tb-149
-
1
E−07
-
-
6
E+03
-
/St/
Tb-150
-
2
E−06
-
-
8
E+04
-
/ET/
Tb-151
-
1
E−06
-
-
4
E+04
-
/ET/
Tb-153
-
2
E−06
-
-
8
E+04
-
/St/
Tb-154
-
5
E−07
-
-
2
E+04
-
/ET/
DOE G 441.1-1C 239
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Tb-155
-
2
E−06
-
-
8
E+04
-
/St/
Tb-156m (24 h)
-
2
E−06
-
-
9
E+04
-
/St/
Tb-156m (5 h)
-
4
E−06
-
-
1
E+05
-
/St/
Tb-156
-
4
E−07
-
-
1
E+04
-
/E/
Tb-157
-
2
E−07
-
-
8
E+03
-
/BS/
Tb-158
-
1
E−08
-
-
6
E+02
-
/BS/
Tb-160
-
1
E−07
-
-
3
E+03
-
/St/
Tb-161
-
4
E−07
-
-
1
E+04
-
/St/
Dy-155
-
2
E−06
-
-
1
E+05
-
/ET/
Dy-157
-
5
E−06
-
-
1
E+05
-
/ET/
Dy-159
-
2
E−06
-
-
8
E+04
-
/BS/
Dy-165
-
6
E−06
-
-
2
E+05
-
/ET/
Dy-166
-
3
E−07
-
-
1
E+04
-
/St/
Ho-155
-
1
E−05
-
-
4
E+05
-
/ET/
Ho-157
-
2
E−05
-
-
1
E+06
-
/ET/
DOE G 441.1-1C 240
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Ho-159
-
2
E−05
-
-
9
E+05
-
/ET/
Ho-161
-
3
E−05
-
-
1
E+06
-
/ET/
Ho-162m
-
9
E−06
-
-
3
E+05
-
/ET/
Ho-162
-
5
E−05
-
-
2
E+06
-
/ET/
Ho-164m
-
3
E−05
-
-
1
E+06
-
/St/
Ho-164
-
2
E−05
-
-
8
E+05
-
/ET/
Ho-166m
-
7
E−09
-
-
2
E+02
-
/St/
Ho-166
-
6
E−07
-
-
2
E+04
-
/St/
Ho-167
-
4
E−06
-
-
1
E+05
-
/ET/
Er-161
-
3
E−06
-
-
1
E+05
-
/ET/
Er-165
-
2
E−05
-
-
1
E+06
-
/ET/
Er-169
-
6
E−07
-
-
2
E+04
-
/St/
Er-171
-
1
E−06
-
-
6
E+04
-
/St/
Er-172
-
4
E−07
-
-
1
E+04
-
/St/
Tm-162
-
9
E−06
-
-
3E+
05
-
/ET/
DOE G 441.1-1C 241
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Tm-166
-
1
E−06
-
-
4
E+04
-
/ET/
Tm-167
-
5
E−07
-
-
2
E+04
-
Section 173
/St/
Tm-170
-
1
E−07
-
-
4
E+03
-
/St/
Tm-171
-
2
E−07
-
-
9
E+03
-
/BS/
Tm-172
-
4
E−07
-
-
1
E+04
-
/St/
Tm-173
-
2
E−06
-
-
8
E+04
-
/St/
Tm-175
-
8
E−06
-
-
2
E+05
-
/ET/
Yb-162
-
1
E−05
1
E−05
-
5
E+05
5
E+05
/ET/ET
Yb-166
-
6
E−07
5
E−07
-
2
E+04
2
E+04
/St/St
Yb-167
-
3
E−05
3
E−05
-
1
E+06
1
E+06
/ET/ET
Yb-169
-
2
E−07
2
E−07
-
9
E+03
8
E+03
/St/St
Yb-175
-
8
E−07
8
E−07
-
3
E+04
2
E+04
/St/St
Yb-177
-
6
E−06
5
E−06
-
2
E+05
2
E+05
/ET/ET
Yb-178
-
5
E−06
5
E−06
-
1
E+05
1
E+05
/ET/E
Lu-169
-
9
E−07
9
E−07
-
3
E+04
3
E+04
/ET/ET
DOE G 441.1-1C 242
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Lu-170
-
4
E−07
4
E−07
-
1
E+04
1
E+04
/ET/ET
Lu-171
-
6
E−07
6
E−07
-
2
E+04
2
E+04
/St/St
Lu-172
-
3
E−07
3
E−07
-
1
E+04
1
E+04
/St/St
Lu-173
-
2
E−07
4
E−07
-
8
E+03
1
E+04
/BS/St
Lu-174m
-
2
E−07
2
E−07
-
7
E+03
8
E+03
/BS/St
Lu-174
-
9
E−08
2
E−07
-
3
E+03
8
E+03
/BS/St
Lu-176m
-
3
E−06
3
E−06
-
1
E+05
1
E+05
/St/St
Lu-176
-
3
E−09
1
E−08
-
1
E+02
6
E+02
/BS/St
Lu-177m
-
5
E−08
4
E−08
-
2
E+03
1
E+03
/St/St
Lu-177
-
5
E−07
5
E−07
-
2
E+04
1
E+04
/St/St
Lu-178m
-
4
E−06
4
E−06
-
1
E+05
1
E+05
/ET/ET
Lu-178
-
8
E−06
8
E−06
-
3
E+05
3
E+05
/ET/ET
Lu-179
-
3
E−06
3
E−06
-
1
E+05
1
E+05
/St/St
Hf-170
1
E−06
1
E−06
-
4
E+04
4
E+04
-
ET/ET
/
Hf-172
6
E−09
3
E−08
-
2
E+02
1
E+03
-
BS/BS
/
DOE G 441.1-1C 243
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Hf-173
2
E−06
2
E−06
-
9
E+04
8
E+04
-
ET/ET
/
Hf-175
5
E−07
6
E−07
-
2
E+04
2
E+04
-
BS/St
/
Hf-177m
2
E−06
1
E−06
-
9
E+04
6
E+04
-
ET/ET
/
Hf-178m
8
E−10
4
E−09
-
3
E+01
1
E+02
-
BS/BS
/
Hf-179m
2
E−07
1
E−07
-
8
E+03
6
E+03
-
BS/St
/
Hf-180m
2
E−06
1
E−06
-
7
E+04
6
E+04
-
ET/ET
/
Hf-181
1
E−07
1
E−07
-
4
E+03
5
E+03
-
BS/St
/
Hf-182m
5
E−06
4
E−06
-
2
E+05
1
E+05
-
ET/ET
/
Hf-182
5
E−10
2
E−09
-
2
E+01
9
E+01
-
BS/BS
/
Hf-183
6
E−06
4
E−06
-
2
E+05
1
E+05
-
ET/ET
/
Hf-184
1
E−06
1
E−06
-
5
E+04
4
E+04
-
ET/St
/
Ta-172
-
5
E−06
5
E−06
-
1
E+05
1
E+05
/ET/ET
Ta-173
-
3
E−06
3
E−06
-
1
E+05
1
E+05
/E/E
Ta-174
-
5
E−06
5
E−06
-
2
E+05
2
E+05
/ET/ET
Ta-175
-
1
E−06
1
E−06
-
6
E+04
6
E+04
/ET/ET
DOE G 441.1-1C 244
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Ta-176
-
1
E−06
1
E−06
-
3
E+04
3
E+04
/ET/ET
Ta-177
-
4
E−06
4
E−06
-
1
E+05
1
E+05
/St/St
Ta-178
-
3
E−06
3
E−06
-
1
E+05
1
E+05
/ET/ET
Ta-179
-
4
E−06
1
E−06
-
1
E+05
7
E+04
/St/St
Ta-180m
-
9
E−06
9
E−06
-
3
E+05
3
E+05
/St/St
Ta-180
-
1
E−07
4
E−08
-
4
E+03
1
E+03
/St/St
Ta-182m
-
6
E−06
6
E−06
-
2
E+05
2
E+05
/ET/ET
Ta-182
-
9
E−08
7
E−08
-
3
E+03
2
E+03
/St/St
Ta-183
-
3
E−07
2
E−07
-
1
E+04
1
E+04
Section 174
/St/St
Ta-184
-
8
E−07
8
E−07
-
3
E+04
3
E+04
/ET/ET
Ta-185
-
5
E−06
5
E−06
-
2
E+05
1
E+05
/ET/ET
Ta-186
-
7
E−06
7
E−06
-
2
E+05
2
E+05
/ET/ET
W-176
3
E−06
-
-
1
E+05
-
-
ET/ /
W-177
5
E−06
-
-
2
E+05
-
-
ET/ /
W-178
3
E−06
-
-
1
E+05
-
-
ET/ /
DOE G 441.1-1C 245
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
W-179
1
E−04
-
-
5
E+06
-
-
ET/ /
W-181
1
E−05
-
-
4
E+05
-
-
ET/ /
W-185
2
E−06
-
-
9
E+04
-
-
St/ /
W-187
1
E−06
-
-
5
E+04
-
-
ET/ /
W-188
6
E−07
-
-
2
E+04
-
-
St/ /
Re-177
1
E−05
1
E−05
-
6
E+05
4
E+05
-
ET/ET
/
Re-178
1
E−05
1
E−05
-
5
E+05
3
E+05
-
ET/ET
/
Re-181
1
E−06
1
E−06
-
5
E+04
4
E+04
-
ET/ET
/
Re-182 (64 h)
4
E−07
3
E−07
-
1
E+04
1
E+04
-
ET/St
/
Re-182 (12 h)
1
E−06
1
E−06
-
4
E+04
4
E+04
-
ET/ET
/
Re-184m
6
E−07
1
E−07
-
2
E+04
4
E+03
-
St/St/
Re-184
7
E−07
3
E−07
-
2
E+04
1
E+04
-
ET/St
/
Re-186m
4 E−7
7
E−08
-
1
E+04
2
E+03
-
St/St/
Re-186
7
E−07
4
E−07
-
2
E+04
1
E+04
-
St/St/
Re-187
2
E−04
1
E−04
-
8
E+06
4
E+06
-
St/St/
DOE G 441.1-1C 246
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Re-188m
