MEMORANDUM FOR KEVIN W. SMITH
FROM:
SUBJECT:
REFERENCES:
MANAGER, LOS ALAMOS SITE OFFICE
>
DONALD L. COOK Why cy f{
DEPUTY ADMINISTRATOR Ol. (ant
FOR DEFENSE PROGRAMS j~
Approval of Request for Relief from Specific Fire Protection
Requirements in Department of Energy Order 420.18, Facility
Safety for the Los Alamos National Laboratory Nuclear Weapons
Training Facility
(1) Memorandum, Donald L. Winchell, Jr. to Brigadier General
Garrett Harencak, Subject: Request for Approval of Permanent
Exemption Request (LANL-DOE-Order-420.1B-Ex-2010-001, R.1)
for Los Alamos National Laboratory Buildings TA-41-1 and
TA-41-6; Lack of Automatic Fire Extinguishing System, Lack of a
Reliable Fire Protection Water Supply, Lack of a Fire Alarm System,
and Non-Compliant Means of Egress, as Required by
DOE-O-420.18, dated June 28, 2010
(2) LANS Letter PCM-10-125, from Mike Rafferty, Prime Contract
Chief, LANS, to Contracting Officer, LASO, Subject: Revised
Request for Temporary Equivalency Approval to DOE Order 420.18
and NFPA 101 Requirements for Los Alamos National Laboratory
(LANL) Buildings TA-41-1 and TA-41-6; Lack of an Automatic Fire
Extinguishing System, Lack of a Reliable Fire Protection Water
Supply, Lack of a Fire Alarm System, and Non-Compliant Means of
Egress, (LANL-DOE-ORDER-420.,1B-EX-2010-001, R.1), dated
June 15, 2010
(3} STO SO No. 2008-OPS-FOD-004, LANL STO Standing Order No.
2008-OPS-FOD-004, R3, TA4/-G001 Tunnel Operations, Revision 3,
dated June 17, 2010
Based on the evaluation conducted by the Office of Nuclear Safety and Governance
{NA-171), | approve the subject exemption request. As required by Department of
Energy (DOE) Order (O}) 420.1B, comments were solicited from the Office of Health,
Safety, and Security (HSS); no abjections were noted.
@& Printed with soy ink on recycled paper
CIRCUMSTANCES
The Nuclear Weapons Training Facility supports training programs for National Nuclear
Security Administration (NNSA) and others in the intelligence community, including
Department of Defense and the Department of Homeland Security. TA-41 is
intermittently occupied during training; it allows small groups of visitors “hands-on”
opportunities to study a wide range of historical models and displays from the US
weapons design inventory. However, TA-41 does not meet DOE O 420.1B fire
protection design requirements, specifically:
e Chapter Il 93 c(1)-A reliable and adequate supply of water for fire suppression
e Chapter ll 13 c (4}- Automatic fire extinguishing systems [in areas with] fire loss
potential in excess of limits defined by DOE.
e Chapter Il 13 ¢ (7) - A means to notify emergency responders and building
occupants of a fire (e.q., fire alarm or signaling system)
e Chapter Il 93 c (8) - Emergency egress ... for safe facility evacuation in the event
of fire as required by applicable codes or fire hazard analysis.
Los Alamos National Security recently upgraded and reactivated the previously disabled
fire detection and alarm system. This action will result in compliance with DOE O
420.18 Chapter |] 43 ¢ {7}. Also, it will improve the level of protection afforded to
building occupants similar to that intended by the National Fire Protection Association
(NFPA) Life Safety Code, resulting in compliance with DOE O 420.1B Chapter Il 43 ¢ (8}.
Section 2
Because of the training material inventory, the maximum possible fire loss (MPFL} for
TA-41 exceeds $3,000,000 (the DOE threshold where automatic fire suppression is
required). Due to inherent hazards associated with maintaining the water supply lines
in the canyon, the existing fire water supply infrastructure has been abandoned in place
and remains impaired. tong term, Los Alamos National Laboratory (LANL) intends to
house nuclear weapons training in a new facility and does not anticipate restoring the
capabilities of the TA-41 structure if destroyed by fire.
SAFETY ASSURANCE
The Los Alamos Site Office (LASO} conditions of approval (Reference 1), the LANL formal
Standing Order (Reference 3) which is attached, and the approved Facility Safety Plan
limit tunnel activities, facility usage, the number of visitors, and combustible materials in
TA-41. The formal Standing Order requires dedicated fire watch during training, access
control, and monthly inspections for combustibles. The installation of a remotely-
monitored automatic smoke detection and alarm systems within TA-41-1 will ensure
early warning to occupants, prompt evacuation, and fire department dispatch in the
event of a fire.
Given the expected remaining operational facility life-cycle, the limited use of the
facility, and the compensatory measures, facility upgrades (automatic fire suppression
and fire suppression water supply) to meet DOE O 420.1B requirements are not
necessary in order to achieve the underlying purpose of the requirement. Therefore, the
costs and risks associated with those upgrades are not justified. The proposed
compensatory actions and the upgrade of the fire alarm and detection system provide a
sufficient level of protection for the facility occupants and the historically-significant
contents. Thus, the request for permanent exemption meets the approval criteria
required in DOE OG 251.1C, Departmental! Directives Program:
a. [it] is not prohibited by law;
b. would not present an undue risk to public health and safety, the
environment, facility workers, or security; and
C. is warranted under the circumstances.
LASO will continue to monitor status of funding and project development, including
design and construction schedule for the proposed replacement facility.
TERMS AND CONDITIONS
The following terms and conditions apply to this approval:
1. Continue to fully implement compensatory measures (including those pertaining
to combustible load and occupancy limits) as specified by LASO in Reference 2;
2, LASO must verify that the recently installed remotely-monitored automatic
smoke detection and fire alarm system within building TA-41-1 complies with
NFPA 72, National Fire Alarm Code;
3, The Standing Order (Reference 3} must remain in effect; any changes to it must
be approved by LASO; and
4, Provide recurring fire department tours to ensure facility familiarity remains
high.