Section 1
U.S. Deparhmt of Energy ORDER
all
Washington, 11.C. DOE 5480.7A
1 J
. 2-17-93
SUBJECT: FIRE PROTECTION
1. PURPOSE . To establish requirements for a comprehensive fire protection
. and related perils protection program sufficient to attain Department of
Energy (DOE) objectives.
i 2. CANCELLATION. DOE 5480.7, FIRE PROTECTION, of 11-16-87.
3. W!K.
a. Provisions:
The provisions of this Order apply to all Departmental Elements. It
specifically applies to personnel and property at all DOE-owned or
-leased structures. This Order has primacy over all other DOE Orders
with respect to matters concerning fire protection.
CD The Naval Nuclear Propulsion Program, as stipulated below, is exempt
from the provisions of this Order.
DOE facilities, projects and programs that are licensed by the
Nuclear Regulatory Commission (NRC) or an NRC Agreement State shall
use the requirements specified by the NRC or NRC Agreement State in
lieu of this Order where requirements overlap NRC or NRC Agreement
State regulations.
b. At)t)lication to Contracts:
The provisions of this Order are to be applied to covered contractors
and they will apply to the extent implemented under a contract or
other agreement. A covered contractor (including Management and
Operating contracts) is a seller of supplies or services performing
on-site at a DDE-owned or -leased facility and awarded a procurement
contract or a subcontract. The term “procurement contract” does not
include small purchases.
4. OBJECTIVES . The objectives of this Order are as follows:
a. Minimize the potential for the occurrence of a fire.
b. Ensure that fire does not cause an on-site or off-site release of
a)
radiological and other hazardous material that will threaten the
public health and safety or the environment.
DISTRIBUTION: INITIATED BY:
All Departmental Elements Assistant Secretary for
Environment, Safety and Health
—
2 DOE 5480.7A
2-17-93
5.
c.
d.
e.
f.
Establish requirements that will provide an acceptable degree of life
safety to DOE and contractor personnel and that there are no undue
hazards to the public from fire and its effects in DOE facilities.
Ensure that process control and safety systems are not damaged by
fire or related perils.
Ensure that vital DOE programs will not suffer unacceptable delays as
a result of fire and its effects. .
Ensure that property
exceed an acceptable
damage from fire and related perils does not
level. 4
MANDATORY FIRE PROTECTION CRITERIA. Fire protection criteria, delineated in
the following codes, standards and other documents are the minimum
requirements for the implementation of the DOE Fire Protection Program.
These criteria are mandatory as a result of statutory requirements or DOE
policy requirements. Where conflicts in the application of these codes and
standards arise, the more restrictive requirements apply.
a.
b.
c.
d.
e.
f.
9“
h.
Code of Federal Regulations (CFR) 29, Part 1910
CFR 29, Part 1926
National Fire Protection Association (NFPA) Codes and Standards
DOE 5480.4, ENVIRONMENTAL PROTECTION, SAFETY, AND HEALTH PROTECTION
STANDARDS, of 5-15-84, which specifies requirements for the application ‘
of environmental protection, safety, and health standards.
DOE 6430.lA, GENERAL DESIGN CRITERIA, of 4-6-89, which provides general
design criteria for use in the acquisition of the Department’s
facilities.
DoE/EP-olo8, “Standard for Fire Protection of AEC Electronic Computer
Data Processing Systems”.
Section 2
DOE/EV-0043, 8-79, “Standard on Fire Protection for Portable
Structures”.
Other DOE Orders and statutory requirements, not listed above, that
contain requirements of a more limited extent relating to the DOE Fire
Protection Program.
DOE 5480.7A
2-17-93
3
NOTE:
APPLICATION OF CODES AND STANDARDS. The fire protection related codes and
standards in effect when facility design commences (code of record) remain
, in effect for the life of the facility. When modifications of a
substantial nature occur, as determined by the authority having
I jurisdiction (AHJ), the current edition of the code shall apply to the
modification. EXCEPTION: If there is a significant hazard that endangers
building occupants or the public, as determined by the AHJ, the facility
shall be upgraded to the requirements of the current edition of the code or
standard. . . . . . . . . . .
6. DOE REFERENCED CRITER~. The following references contain additional. criteria and guidelines pertaining to the DOE Fire Protection Program:
a.
b.
c.
e.
f.
9.
●
h.
j.
k.
1.
m.
a’ n.
DOE Fire Protection Resource Manual.
“General Fire Fighting Guidance for Nuclear Weapons,” (this
document is Confidential Restricted Data) (TP20-11) (DOE).