3
E−05
2
E−05
-
1
E+06
1
E+06
-
St/St/
Re-188
8
E−07
7
E−07
-
3
E+04
2
E+04
-
St/St/
Re-189
1
E−06
9
E−07
-
4
E+04
3
E+04
-
St/St/
Os-180
1
E−05
1
E−05
1
E−05
5
E+05
3
E+05
3
E+05
ET/ET
/ET
Os-181
3
E−06
3
E−06
3
E−06
1
E+05
1
E+05
1
E+05
ET/ET
/ET
Os-182
1
E−06
9
E−07
9
E−07
3
E+04
3
E+04
3
E+04
ET/ET
/ET
Os-185
4
E−07
5
E−07
5
E−07
1
E+04
2
E+04
1
E+04
St/St/
St
Os-189m
1
E−04
7
E−05
7
E−05
4
E+06
2
E+06
2
E+06
St/St/
St
Os-191m
1
E−05
4
E−06
4
E−06
5
E+05
1
E+05
1
E+05
St/St/
St
Os-191
1
E−06
4
E−07
3
E−07
5
E+04
1
E+04
1
E+04
St/St/
St
Os-193
2
E−06
8
E−07
8
E−07
7
E+04
3
E+04
3
E+04
St/St/
St
Os-194
4
E−08
4
E−08
1
E−08
1
E+03
1
E+03
4
E+02
St/St/
St
Ir-182
9
E−06
7
E−06
7
E−06
3
E+05
2
E+05
2
E+05
ET/ET
/ET
Ir-184
1
E−06
1
E−06
1
E−06
7
E+04
6
E+04
7
E+04
ET/ET
/ET
Ir-185
2
E−06
1
E−06
1
E−06
7
E+04
7
E+04
7
E+04
ET/ET
/ET
DOE G 441.1-1C 247
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Ir-186 (16 h)
8
E−07
7
E−07
7
E−07
2
E+04
2
E+04
2
E+04
ET/ET
/ET
Ir-186 (2 h)
5
E−06
4
E−06
4
E−06
1
E+05
1
E+05
1
E+05
ET/ET
/ET
Ir-187
4
E−06
3
E−06
3
E−06
1
E+05
1
E+05
1
E+05
ET/ET
/ET
Ir-188
6
E−07
6
E−07
6
E−07
2
E+04
2
E+04
2
E+04
ET/ET
/ET
Ir-189
3
E−06
1
E−06
1
E−06
1
E+05
5
E+04
4
E+04
St/St/
St
Ir-190m (3 h)
2
E−06
2
E−06
2
E−06
8
E+04
8
E+04
7
E+04
ET/ET
/ET
Ir-190m (1 h)
9
E−05
5
E−05
5
E−05
3
E+06
2
E+06
1
E+06
ET/St
/St
Ir-190
4
E−07
2
E−07
2
E−07
1
E+04
9
E+03
8
E+03
ET/St
/St
Ir-192m
1
E−07
1
E−07
2
E−08
3
E+03
6
E+03
1
E+03
St/St/
St
Ir-192
2
E−07
1
E−07
1
E−07
9
E+03
5
E+03
4
E+03
St/St/
St
Ir-194m
8
Section 175
E−08
8
E−08
6
E−08
3
E+03
3
E+03
2
E+03
St/St/
St
Ir-194
1
E−06
7
E−07
7
E−07
5
E+04
2
E+04
2
E+04
St/St/
St
Ir-195m
2
E−06
2
E−06
2
E−06
9
E+04
7
E+04
7
E+04
ET/ET
/ET
Ir-195
7
E−06
5
E−06
4
E−06
2
E+05
1
E+05
1
E+05
ET/ET
/ET
Pt-186
3
E−06
-
-
1
E+05
-
-
ET/ /
DOE G 441.1-1C 248
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Pt-188
8
E−07
-
-
3
E+04
-
-
E/ /
Pt-189
3
E−06
-
-
1
E+05
-
-
ET/ /
Pt-191
1
E−06
-
-
7
E+04
-
-
ET/ /
Pt-193m
2
E−06
-
-
8
E+04
-
-
ET/ /
Pt-193
2
E−05
-
-
7
E+05
-
-
ET/ /
Pt-195m
1
E−06
-
-
5
E+04
-
-
ET/ /
Pt-197m
7
E−06
-
-
2
E+05
-
-
ET/ /
Pt-197
3
E−06
-
-
1
E+05
-
-
ET/ /
Pt-199
1
E−05
-
-
4
E+05
-
-
ET/ /
Pt-200
1
E−06
-
-
5
E+04
-
-
St/ /
Au-193
4
E−06
3
E−06
3
E−06
1
E+05
1
E+05
1
E+05
ET/E/
St
Au-194
9
E−07
9
E−07
9
E−07
3
E+04
3
E+04
3
E+04
ET/ET
/ET
Au-195
3
E−06
7
E−07
4
E−07
1
E+05
2
E+04
1
E+04
ET/St
/St
Au-198m
6
E−07
2
E−07
2
E−07
2
E+04
1
E+04
1
E+04
ET/St
/St
Au-198
1
E−06
5
E−07
5
E−07
4
E+04
2
E+04
1
E+04
ET/St
/St
DOE G 441.1-1C 249
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Au-199
2
E−06
8
E−07
7
E−07
7
E+04
3
E+04
2
E+04
ET/St
/St
Au-200m
5
E−07
4
E−07
4
E−07
1
E+04
1
E+04
1
E+04
ET/ET
/ET
Au-200
1
E−05
7E−
06
7
E−06
4
E+05
2
E+05
2
E+05
ET/ET
/ET
Au-201
1
E−05
1
E−05
9
E−06
5
E+05
3
E+05
3
E+05
ET/ET
/ET
Hg-193m (Org)
1
E−06
-
-
4
E+04
-
-
ET/ /
Hg-193m
1
E−06
1
E−06
-
4
E+04
4
E+04
-
ET/ET
/
Hg-193m (Vapor)
-
1
E−07
-
-
6
E+03
-
/St/
Hg-193 (Org)
5
E−06
-
-
1
E+05
-
-
ET/ /
Hg-193
5
E−06
4
E−06
-
1
E+05
1
E+05
-
ET/ET
/
Hg-193 (Vapor)
-
5
E−07
-
-
1
E+04
-
/St/
Hg-194 (Org)
2
E−08
-
-
1
E+03
-
-
St/ /
Hg-194
3
E−08
1
E−07
-
1
E+03
3
E+03
-
St/St/
Hg-194 (Vapor)
-
1
E−08
-
-
5
E+02
-
/St/
Hg-195m (Org)
1
E−06
-
-
5
E+04
-
-
ET/ /
Hg-195m
1
E−06
8
E−07
-
5
E+04
3
E+04
-
ET/St
/
DOE G 441.1-1C 250
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Hg-195m (Vapor)
-
6
E−08
-
-
2
E+03
-
/St/
Hg-195 (Org)
6
E−06
-
-
2
E+05
-
-
ET/ /
Hg-195
6
E−06
6
E−06
-
2
E+05
2
E+05
-
ET/ET
/
Hg-195 (Vapor)
-
4
E−07
-
-
1
E+04
-
/St/
Hg-197m (Org)
1
E−06
-
-
5
E+04
-
-
ET/ /
Hg-197m
1
E−06
8
E−07
-
5
E+04
3
E+04
-
ET/St
/
Hg-197m (Vapor)
-
9
E−08
-
-
3
E+03
-
/St/
Hg-197 (Org)
4
E−06
-
-
1
E+05
-
-
ET/ /
Hg-197
4
E−06
2
E−06
-
1
E+05
7
E+04
-
ET/St
/
Hg-197 (Vapor)
-
1
E−07
-
-
4
E+03
-
/St/
Hg-199m (Org)
8
E−06
-
-
3
E+05
-
-
ET/ /
Hg-199m
8
E−06
5
E−06
-
3
E+05
1
E+05
-
ET/ET
/
Hg-199m (Vapor)
-
3
E−06
-
-
1
E+05
-
/St/
Hg-203 (Org)
7
E−07
-
-
2
E+04
-
-
St/ /
Hg-203
9
E−07
2
E−07
-
3
E+04
1
E+04
-
St/St/
DOE G 441.1-1C 251
5-19-08
Radionuclide
Absorption Type
3
Section 176
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Hg-203 (Vapor)
-
8
E−08
-
-
2
E+03
-
/St/
Tl-194m
5
E−06
-
-
2
E+05
-
-
ET/ /
Tl-194
2
E−05
-
-
8
E+05
-
-
ET/ /
Tl-195
6
E−06
-
-
2
E+05
-
-
ET/ /
Tl-197
8
E−06
-
-
2
E+05
-
-
ET/ /
Tl-198m
2
E−06
-
-
9
E+04
-
-
ET/ /
Tl-198
1
E−06
-
-
5
E+04
-
-
ET/ /
Tl-199
5
E−06
-
-
2
E+05
-
-
ET/ /
Tl-200
8
E−07
-
-
3
E+04
-
-
ET/ /
Tl-201
4
E−06
-
-
1
E+05
-
-
ET/ /
Tl-202
1
E−06
-
-
5
E+04
-
-
ET/ /
Tl-204
9
E−07
-
-
3
E+04
-
-
St/ /
Pb-195m
7
E−06
-
-
2
E+05
-
-
ET/ /
Pb-198
2
E−06
-
-
9
E+04
-
-
ET/ /
Pb-199
4
E−06
-
-
1
E+05
-
-
ET/ /
DOE G 441.1-1C 252
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Pb-200
1
E−06
-
-
4
E+04
-
-
ET/ /
Pb-201
2
E−06
-
-
7
E+04
-
-
ET/ /
Pb-202m
1
E−06
-
-
6
E+04
-
-
ET/ /
Pb-202
4
E−08
-
-
1
E+03
-
-
St/ /
Pb-203
2
E−06
-
-
7
E+04
-
-
ET/ /
Pb-205
9
E−07
-
-
3
E+04
-
-
BS/ /
Pb-209
9
E−06
-
-
3
E+05
-
-
ET/ /
Pb-210
1
E−10
-
-
5
E+00
-
-
BS/ /
Pb-211
4
E−08
-
-
1
E+03
-
-
ET/ /
Pb-212
5
E−09
-
-
2
E+02
-
-
ET/ /
Pb-214
4
E−08
-
-
1
E+03
-
-
ET/ /
Bi-200
5
E−06
4
E−06
-
2
E+05
1
E+05
-
ET/ET
/
Bi-201
3
E−06
2
E−06
-
1
E+05
1
E+05
-
ET/ET
/
Bi-202
2
E−06
2
E−06
-
9
E+04
9
E+04
-
ET/ET
/
Bi-203
7
E−07
7
E−07
-
2
E+04
2
E+04
-
ET/ET
/
DOE G 441.1-1C 253
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Bi-205
4
E−07
4
E−07
-
1
E+04
1
E+04
-
ET/ET
/
Bi-206
2
E−07
2
E−07
-
9
E+03
8
E+03
-
ET/ET
/
Bi-207
4
E−07
1
E−07
-
1
E+04
6
E+03
-
ET/St
/
Bi-210m
3
E−09
2
E−10
-
1
E+02
9
E+00
-
K/St/
Bi-210
1
E−07
9
E−09
-
6
E+03
3
E+02
-
K/St/
Bi-212
1
E−08
8
E−09
-
4
E+02
3
E+02
-
ET/ET
/
Bi-213
1
E−08
7
E−09
-
4
E+02
2
E+02
-
ET/ET
/
Bi-214
1
E−08
1
E−08
-
6
E+02
4
E+02
-
ET/ET
/
Po-203
5
E−06
4
E−06
-
1
E+05
1
E+05
-
ET/ET
/
Po-205
4
E−06
3
E−06
-
1
E+05
1
E+05
-
ET/ET
/
Po-207
1
E−06
1
E−06
-
7
E+04
6
E+04
-
ET/ET
/
Po-210
7
E−10
2
E−10
-
2
E+01
9
E+00
-
K/St/
At-207
1
E−06
2
E−07
-
4
E+04
1
E+04
-
St/St/
At-211
7
E−09
5
E−09
-
2
E+02
1
E+02
-
ET/St
/
Rn-220
5
1
E−08
-
-
6
E+02
-
-
-
DOE G 441.1-1C 254
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Rn-222
5
8
E−08
-
-
3
E+03
-
-
-
Fr-222
1
E−08
-
-
3
E+02
-
-
ET/ /
Fr-223
4
E−07
-
-
1
E+04
-
-
St/ /
Ra-223
-
9
E−11
-
-
3
E+00
-
/St/
Ra-224
-
2
E−10
-
-
8
E+00
-
/St/
Ra-225
-
1
E−10
-
-
4
E+00
-
/St/
Ra-226
-
2
E−10
-
-
9
E+00
-
/St/
Ra-227
-
8
E−07
-
-
3
E+04
-
/BS/
Ra-228
-
1
E−10
-
-
5
E+00
-
/BS/
Ac-224
1
E−08
6
E−09
5
E−09
6
E+02
2
E+02
2
E+02
BS/St
/St
Ac-225
2
E−10
9
E−11
8
E−11
7
E+00
3
E+00
Section 177
3
E+00
BS/St
/St
Ac-226
1
E−09
6
E−10
5
E−10
4
E+01
2
E+01
2
E+01
ET/St
/St
Ac-227
2
E−13
1
E−12
1
E−11
1
E−02
5
E−02
4
E−01
BS/BS
/St
Ac-228
6
E−09
3
E−08
4
E−08
2
E+02
1
E+03
1
E+03
BS/BS
/St
Th-226
-
4
E−09
4
E−09
-
1
E+02
1
E+02
/ET/ET
DOE G 441.1-1C 255
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Th-227
-
9
E−11
7
E−11
-
3
E+00
2
E+00
/St/St
Th-228
-
2
E−11
2
E−11
-
7
E−01
8
E−01
/BS/St
Th-229
-
2
E−12
1
E−11
-
7
E−02
4
E−01
/BS/St
Th-230
-
3
E−12
4
E−11
-
1
E−01
1
E+00
/BS/BS
Th-231
-
1
E−06
1
E−06
-
5
E+04
5
E+04
/St/St
Th-232
-
3
E−12
4
E−11
-
1
E−01
1
E+00
/BS/BS
Th-234
-
1
E−07
9
E−08
-
3
E+03
3
E+03
/St/St
Pa-227
-
4
E−09
4
E−09
-
1
E+02
1
E+02
/ET/ET
Pa-228
-
1
E−08
1
E−08
-
3
E+02
4
E+02
/BS/St
Pa-230
-
1
E−09
9
E−10
-
4
E+01
3
E+01
/St/St
Pa-231
-
1
E−12
1
E−11
-
4
E−02
4
E−01
/BS/BS
Pa-232
-
1
E−08
1
E−07
-
6
E+02
7
E+03
/BS/BS
Pa-233
-
2
E−07
1
E−07
-
7
E+03
6
E+03
/St/St
Pa-234
-
7
E−07
7
E−07
-
2
E+04
2
E+04
/ET/ET
U-230
6
E−10
5
E−11
4
E−11
2
E+01
2
E+00
1
E+00
K/St/
St
DOE G 441.1-1C 256
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
U-231
2
E−06
1
E−06
1
E−06
8
E+04
4
E+04
4
E+04
ET/St
/St
U-232
5
E−11
1
E−10
2
E−11
2
E+00
4
E+00
7
E−01
BS/St
/ET
U-233
4
E−10
2
E−10
7
E−11
1
E+01
9
E+00
2
E+00
BS/St
/ET
U-234
5
E−10
2
E−10
7
E−11
1
E+01
9
E+00
2
E+00
BS/St
/ET
U-235
5
E−10
3
E−10
8
E−11
1
E+01
1
E+01
3
E+00
BS/St
/ET
U-236
5
E−10
2
E−10
7
E−11
1
E+01
1
E+01
2
E+00
BS/St
/ET
U-237
1
E−06
3
E−07
3
E−07
4
E+04
1
E+04
1
E+04
ET/St
/St
U-238
5
E−10
3
E−10
8
E−11
2
E+01
1
E+01
3
E+00
BS/St
/ET
U-239
1
E−05
9
E−06
9
E−06
5
E+05
3
E+05
3
E+05
ET/ET
/ET
U-240
1
E−06
7
E−07
6
E−07
5
E+04
2
E+04
2
E+04
ET/St
/St
Np-232
-
3
E−06
-
-
1
E+05
-
/BS/
Np-233
-
7
E−05
-
-
2
E+06
-
/ET/
Np-234
-
5
E−07
-
-
2
E+04
-
/ET/
Np-235
-
1
E−06
-
-
4
E+04
-
/BS/
Np-236 (1 E+05 yr)
-
4
E−11
-
-
1
E+00
-
/BS/
DOE G 441.1-1C 257
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Np-236 (22 h)
-
5
E−08
-
-
1
E+03
-
/BS/
Np-237
-
8
E−12
-
-
3
E−01
-
/BS/
Np-238
-
1
E−07
-
-
4
E+03
-
/BS/
Np-239
-
5
E−07
-
-
1
E+04
-
/St/
Np-240
-
2
E−06
-
-
8
E+04
-
/ET/
Pu-234
-
3
E−08
3
E−08
-
1
E+03
1
E+03
/St/St
Pu-235
-
9
E−05
8
E−05
-
3
E+06
3
E+06
/ET/ET
Pu-236
-
1
E−11
7
E−11
-
6
E−01
2
E+00
/BS/St
Pu-237
-
1
E−06
1
E−06
-
7
E+04
6
E+04
/St/St
Pu-238
-
6
E−12
5
E−11
-
2
E−01
1
E+00
/BS/St
Pu-239
-
5
E−12
6
E−11
-
2
E−01
2
E+00
/BS/BS
Pu-240
-
5
E−12
6
E−11
-
2
E−01
2
E+00
/BS/BS
Pu-241
-
2
E−10
2
E−09
-
1
E+01
1
E+02
/BS/BS
Pu-242
-
5
E−12
6
E−11
-
2
E−01
2
E+00
/BS/BS
Pu-243
-
5
E−06
5
E−06
-
1
E+05
1
E+05
/E/E
Section 178
DOE G 441.1-1C 258
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Pu-244
-
5
E−12
6
E−11
-
2
E−01
2
E+00
/BS/BS
Pu-245
-
9
E−07
8
E−07
-
3
E+04
3
E+04
/St/St
Pu-246
-
8
E−08
8
E−08
-
3
E+03
2
E+03
/St/St
Am-237
-
8
E−06
-
-
3
E+05
-
/ET/
Am-238
-
2
E−06
-
-
9
E+04
-
/BS/
Am-239
-
1
E−06
-
-
6
E+04
-
/ET/
Am-240
-
7
E−07
-
-
2
E+04
-
/ET/
Am-241
-
5
E−12
-
-
1
E−01
-
/BS/
Am-242m
-
5
E−12
-
-
1
E−01
-
/BS/
Am-242
-
4
E−08
-
-
1
E+03
-
/St/
Am-243
-
5
E−12
-
-
1
E−01
-
/BS/
Am-244m
-
3
E−06
-
-
1
E+05
-
/BS/
Am-244
-
1
E−07
-
-
5
E+03
-
/BS/
Am-245
-
5
E−06
-
-
2
E+05
-
/ET/
Am-246m
-
6
E−06
-
-
2
E+05
-
/ET/
DOE G 441.1-1C 259
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Am-246
-
2
E−06
-
-
9
E+04
-
/ET/
Cm-238
-
1
E−07
-
-
4
E+03
-
/St/
Cm-240
-
2
E−10
-
-
7
E+00
-
/St/
Cm-241
-
2
E−08
-
-
8
E+02
-
/St/
Cm-242
-
1
E−10
-
-
5
E+00
-
/St/
Cm-243
-
7
E−12
-
-
2
E−01
-
/BS/
Cm-244
-
9
E−12
-
-
3
E−01
-
/BS/
Cm-245
-
5
E−12
-
-
1
E−01
-
/BS/
Cm-246
-
5
E−12
-
-
1
E−01
-
/BS/
Cm-247
-
5
E−12
-
-
2
E−01
-
/BS/
Cm-248