DOE 5482.lB, ENVIRONMENT, SAFETY, AND HEALTH APPRAISAL PROGRAM, of
9-23-86, which establishes the environmental protection, safety, and
health protection appraisal program.
DOE 5484.1, ENVIRONMENTAL PROTECTION, SAFETY, AND HEALTH PROTECTION
INFORMATION REPORTING REQUIREMENTS, of 2-24-81, which establishes
procedures for the reporting of information having environmental
protection, safety, or health protection significance.
DOE 5500.lB, EMERGENCY MANAGEMENT SYSTEM, of 4-30-91, which establishes
procedures for planning for emergencies involving DOE or requiring DOE
assistance.
National Fire Protection Assoc.
Factory Mutual Loss Prevention
Society of Fire Protection Eng
ation Handbooks.
Data Sheets.
neers (SFPE) Handbook.
DOE Explosives Safety Manual, DOE/EV/06194.
Local and State fire protection criteria.
American Petroleum Institute Guidelines.
NFPA guides, manuals
“Product Directories
periodic supplements
and recommended practices.
of Underwriters Laboratories,” toqether with the
(UL).
“Factory Mutua Research Corporation Approva” Guide” (FM).
4
7. j)EFINITIONS.
DOE 5480.7A
2-17-93
●
a.
b.
c.
d.
e.
f.
9“
weDtable. When applied to fire safety, “acceptable” is a level of
protection which the Authority Having Jurisdiction, after consultation with
the cognizant DOE fire protection engineer(s), considers sufficient to
achieve the objectives defined above. In some instances, it is a level of
protection necessary to meet a code or standard. In other instances it is
a level of protection that deviates (plus or minus) from a code or standard
as necessary and yet adequately protects against the inherent fire hazards.
Authority Havina Jurisdiction (AHJ~. The decision making authority in
matters concerning fire protection. Except as directed by the Program
Secretarial Officers, the Heads of Field Organizations or designee is the
AHJ. Decisions impacting fire safety shall be made by the AHJ only after .
consultation with the cognizant DOE fire protection engineer(s). Where an
Area Office or Site Office exists within the DOE organization, a formal,
clearly defined delegation of fire protection responsibility shall be
established regarding the AHJ.
Section 3
DOE Fire Protection Proaram. Those fire protection requirements,
hardware, administrative controls, procedures, guidelines, plans,
personnel, analyses, and technical criteria that comprehensively ensure
that DOE objectives relating to fire safety are achieved.
~aulvalen y
. The approved alternate means of satisfying the technical
provision: ;f a fire protection code or standard. (Deviations from ●
specific requirements of occupational safety and health standards, as
delineated in the Code of Federal Regulations, are treated as variances as
defined in the Department’s Occupational Safety and Health Program).
EXem~tio~. The approved deviation from a non-statutory code, standard or
DOE Order. (Deviations from specific requirements of occupational safety
and health standards, as delineated in the Code of Federal Regulations, are
treated as variances as defined in the Department’s Occupational Safety and
Health Program).
Fire A
. re~. A location bounded by construction having a minimum fire
resistance rating of 2 hours with openings protected by appropriately ●
fire-rated doors, dampers, or penetration seals. The boundaries of
exterior fire areas (yard areas) shall be as determined by the authority
having jurisdiction. 9
Fire LOSS. The dol”
condition (refer to
to the facility and
value. Losses will
ar cost of restoring damaged property to its pre-fire
DOE 5484.1) . In determining loss, the estimated damage
contents shall include replacement cost, less salvage
exclude costs of restoration of:
(1) Property that is scheduled for demolition.
(2) Property:
(a) decommissioned and not carried on books as a value, or
5
2-17-93
(b) where there is no loss potential.
Include the cost of decontamination and cleanup, the loss of production or
program continuity, the indirect costs of fire extinguishment [such as
damaged fire department equipment), and consequent effects on related
areas, in all property loss amounts.
h. Fire Protection. ..&broad term which encompasses all aspects of fire
safety, including: building construction and fixed building fire
features, fire suppression and detection systems, fire water systems,
emergency process safety control systems, emergency fire fighting
organizations (fire departments, fire brigades, etc.), fire protection
engineering, and fire prevention. Fire protection is concerned with
preventing or minimizing the direct and indirect consequences of fire.
It also includes aspects of the following perils as they relate to fire
protection: explosion, natural phenomenon, smoke and water damage from
fire.
i. Fire Protection Sfstem. Any system designed to detect, extinguish, and
limit the extent of fire damage or enhance life safety. Where
redundant fire protection systems are required, any two of the
following will satisfy that requirement. These include:
(1)
(2)
(3)
(4)
Automatic suppression systems, such as fire sprinklers, foam,
gaseous, explosion suppression, or other specialized extinguishing
systems plus appropriate alarms. An adequate supply, storage and
distribution system is an essential element.