-
1
E−12
-
-
5
E−02
-
/BS/
Cm-249
-
8
E−06
-
-
3
E+05
-
/ET/
Cm-250
-
2
E−13
-
-
8
E−03
-
/BS/
Bk-245
-
3
E−07
-
-
1
E+04
-
/St/
Bk-246
-
8
E−07
-
-
3
E+04
-
/ET/
DOE G 441.1-1C 260
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Bk-247
-
3
E−12
-
-
1
E−01
-
/BS/
Bk-249
-
1
E−09
-
-
5
E+01
-
/BS/
Bk-250
-
2
E−07
-
-
9
E+03
-
/BS/
Cf-244
-
1
E−08
-
-
5
E+02
-
/ET/
Cf-246
-
1
E−09
-
-
5
E+01
-
/St/
Cf-248
-
5
E−11
-
-
2
E+00
-
/BS/
Cf-249
-
3
E−12
-
-
1
E−01
-
/BS/
Cf-250
-
7
E−12
-
-
2
E−01
-
/BS/
Cf-251
-
3
E−12
-
-
1
E−01
-
/BS/
Cf-252
-
1
E−11
-
-
6
E−01
-
/BS/
Cf-253
-
5
E−10
-
-
2
E+01
-
/St/
Cf-254
-
2
E−11
-
-
8
E−01
-
/BS/
Es-250
-
4
E−07
-
-
1
E+04
-
/BS/
Es-251
-
3
E−07
-
-
1
E+04
-
/St/
Es-253
-
2
E−10
-
-
9
E+00
-
/St/
DOE G 441.1-1C 261
5-19-08
Radionuclide
Absorption Type
3
Absorption Type
3
Stoch
astic
or
organ or
tissue
1
µCi/mL
Bq/m
3
F
M
S
F
M
S
( F/
M/ S)
Es-254m
-
1
E−09
-
-
5
E+01
-
/St/
Es-254
-
6
E−11
-
-
2
E+00
-
/BS/
Fm-252
-
2
E−09
-
-
8
E+01
-
/St/
Fm-253
-
1
E−09
-
-
6
E+01
-
/St/
Fm-254
-
6
E−09
-
-
2
E+02
-
/ET/
Fm-255
-
2
E−09
-
-
8
E+01
-
/St/
Fm-257
-
1
E−10
-
-
4
E+00
-
/St/
Md-257
-
2
E−08
-
-
1
E+03
-
/St/
Md-258
-
1
E−10
-
-
4
E+00
-
/St/
Footnotes for Appendix A
1 A determination of whether the DACs are controlled by stochastic (St) or deterministic (organ or tissue) dose, or
Section 179
if they both give the same result (E), for each absorption type, is given in this column. The key to the organ notation
for deterministic dose is: BS = Bone surface, ET = Extra thoracic, K = Kidney, L = Liver, and T = Thyroid. A blank
indicates that no calculations were performed for the absorption type shown.
2 The ICRP identifies these materials as soluble or reactive gases and vapors or highly soluble or reactive gases and
vapors. For tritiated water, the inhalation DAC values allow for an additional 50% absorption through the skin, as
described in ICRP Publication No. 68, Dose Coefficients for Intakes of Radionuclides by Workers. For elemental tritium,
the DAC values include a factor that irradiation from gas within the lungs might increase the dose by 20%.
3 A dash indicates no values given for this data category.
4 DAC values derived using hafnium tritide particle and are based on “observed activity” (i.e., only radiation
emitted from the particle is considered). DAC values derived using methodology found in Radiological Control
Programs for Special Tritium Compounds, DOE-HDBK-1184-2004.
5 These values are appropriate for protection from radon combined with its short-lived decay products and are
based on information given in ICRP Publication 65: Protection Against Radon-222 at Home and at Work and in DOE-
STD-1121-98: Internal Dosimetry. The values given are for 100% equilibrium concentration conditions of the short-
DOE G 441.1-1C 262
5-19-08
lived radon decay products with the parent. To allow for an actual measured equilibrium concentration or a
demonstrated equilibrium concentration, the values given in this table should be multiplied by the ratio (100%/actual
%) or (100%/demonstrated %), respectively. Alternatively, the DAC values for Rn-220 and Rn-222 may be replaced by
2.5 working level (WL) and 0.83 WL, respectively, for appropriate limiting of decay product concentrations. A WL is
any combination of short-lived radon decay products, in one liter of air without regard to the degree of equilibrium,
that will result in the ultimate emission of 1.3 E+05 MeV of alpha energy.
DOE G 441.1-1C 263
5-19-08
Appendix B
Reserved
DOE G 441.1-1C 265
5-19-08
Appendix C
Derived Air Concentration (DAC) For Workers From External Exposure During
Immersion In A Cloud Of Airborne Radioactive Material
a. The data presented in appendix C are to be used for controlling occupational exposures in
accordance with § 835.209, identifying the need for air monitoring in accordance with § 835.403 and
identifying the need for posting of airborne radioactivity areas in accordance with § 835.603(d).
b. The air immersion DAC values shown in this appendix are based on a stochastic dose limit of 5
rems (0.05 Sv) per year. Four columns of information are presented: (1) radionuclide; (2) half-life in
units of seconds (s), minutes (min), hours (h), days (d), or years (yr); (3) air immersion DAC in units of
µCi/mL; and (4) air immersion DAC in units of Bq/m3. The data are listed by radionuclide in order of
increasing atomic mass. The air immersion DACs were calculated for a continuous, nonshielded
exposure via immersion in a semi-infinite cloud of airborne radioactive material. The DACs listed in this
appendix may be modified to allow for submersion in a cloud of finite dimensions.
c. The DAC values are given for individual radionuclides. For known mixtures of radionuclides,
Section 180
determine the sum of the ratio of the observed concentration of a particular radionuclide and its
corresponding DAC for all radionuclides in the mixture. If this sum exceeds unity (1), then the DAC has
been exceeded. For unknown radionuclides, the most restrictive DAC (lowest value) for those isotopes
not known to be absent shall be used.