Automatic fire detection, occupant warning, manual fire alarm, and
fire alarm reporting systems combined with properly equipped and
adequately trained fire departments or brigades.
Fire barrier systems or combinations of physical separation and
barriers for outdoor locations.
Other systems, such as alternate process control systems, as
approved by the AHJ.
.
j. Maximum Credible Fire Loss (MCFL). The property damage that would be
Section 4
expected from a fire, assuming that:
#
(1) All installed fire protection systems function as designed.
(2) The effect of emergency response is omitted except for post-fire
actions such as salvage work, shutting down water systems, and
restoring operation.
k. Maximum Possible Fire Loss (MPFL). The value of property, excluding
land, within a fire area, unless a fire hazards analysis demonstrates a
~)
lesser (or greater) loss potential. This assumes the failure of both
automatic fire suppression systems and manual fire fighting efforts.
6 DOE 5480.7A
2-17-93
1. PmD ertv. All government-owned or leased structures and contents for which
the Department has responsibility, including:
(1) All DOE land, structures, and contents.
(2) All leased locations.
(3) All other Government property on DOE land or in DOE structures.
(4) Other property that occupy DOE land or are in DOE structures.
m. Qual i fied Fire Protection En~ineer. A graduate of an accredited
engineering curriculum and having completed not less than four years of “
engineering practice, three of which shall have been in responsible charge
of diverse fire protection engineering work. If not such a graduate, a
qualified engineer shall, either: demonstrate a knowledge of the principles
of engineering and have completed not less than six years engineering
practice, three of which shall have been in responsible charge of diverse
fire protection engineering projects; be a registered professional engineer
in fire protection; or meet the requirements for a Grade 11 or higher Fire
Protection Engineer as defined by the Office of Personnel Management.
n. Related Perils. Aspects of the following as they relate to fire
protection: explosion, natural phenomenon, smoke, and water damage. ●
o. ~.lB~ term used to describe the overall potential for loss (refer to DOE
. .
P* Safetv Cla s EQUs iDment. Systems, structures, or components including
primary environmental monitors and portions of process systems, whose
failure could adversely affect the environment, or the safety and health of
the public.
For nuclear reactors and non-reactor nuclear facilities, Class A Equipment
includes those systems, structures, or components with the following
characteristics: *
o Those whose failure would produce exposure consequences that would
exceed DOE established guidelines at the site boundary or nearest point ●
of uncontrolled public access.
o Those required to maintain operating parameters within the safety
limits specified in Technical Safety Requirements (Technical
Specification or Operational Safety Requirements) during normal
operations and anticipated operational occurrences.
o Those required for nuclear criticality safety.
7
.
,
8.
0 Those required to monitor the release of radioactive materials to
the environment during and after a design basis accident.
o Those required to monitor and maintain the facility in a safe
shutdown condition.
o Those that control the safety class items described above.
. . . . .
q“ Vital Prog~. A DOE program so defined by the Program Secretarial
Officers.
RESPONSIBILITIES ANII AUTHORITIES.
a. Proqram Secretarial Officers.
For matters affecting facilities under their programmatic
responsibility, PSOS shall:
(1)
(2)
(3)
(4)
(5)
(6)
Direct DOE fire protection programs for personnel and property
under their responsibility.
Evaluate and assess in accordance with this Order, the adequacy of
contractor fire protection programs so as to assure that the
criteria in paragraph 8h are met and the elements delineated in
paragraph 9 are incorporated.
Section 5
Review and define each vital program and provide current
information to the head of the field organization describing the
maximum acceptable impact on the program if a property within the
field organization is lost due to a fire. This shall include the
maximum acceptable down time if less than 6 months and fire loss if
less than $150M.
Establish and maintain a system to assure that the DOE fire
protection program is documented and incorporated in the plans and
specifications for all new facilities and for major modifications
of existing facilities. This includes oversight by a qualified
fire protection engineer of plans, specifications, and testing of
fire protection features.
Review field organization requests for exemptions. Obtain EH-1
approval for proposed actions on exemption requests. (Coordinates
with NS-1 when nuclear fire safety issues are involved.)
Maintain or has access to an adequate fire protection staff,
including one or more qualified fire protection engineers, to
accomplish the above responsibilities. Continuing education and
training should be provided to maintain and enhance the level of
competency of the fire protection staff.