Air Immersion DAC
Radionuclide
Half-Life
(µCi/mL)
(Bq/m3)
Ar-37
35.02 d
3 E+00
1 E+11
Ar-39
269 yr
1 E−03
5 E+07
Ar-41
1.827 h
3 E−06
1 E+05
Kr-74
11.5 min
3 E−06
1 E+05
Kr-76
14.8 h
1E−05
3 E+05
Kr-77
74.7 min
4 E−06
1 E+05
Kr-79
35.04 h
1 E−05
6 E+05
Kr-81
2.1E+05 yr
7 E−04
2 E+07
Kr-83m
1.83 h
7E−02
2 E+09
Kr-85
10.72 yr
7 E−04
2 E+07
Kr-85m
4.48 h
2 E−05
1 E+06
DOE G 441.1-1C 266
5-19-08
Air Immersion DAC
Radionuclide
Half-Life
(µCi/mL)
(Bq/m3)
Kr-87
76.3 min
4 E−06
1 E+05
Kr-88
2.84 h
1 E−06
7 E+04
Xe-120
40.0 min
1 E−05
4 E+05
Xe-121
40.1 min
2 E−06
8 E+04
Xe-122
20.1 h
8 E−05
3 E+06
Xe-123
2.14 h
6 E−06
2 E+05
Xe-125
16.8 h
1 E−05
6E+05
Xe-127
36.406 d
1E−05
6 E+05
Xe-129m
8.89 d
2 E−04
7 E+06
Xe-131m
11.84 d
5 E−04
1 E+07
Xe-133
5.245 d
1E−04
5 E+06
Xe-133m
2.19 d
1 E−04
5 E+06
Xe-135
9.11 h
1 E−05
6 E+05
Xe-135m
15.36 min
1 E−05
3 E+05
Xe-138
14.13 min
3 E−06
1E+05
For any single radionuclide not listed above with decay mode other than alpha emission or
spontaneous fission and with radioactive half-life less than two hours, the DAC value shall be 6 E−06
µCi/mL (2 E+04 Bq/m3).
DOE G 441.1-1C 267
5-19-08
Appendix D
Surface Contamination Values
The data presented in appendix D are to be used in identifying and posting contamination and high
contamination areas in accordance with § 835.603(e) and (f) and identifying the need for surface
contamination monitoring and control in accordance with § 835.1101 and 1102.
Surface Contamination Values1 in dpm/100 cm2
Radionuclide
Removable 2,4
Total
(Fixed +
Removable)2,3
U-nat, U-235, U-238, and associated decay
products
7 1,000
7 5,000
Transuranics, Ra-226, Ra-228, Th-230,
Th-228, Pa-231, Ac-227, I-125, I-129
20
500
Th-nat, Th-232, Sr-90, Ra-223, Ra-224, U-
232, I-126, I-131, I-133
200
1,000
Beta-gamma emitters (nuclides with decay
modes other than alpha emission or
spontaneous fission) except Sr-90 and others
noted above5
1,000
5,000
Tritium and STCs 6
10,000
See Footnote 6
1 The values in this appendix, with the exception noted in footnote 6 below, apply to radioactive
contamination deposited on, but not incorporated into the interior or matrix of, the contaminated item.
Where surface contamination by both alpha- and beta-gamma-emitting nuclides exists, the limits
established for alpha- and beta-gamma-emitting nuclides apply independently.
2 As used in this table, dpm (disintegrations per minute) means the rate of emission by radioactive
material as determined by correcting the counts per minute observed by an appropriate detector for
background, efficiency, and geometric factors associated with the instrumentation.
3 The levels may be averaged over one square meter provided the maximum surface activity in any
area of 100 cm2 is less than three times the value specified. For purposes of averaging, any square
meter of surface shall be considered to be above the surface contamination value if: (1) from
measurements of a representative number of sections it is determined that the average contamination
level exceeds the applicable value; or (2) it is determined that the sum of the activity of all isolated spots
or particles in any 100 cm2 area exceeds three times the applicable value.
Section 181
DOE G 441.1-1C 268
5-19-08
4 The amount of removable radioactive material per 100 cm2 of surface area should be determined
by swiping the area with dry filter or soft absorbent paper, applying moderate pressure, and then
assessing the amount of radioactive material on the swipe with an appropriate instrument of known
efficiency. (Note - The use of dry material may not be appropriate for tritium.) When removable
contamination on objects of surface area less than 100 cm2 is determined, the activity per unit area shall
be based on the actual area and the entire surface shall be wiped. It is not necessary to use swiping
techniques to measure removable contamination levels if direct scan surveys indicate that the total
residual surface contamination levels are within the limits for removable contamination.
5 This category of radionuclides includes mixed fission products, including the Sr-90 which is present
in them. It does not apply to Sr-90 which has been separated from the other fission products or
mixtures where the Sr-90 has been enriched.
6 Tritium contamination may diffuse into the volume or matrix of materials. Evaluation of surface
contamination shall consider the extent to which such contamination may migrate to the surface in
order to ensure the surface contamination value provided in this appendix is not exceeded. Once this
contamination migrates to the surface, it may be removable, not fixed; therefore, a "Total" value does
not apply. In certain cases, a “Total” value of 10,000 dpm/100 cm2 may be applicable either to metals of
the types from which insoluble special tritium compounds are formed, that have been exposed to
tritium, or to bulk materials to which insoluble special tritium compound particles are fixed to a surface.
7 These limits apply only to the alpha emitters within the respective decay series.
DOE G 441.1-1C 269
5-19-08
Appendix E
Values For Establishing Sealed Radioactive Source Accountability And Radioactive
Material Posting And Labeling Requirements
The data presented in appendix E are to be used for identifying accountable sealed radioactive
sources and radioactive material areas as those terms are defined at § 835.2(a), establishing the need
for radioactive material area posting in accordance with § 835.603(g), and establishing the need for
radioactive material labeling in accordance with § 835.605.
Nuclide
Activity (µCi)
H-3 1.5E+08
Be-7 3.1E+03
Be-10 1.4E+05
C-14 4.6E+06
Na-22 1.9E+01
Al-26 1.5E+01
Si-32 4.9E+04
S-35 2.4E+06
Cl-36 5.2E+05
K-40 2.7E+02
Ca-41 9.3E+06
Ca-45 1.1E+06
Sc-46 6.2E+01
Ti-44 1.5E+02
V-49 1.0E+08
Mn-53 7.5E+07
Mn-54 6.5E+01
Fe-55 2.9E+06
Fe-59 1.9E+02
Fe-60 8.1E+03
Co-56 3.9E+01
Co-57 2.3E+02
Co-58 1.3E+02
Co-60 1.7E+01
Ni-59 3.2E+06
Ni-63 1.3E+06
Zn-65 1.1E+02
Ge-68 5.6E+02
As-73 5.3E+02
Se-75 6.3E+01
Se-79 8.7E+05
Rb-83 9.1E+01
Rb-84 2.0E+02
Sr-85 1.2E+02
Sr-89 4.8E+05
Nuclide
Activity (µCi)
Sr-90 3.5E+04
Y-88 3.3E+01
Y-91 5.0E+04
Zr-88 1.1E+02
Zr-93 9.3E+04
Zr-95 1.9E+02
Nb-91 6.9E+01
Nb-91m 3.6E+02
Nb-92 1.8E+01
Nb-93m 4.4E+02
Nb-94 2.3E+01
Nb-95 3.4E+02
Mo-93 7.7E+01
Tc-95m 1.3E+02
Tc-97 8.1E+01
Tc-97m 3.5E+02
Tc-98 2.5E+01
Tc-99 8.4E+05
Ru-103 4.4E+02
Ru-106 2.5E+02
Rh-101 8.7E+05
Rh-102 3.0E+05
Rh-102m 6.4E+05
Pd-107 9.3E+06
Ag-105 3.3E+06
Ag-108m 1.8E+01
Ag-110m 2.2E+01
Cd-109 1.6E+02
Cd-113m 2.0E+04
Cd-115m 1.0E+04
In-114m 7.7E+02
Sn-113
3.1E+02
Sn-119m 3.3E+02
Sn-121m 8.1E+05
Section 182
Sn-123 1.3E+04
DOE G 441.1-1C 270
5-19-08
Nuclide
Activity (µCi)
Sn-126 1.8E+02
Sb-124 9.1E+01
Sb-125 6.7E+01
Te-121m 1.8E+02
Te-123m 2.8E+02
Te-125m 4.4E+02
Te-127m 8.0E+02
Te-129m 2.3E+03
I-125 3.5E+02
I-129 1.8E+02
Cs-134 2.6E+01
Cs-135 1.3E+06
Cs-137 6.0E+01
Ba-133 5.1E+01
La-137 2.7E+05
Ce-139 2.4E+02
Ce-141 2.4E+03
Ce-144 1.4E+03
Pm-143 1.3E+02
Pm-144 2.9E+01
Pm-145 2.6E+02
Pm-146 4.4E+01
Pm-147 7.7E+05
Pm-148m 1.0E+02
Sm-145 2.4E+06
Sm-146 4.0E+02
Sm-151 2.5E+05
Eu-148 1.1E+06
Eu-149 1.1E+07
Eu-152 3.1E+01
Eu-154 3.1E+01
Eu-155
3.6E+02
Gd-146 5.1E+05
Gd-148 9.0E+01
Gd-151 2.9E+06
Gd-153 2.1E+02
Tb-157 2.5E+03
Tb-158 9.0E+04
Tb-160 1.2E+02
Dy-159 1.0E+07
Ho-166m 2.1E+01
Tm-170 8.4E+03
Tm-171 2.8E+04
Yb-169 5.5E+02
Lu-173 1.8E+06
Lu-174 9.3E+05
Nuclide
Activity (µCi)
Lu-174m 1.0E+06
Lu-177m 5.8E+01
Hf-172 7.3E+04
Hf-175 3.0E+06
Hf-178m 8.7E+03
Hf-181 3.4E+02
Hf-182 7.5E+03
Ta-179 9.3E+06
Ta-182 7.3E+01
W-181 1.0E+03
W-185 3.9E+06
W-188 6.3E+04
Re-183 5.3E+02
Re-184 2.6E+02
Re-184m 1.5E+02
Re-186m 3.4E+05
Os-185 1.3E+02
Os-194 6.4E+04
Ir-192 1.3E+02
Ir-192m 1.4E+05
Ir-194m 2.7E+01
Pt-193 8.7E+07
Au-195 4.8E+02
Hg-194 5.2E+04
Hg-203 4.9E+02
Tl-204 2.2E+04
Pb-202 1.9E+05
Pb-205 9.0E+01
Pb-210 9.2E+01
Bi-207 1.7E+01
Bi-208 1.5E+01
Bi-210m 1.2E+03
Po-209 6.3E+03
Po-210 1.2E+03
Ra-226 2.2E+02
Ra-228 1.5E+03
Ac-227 4.2E+00
Th-228 8.4E+01
Th-229 3.1E+01
Th-230 5.4E+00
Th-232 9.3E+01
Pa-231 3.0E+01
U-232 1.0E+02
U-233 3.9E+02
U-234 2.9E+02
U-235 6.7E+01
DOE G 441.1-1C 271
5-19-08
Nuclide
Activity (µCi)
U-236 3.1E+02
U-238 3.5E+02
Np-235 1.1E+02
Np-236 2.1E+01
Np-237 4.9E+01
Pu-236 2.0E+02
Pu-237 3.3E+02
Pu-238 9.0E+01
Pu-239 8.4E+01
Pu-240 8.4E+01
Pu-241 4.6E+03
Pu-242 8.7E+01
Pu-244 9.0E+01
Am-241 7.2E+01
Am-242m 1.1E+02
Am-243 7.3E+01
Cm-241 1.0E+05
Cm-242 6.2E+02
Cm-243 4.8E+01
Nuclide
Activity (µCi)
Cm-244 1.5E+02
Cm-245 5.0E+01
Cm-246 1.0E+02
Cm-247 8.5E+01
Cm-248 2.8E+01
Cm-250 5.4E+00
Bk-247 6.0E+01
Bk-249 2.7E+04
Cf-248 4.4E+02
Cf-249 5.5E+01
Cf-250 1.2E+02
Cf-251 5.3E+01
Cf-252 5.2E+00
Cf-254 1.2E+02
Es-254 6.3E+01
Es-255 8.8E+03
Fm-257 5.1E+02
Md-258 6.1E+02
Any alpha emitting radionuclide not listed in appendix E and mixtures of alpha emitters of unknown
composition have a value of 10 µCi.
With the exception that any type of STC has a value of 10 Ci, any radionuclide other than alpha
emitting radionuclides not listed in appendix E and mixtures of beta emitters of unknown composition
have a value of 100 µCi. DOE DOE-HDBK-1184-2004, RADIOLOGICAL CONTROL PROGRAMS FOR SPECIAL
TRITIUM COMPOUNDS (DOE 2004d), provides guidance for radiological controls, including monitoring,
for special tritium compounds.
Note: Where there is involved a combination of radionuclides in known amounts, derive the value
for the combination as follows: determine, for each radionuclide in the combination, the ratio between
the quantity present in the combination and the value otherwise established for the specific
radionuclide when not in combination. If the sum of such ratios for all radionuclides in the combination
exceeds unity (1), then the accountability criterion has been exceeded.
The values in the above table were derived based on the quantity of radioactive material which
Section 183
results in either an external or internal whole body dose, from either inhalation or ingestion, of 100
millirems. The external exposure scenario assumed a photon exposure for 12 hours a day for 365 days
with the source distance being at 1 meter, with the exception for Californium-252, which was obtained
by substituting a neutron exposure for the photon exposure in the external exposure scenario using
values from Reference Neutron Radiations – Part 1: Characteristics and Methods of Production, ISO/CD,
8529-1. The internal exposure scenario assumed an instantaneous intake of 0.001% of the material by
an individual. The scenario which resulted in a lower quantity of radioactive material was chosen.
DOE G 441.1-1C 272
5-19-08
Appendix F
Radiation Weighting Factors
The below table is taken from the “Definitions” section of 10 CFR 835 and is provided for
information purposes. There is no corresponding Appendix F in 10 CFR 835.
RADIATION WEIGHTING FACTORS1, wR
Type and energy range Radiation weighting factor
Photons, electrons and muons, all energies
1
Neutrons, energy < 10 keV2, 3
5
Neutrons, energy 10 keV to 100 keV2, 3
10
Neutrons, energy > 100 keV to 2 MeV2, 3
20
Neutrons, energy > 2 MeV to 20 MeV2, 3
10
Neutrons, energy > 20 MeV2, 3
5
Protons, other than recoil protons, energy > 2
MeV
5
Alpha particles, fission fragments, heavy nuclei
20
1. All values relate to the radiation incident on the body or, for internal sources, emitted from
the source.
2. When spectral data are insufficient to identify the energy of the neutrons, a radiation
weighting factor of 20 shall be used.
3. When spectral data are sufficient to identify the energy of the neutrons, the following
equation may be used to determine a neutron radiation weighting factor value:
wR = 5 + 17 exp 6
))2(ln( 2
nE
Where En is the neutron energy in MeV.
DOE G 441.1-1C 273
5-19-08
Appendix G
Tissue Weighting Factors
The below table is taken from the “Definitions” section of 10 CFR 835 and is provided for
information purposes. There is no corresponding Appendix G in 10 CFR 835.
TISSUE WEIGHTING FACTORS FOR VARIOUS ORGANS AND TISSUES
Organs or tissues, T
Tissue weighting
factor, wT
Gonads
0.20
Red bone marrow
0.12
Colon
0.12
Lungs
0.12
Stomach
0.12
Bladder
0.05
Breast
0.05
Liver
0.05
Esophagus
0.05
Thyroid
0.05
Skin
0.01
Bone surfaces
0.01
Remainder1
0.05
Whole body2
1.00
1 "Remainder" means the following additional tissues and organs and their masses, in grams,
following parenthetically: adrenals (14), brain (1400), extrathoracic airways (15), small intestine
(640), kidneys (310), muscle (28,000), pancreas (100), spleen (180), thymus (20), and uterus (80).
The equivalent dose to the remainder tissues (Hremainder), is normally calculated as the mass-weighted
mean dose to the preceding ten organs and tissues. In those cases in which the most highly
irradiated remainder tissue or organ receives the highest equivalent dose of all the organs, a
weighting factor of 0.025 (half of remainder) is applied to that tissue or organ and 0.025 (half of
remainder) to the mass-weighted equivalent dose in the rest of the remainder tissues and organs to
give the remainder equivalent dose.
DOE G 441.1-1C 274
5-19-08
2 For the case of uniform external irradiation of the whole body, a tissue weighting factor (wT)
equal to 1 may be used in determination of the effective dose.
DOE G 441.1-1C 275
5-19-08
REFERENCES
Section 184
(AEC 1954) Atomic Energy Commission 1954. U.S. Atomic Energy Act of 1954, as amended.
Public Law 83-703 (68 Stat. 919), Title 42 U.S.C., Section 2011.
(ANSI 1979) American National Standards Institute 1979. ANSI N320, American National
Standard Performance Specifications for Reactor Emergency Radiological Monitoring
Instrumentation, New York, NY.
(ANSI 1988) American National Standards Institute 1988. ANSI N13.3, Dosimetry for Criticality
Accidents. McClean, VA.
(ANSI 1993) American National Standards Institute 1993. ANSI N43.3-1993, General Radiation
Safety -Installations Using Non-Medical X-Ray and Sealed Gamma-Ray Sources, Energies up to 10
MeV. New York, NY.
(ANSI 1997a) American National Standards Institute 1997. ANSI N323A-1997, American National
Standard Radiation Protection Instrumentation Test and Calibration, Portable Survey Instruments.
New York, NY.
(ANSI 1997b) American National Standards Institute 1997. ANSI N322, American National
Standard Inspection, Test, Construction, and Performance Requirements for Direct Reading
Electrostatic/Electroscope Type Dosimeters, New York, NY.
(ANSI 1989a) American National Standards Institute 1989. ANSI N13.5-R1989, American
National Standard Performance Specifications for Direct Reading and Indirect Reading Pocket
Dosimeters. New York, NY.
(ANSI 1989b) American National Standards Institute 1989. ANSI N42.17A-1989, Performance
Specifications for Health Physics Instrumentation - Portable Instrumentation for Use in Normal
Environmental Conditions. New York, NY.
(ANSI 1989c) American National Standards Institute 1989. ANSI N42.17C-1989, Performance
Specifications for Health Physics Instrumentation - Portable Instrumentation for Use in Extreme
Environmental Conditions. New York, NY.
(ANSI 1989d) American National Standards Institute 1989. ANSI N42.17B, Performance
Specifications for Health Physics Instrumentation - Occupational Airborne Radioactivity Monitoring
Instrumentation. New York, NY.
(ANSI 1989e) American National Standards Institute 1989. ANSI N2.1-1971(R1989), Radiation
Symbol. New York, NY.
(ANSI 1992a) American National Standards Institute 1992. ANSI N13.27, Performance
Specifications for Pocket-sized Alarming Dosimeter/Ratemeters. New York, NY.
http://webstore.ansi.org/ansidocstore/product.asp?sku=N322%2D1997
http://webstore.ansi.org/ansidocstore/product.asp?sku=N322%2D1997
http://webstore.ansi.org/ansidocstore/product.asp?sku=N322%2D1997
DOE G 441.1-1C 276
5-19-08
(ANSI 1992b) American National Standards Institute 1992. ANSI Z88.2-1992, Practices for
Respiratory Protection. New York, NY.
(ANSI/HPS 1996) American National Standards Institute/Health Physics Society 1996. ANSI/HPS
N13.30-1996, Performance Criteria for Radiobioassay. McLean, VA .
(ANSI/HPS 1997a) American National Standards Institute/Health Physics Society 1997.
ANSI/HPS N13.41-1997, Criteria for Performing Multiple Dosimetry. McClean, VA.
(ANSI/HPS 1997b) American National Standards Institute/Health Physics Society 1997.
ANSI/HPS N43.6-1997, Sealed Radioactive Sources Classification. Mclean, VA.
(ANSI/HPS 1999) American National Standards Institute/Health Physics Society 1999. ANSI /HPS
N13.6-1999, Practice for Occupational Radiation Exposure Records Systems. McClean, VA.
(ANSI/HPS 2000) American National Standards Institute/Health Physics Society 2000. ANSI/HPS
N13.39-2000, American National Standard for Design of Internal Dosimetry Programs. McLean, VA.
Section 185
(ANSI/HPS 2001a) American National Standards Institute/Health Physics Society 2001.
ANSI/HPS N43.2-2001, Radiation Safety for X-Ray Diffraction and Fluorescence Analysis Equipment.
McClean, VA.
(ANSI/HPS 2001b) American National Standards Institute/Health Physics Society 2001.
ANSI/HPS N13.49-2001, Performance and Documentation of Radiological Surveys. McClean, VA.
(ANSI/HPS 2005) American National Standards Institute/Health Physics Society 2005. ANSI/HPS
N43.5-2005, Radiological Safety Standard for the Design of Radiographic and Fluoroscopic Industrial
X-Ray Equipment. McClean, VA.
(ANSI/NCSL 1994) American National Standards Institute/National Conference of Standards
Laboratories 1994. ANSI/NCSL Z540-1-1994, American National Standard for
Calibration - Calibration Laboratories and Measuring and Test Equipment -General Requirements,
Boulder, Colorado.
(BRH 1970) Bureau of Radiological Health. Radiological Health Handbook, U.S. Government
Printing Office. Washington, D.C.
(DOE 1993) DOE O 5480.30, Ch 1, Nuclear Reactor Safety Design Criteria, U.S. Department of
Energy. Washington, D.C.
(DOE 1994) DOE-STD-1070-94, GUIDELINES FOR EVALUATION OF NUCLEAR FACILITY TRAINING
PROGRAMS, U.S. Department of Energy. Washington, D.C
(DOE 1996) DOE P 441.1, Department of Energy Radiological Health and Safety Policy, U.S.
Department of Energy. Washington, D.C.
(DOE 1998a) DOE-STD-1111-98, DEPARTMENT OF ENERGY LABORATORY ACCREDITATION
PROGRAM ADMINISTRATION, U.S. Department of Energy. Washington, D.C.
DOE G 441.1-1C 277
5-19-08
(DOE 1998b) DOE-STD-1112-98. DEPARTMENT OF ENERGY LABORATORY ACCREDITATION
PROGRAM FOR RADIOBIOASSAY, U.S. Department of Energy. Washington, D.C.
(DOE 2001a) 10 CFR 830 Subpart A, U.S. Department of Energy, Quality Assurance
Requirements. 66 FR 1810, Federal Register, Vol. 66, No. 7, dated 1-10-2001. Washington, D.C.
DOE 2001b) DOE O 435.1, Ch.1, Radioactive Waste Management. U.S. Department of Energy.
Washington, D.C.
(DOE 2002) DOE-HDBK-1108-2002, RADIOLOGICAL SAFETY TRAINING FOR ACCELERATOR
FACILITIES, U.S. Department of Energy. Washington, D.C.
(DOE 2004a) DOE O 420.2B, Safety of Accelerator Facilities, U.S. Department of Energy.
Washington, D.C.
(DOE 2004b) DOE O 231.1A, Ch.1. Environment, Safety and Health Reporting, U.S. Department
of Energy. Washington, D.C.
(DOE 2004c) DOE M 231.1-1A, Ch. 1, Environment, Safety and Health Reporting Manual, U.S.
Department of Energy. Washington, D.C.
(DOE 2005a) DOE O 414.1C, Quality Assurance, U.S. Department of Energy, Washington, D.C.
(DOE 2005b) DOE O 226.1, Implementation of Department of Energy Oversight Policy, U.S.
Department of Energy. Washington, D.C.
(DOE 2005c) DOE O 151.1C, Comprehensive Emergency Management System, U.S. Department
of Energy. Washington, D.C.
(DOE 2005d) DOE O 420.1B, Facility Safety, U.S. Department of Energy. Washington, D.C.
(DOE 2007a) 10 CFR 835, U.S. Department of Energy. Occupational Radiation Protection.
Federal Register, Vol. 72, No. 110, dated 06-10-2007. Washington, D.C.
(DOE 2007b) 10 CFR 820, U. S. Department of Energy, Procedural Rules for DOE Nuclear
Activities, Vol. 72, No. 110, dated 06-10-2007. Washington, D.C.
(DOE 2007c) DOE O 440.1B, Worker Protection Program for DOE (Including the National Nuclear
Security Administration) Federal Employees, U.S. Department of Energy. Washington, D.C.
(DOE 2007e) DOE-HDBK-1130-2007, RADIOLOGICAL WORKER TRAINING, U.S. Department of
Energy. Washington, D.C.
Section 186
(DOE 2007f) DOE-HDBK-1131-2007, GENERAL EMPLOYEE RADIOLOGICAL TRAINING, U.S.
Department of Energy. Washington, D.C.
DOE G 441.1-1C 278
5-19-08
(DOE 2007g) DOE-STD-1107-2007, Chg 1, KNOWLEDGE, SKILLS, AND ABILITIES FOR KEY
RADIATION PROTECTION POSITIONS AT DOE FACILITIES, U.S. Department of Energy. Washington,
D.C.
(DOE 2008a) DOE-STD-1098-2008, RADIOLOGICAL CONTROL, U.S. Department of Energy.
Washington, D.C.
(DOE 2008b) DOE HDBK 1110-2008, ALARA TRAINING FOR TECHNICAL SUPPORT PERSONNEL,
U.S. Department of Energy. Washington, D.C.
(DOE 2008c) DOE-HDBK-1130-2008, RADIOLOGICAL WORKER TRAINING MATERIALS, APPENDIX
A: RADIOLOGICAL CONTROL TRAINING FOR SUPERVISORS; U.S. Department of Energy. Washington,
D.C.
(DOE 2008d) DOE-HDBK-1145-2008, RADIOLOGICAL SAFETY TRAINING FOR PLUTONIUM
FACILITIES, U.S. Department of Energy. Washington, D.C.
(DOE 2008e) DOE-HDBK-1141-2008, RADIOLOGICAL ASSESSOR TRAINING, U.S. Department of
Energy. Washington, D.C.
(DOE 2008f) DOE-HDBK-1129-2008, TRITIUM HANDLING AND SAFE STORAGE, Appendix F:
RADIOLOGICAL TRAINING FOR TRITIUM FACILITIES, U.S. Department of Energy. Washington, D.C.
(DOE 2008g) DOE-HDBK-1130-2008; RADIOLOGICAL WORKER (RW) TRAINING
MATERIALS,Appendix B: RADIOLOGICAL CONTAMINATION CONTROL TRAINING FOR LABORATORY
RESEARCH, U.S. Department of Energy. Washington, D.C.
(DOE 2008h) DOE-HDBK-1130-2008; RADIOLOGICAL WORKER (RW) TRAINING MATERIALS,
Appendix C RADIOLOGICAL SAFETY TRAINING FOR RADIATION-PRODUCING (X-RAY) DEVICES, U.S.
Department of Energy. Washington, D.C.
(DOE 2008i) DOE-HDBK-1113-2008, RADIOLOGICAL SAFETY TRAINING FOR URANIUM FACILITIES,
U.S. Department of Energy. Washington, D.C.
(DOE 2008j) DOE-STD-1121-2008, INTERNAL DOSIMETRY, U.S. Department of Energy.
Washington, D.C.
(DOE 2008k) DOE-STD-1129-2008. TRITIUM HANDLING AND SAFE STORAGE, APPENDIX E:
RADIOLOGICAL CONTROL PROGRAMS FOR SPECIAL TRIT IUM COMPOUNDS, U.S. Department of
Energy, Washington, D.C.
(DOE 2009a) DOE M 251.1C, Departmental Directives Program Manual, U.S. Department of
Energy, Washington, D.C.
(DOE 2010a) DOE O 426.2, Personnel Selection, Training, Qualification, and Ceftification
Requirements for DOE Nuclear Facilities.
DOE G 441.1-1C 279
5-19-08
(DOE 2010b) DOE O 413.3B, Program and Project Management for the Acquisition of Capital
Assets, U.S. Department of Energy, Washington, D.C.
(DOE 2011a) DOE O 458.1. Radiation Protection of the Public and the Environment, U.S.
Department of Energy. Washington, D.C.
(DOE 2011b) DOE O 414.1D, Quality Assurance, U.S. Department of Energy. Washington, D.C.
(DOE 2011) DOE G 440.1-8, Implementation Guide for Use with Title 10 code of Federal
Regulations Part 851, Worker Safety and Health Program, U.S. Department of Energy. Washington,
D.C.
(EPA 1987) U.S. Environmental Protection Agency 1987. Radiation Protection Guidance to
Federal Agencies for Occupational Exposure. 52 FR 2822, Federal Register, Vol. 52, No. 17.
Washington, D.C.
(FOIA 1986) Freedom of Information Act 1986. Public Law 99-570, Title 5 U.S.C. sec. 552.
(ICRP 1977) International Commission on Radiological Protection 1977. ICRP Publication 26,
Recommendation of the International Commission on Radiological Protection, Pergamon Press. New
York, New York.
(ICRP 1979) International Commission on Radiological Protection 1979. ICRP Publication 30,
Limits for Intakes of Radionuclides by Workers: Design and Interpretation, Pergamon Press. New
York, New York.
Section 187
(ICRP 1982) International Commission on Radiological Protection 1982. ICRP Publication 37,
Cost-Benefit Analysis in the Optimization of Radiation Protection, Pergamon Press. New York, New
York.
(ICRP 1990) International Commission on Radiological Protection 1990. ICRP Publication 55,
Optimization and Decision-Making in Radiological Protection, Pergamon Press. New York, New York.
(ICRP 1991) International Commission on Radiological Protection 1991. ICRP Publication 60,
1990 Recommendations of the ICRP on Radiological Protection, Pergamon Press. New York, New
York.
(ICRP 1995) International Commission on Radiological Protection 1995. ICRP Publication 68,
Dose Coefficients for Intakes of Radionuclides by Workers, Pergamon Press. New York, New York.
(ICRP 1996) International Commission on Radiological Protection 1996. ICRP Publication 74,
Conversion Coefficients for Use in Radiological Protection Against External Radiation, Pergamon
Press. New York, New York.
(ICRP 1998) International Commission on Radiological Protection 1998. ICRP Publication 88,
Doses to the Embryo and Fetus from Intakes of Radionuclides by the Mother, Pergamon Press.
New York, New York.
DOE G 441.1-1C 280
5-19-08
(ICRU 1988) International Commission on Radiation Units and Measurements 1988. ICRU
Report No. 43, Determination of Dose Equivalents from External Radiation Sources - Part 2.
Bethesda, MD.
(ISO 1977) International Organization for Standardization 1977. ISO 1677, Sealed Radioactive
Sources - General. Geneva, Switzerland.
(ISO 1990) International Organization for Standardization 1990. Draft International Standard
ISO/DIS 9978, Radiation Protection Sealed Radioactive Sources Leakage Test Methods. Geneva,
Switzerland.
(NCRP 1972) National Council on Radiation Protection and Measurements 1972. NCRP Report
No. 40, Protection Against Radiation from Brachytherapy Sources. Bethesda, Maryland.
(NCRP 1980) National Council on Radiation Protection and Measurements 1980. NCRP Report
No. 65, Management of Persons Accidentally Contaminated with Radionuclides. Bethesda,
Maryland.
(NCRP 1985) National Council on Radiation Protection and Measurements 1985. NCRP Report
No. 84.,General Concepts for the Dosimetry of Internally Deposited Radionuclides. Bethesda,
Maryland.
(NCRP 1987a) National Council on Radiation Protection and Measurements 1987. NCRP Report
No. 87, Use of Radiobioassay Procedures for Assessment of Internal Radionuclide Deposition.
Bethesda, Maryland.
(NCRP 1987b) National Council on Radiation Protection and Measurements 1987. NCRP Report
No. 91, Recommendations on Limits for Exposure to Ionizing Radiation. Bethesda, MD.
(NCRP 1989) National Council on Radiation Protection and Measurements 1989. NCRP Report
No. 106, Limit for Exposure to "Hot Particles" on the Skin. Bethesda, MD.
(NCRP 1992) National Council on Radiation Protection and Measurements 1992. NCRP Report
No. 114, dated 11-30-92, Maintaining Radiation Protection Records. Bethesda, MD
(NCRP 1993) National Council on Radiation Protection and Measurements 1993. NCRP Report
No. 116, Limitation of Exposure to Ionizing Radiation. Washington, D.C.
(NCSL 1989) National Conference of Standards Laboratories 1989. Recommended Practice RP-1,
Establishment and Adjustment of Calibration Intervals. Boulder, Colorado.
(NRC 1987) U.S. Nuclear Regulatory Commission 1987. Regulatory Guide 8.13, Instruction
Concerning Prenatal Radiation Exposure. Washington, D.C.
Section 188
(NRC 1992) U.S. Nuclear Regulatory Commission 1992. 10 CFR 34, Licenses for Radiography and
Radiation Safety Requirements for Radiographic Operations. Washington, D.C.
DOE G 441.1-1C 281
5-19-08
(NRC 1993) U.S. Nuclear Regulatory Commission 1993. NUREG-1400, Rev. 1, Air Sampling in the
Workplace. Washington, D.C.
(NRC 1998) U.S. Nuclear Regulatory Commission 1998. NUREG-1556, Volume 11, Consolidated
Guidance About Materials Licenses. . Washington, D.C.
(OSHA 174) Occupational Safety and Health Administration 1974. Occupational Safety and
Health Standards, 29 CFR 1910, 39 FR 23502. Washington, D.C.
(PA 1974) Privacy Act 1974. Privacy Act of 1974, as amended, Public Law 93-579, Title 5 U.S.C.
sec. 552a.
(PNL 1987) Pacific Northwest Laboratory 1987. PNL-6301, Neutron Dose and Energy Spectra
Measurements at Savannah River Plant, Richland, WA.
(PNL 1988a) Pacific Northwest Laboratory 1988. PNL-6577, Health Physics Manual of Good
Practices for Reducing Radiation Exposure to As Low As Reasonably Achievable (ALARA), Richland,
WA.
(PNL 1988b) Pacific Northwest Laboratory 1988. PNL-6620, Personnel Neutron Dose Assessment
Upgrade, Richland, WA.
(USLW 1991) United States Law Week. United Automobile Workers v. Johnson Controls, Inc. 499
U.S. 187, 206 (1991).
TABLE OF CONTENTS
RADIATION PROTECTION PROGRAMS
1.0 PURPOSE AND APPLICABILITY
1.0 PURPOSE AND APPLICABILITY
1.0 PURPOSE AND APPLICABILITY
1.1 USE OF CONSENSUS STANDARDS
1.2 ACRONYMS
2.0 DEFINITIONS
2.0 DEFINITIONS
2.0 DEFINITIONS
3.0 RADIATION PROTECTION PROGRAMS
3.0 RADIATION PROTECTION PROGRAMS
3.0 RADIATION PROTECTION PROGRAMS
4.0 ALARA
5.0 INTERNAL DOSIMETRY PROGRAM
6.0 EXTERNAL DOSIMETRY PROGRAM
7.0 RADIATION GENERATING DEVICES
8.0 EVALUATION AND CONTROL OF RADIATION DOSE TO THE EMBRYO/FETUS
9.0 PORTABLE MONITORING INSTRUMENT CALIBRATION
10.0 AIR MONITORING
11.0 RADIOACTIVE CONTAMINATION CONTROL
12.0 POSTING AND LABELING FOR RADIOLOGICAL CONTROL
13.0 OCCUPATIONAL RADIATION PROTECTION RECORD-KEEPING AND REPORTING
13.1 Implementation Guidance
13.2 Records to be Generated and Maintained
13.3 Reports
13.4 Privacy Act Considerations
13.5 Record – Keeping Standards
14.0 RADIATION SAFETY TRAINING
14.1 Implementation Guidance
14.3 Training Course Content
14.4 Facility-Specific Materials
14.5 Conduct of Radiation Safety Training
14.6 Completion of Radiation Safety Training
14.7 Periodic Radiation Safety Training
14.8 Use of Escorts in Lieu of Training
14.9 Refresher Training
14.10 Other Training Programs
14.11 Training Effectiveness Evaluations
15.0 SEALED RADIOACTIVE SOURCE ACCOUNTABILITY AND CONTROL
16.0 TECHNICAL TABLES FOR OCCUPATIONAL RADIATION PROTECTION
Appendix A
Appendix B
Reserved
Appendix C
Appendix D
Appendix E
Appendix F
REFERENCES