. . . ,- ‘
8 DOE 5480.7A
2-17-93
b. Assistant Secretar~ for Environment, Safety and Health (EH-1).The
(1)
(2)
(3)
(4)
(5)
(6)
(7)
Develops fire protection requirements and guidelines for programs and
facilities. Coordinates the development of fire protection criteria
with the Office of Organization, Resources and Facilities Management
(AD-1 O), the Director of Nuclear Safety Pol icy and Standards (NE-70),
PSOS, and other appropriate Headquarters organizations to assure the
consistency of such criteria with the requirements of applicable fire
protection codes and, DOE 5480.4, and this Order.
Evaluates and assesses, in accordance with this Order and DOE 5482.lB,
the adequacy of DOE fire protection programs.
Disseminates fire protection related technical information through the
Annual Summary of DOE Fire Protection Programs and updates of the Fire
Protection Resource Manual.
Issues guidance and interpretations of the DOE fire protection program
in coordination with NE-70.
Approves fire protection exemption requests.
requests shall be completed within 60 days of
Approval of the Office of the Secretary (S-1)
any generic fire protection exemption request
safety implications.
Coordinates activities of the DOE Fire Safety
Action on exemption
recei~t of the- rewest.
shall’ be solicited for
that has DOE-wide nuclear ●
Committee
Maintains or has access to an adequate fire protection staff to
accomplish the above responsibilities, including one or more qualified
fire protection engineers. Continuing education and training should be
provided to maintain and enhance the level of competency of the fire
protection staff.
c. The Director of Nuclear Safety (NS-1).
(1)
(2)
(3)
Evaluates and assesses, in accordance with this Order the adequacy of
DOE Fire Protection Programs relative to nuclear safety.
Concurs with fire protection exemptions that relate to nuclear fire
safety. Action on exemption requests shall be completed within 60 days
of receipt of the request.
Maintains or has access to an adequate fire protection staff, including
a qualified fire protection engineer, to accomplish the above
responsibilities. Continuing education and training should be provided
to maintain and enhance the level of competency of the fire protection
staff.
DOE 5480.7A
2-17-93
9
al)
.
.
d.
e.
Section 6
f.
9“
. . . .
The Assistant Secretary for Nuclear Enerqv [NE-1).
(1)
(2)
T h e
Reviews and concurs with fire protection policy and guidance
developed by Eli-1 that relate to nuclear safety. Provides
interpretation and guidance concerning the fire protection criteria
for nuclear facilities.
Maintains or has access to an adequate fire protection staff,
including a qualified fire protection engineer, to accomplish the
above responsil~il ities. Continuing education and training should be
provided to maintain and enhance the level of competency of the fire
protection staFf.
Director of th~ Naval Nuclear Propulsion Proqram (NE-60).
Presidential Executive Order 12344, statutorily prescribed by
Public Law 98-525, 42 U.S.C. S7158 note (1984), establishes the
responsibilities and authorities of the Director, Naval Nuclear
Propulsion Program (who is also the Deputy Assistant Secretary for Naval
Reactors within the Department) over all facilities and activities which
comprise the program, a joint Navy-DOE organization. These executive and
legislative actions establish that the Director is responsible for all
matters pertaining to naval nuclear propulsion for all program facilities
and activities. Accordingly, the Provisions of this Order do not apply
to the Naval Nuclear Prop~l~ion Program.
The Director of Administration and Management [AD-1).
(1) Ensures that the requirements of this Order are inc.
DOE 6430.lA, GENERAL DESIGN CRITERIA.
(2) Evaluates and i~ssesses the adequacy of fire protect
Records Management Programs.
Heads of Field Organizations.
uded within
on for DOE
As directed by the PSO, the Heads of Field Organizations shall:
(1)
(2)
Ensure a level of fire protection adequate to meet the objectives of
this Order for personnel and property within their responsibility.
Where an area office exists within the organization, a clear, formal
delegation of fire protection responsibilities shall be established.
Establish and maintain a system to assure that the DOE fire
protection program is documented and incorporated in the plans and
specifications for all new facilities and for major modifications of
existing facilities. This includes oversight by a qualified fire
protection engineer of plans, specifications, and testing of fire
protection features.
10 DOE 5480.7A
2-17-93
(3)
(4)
(5)
(6)
(7)
(8)
(9)
( l o )
Review implementation plans for compliance with recommendations
resulting from fire protection assessments. Forwards a copy of
compliance plans, exemption requests, equivalency determinations,
compliance schedule approvals, and other requested data to the PSO.
Approve contractor requests for fire safety equivalences.
Maintain a list of facilities/contractors for which they have fire
protection appraisal responsibility in accordance with this Order,
indicating the assessment frequency for each.
Conduct fire protection assessments of facilities and/or contractors ,
according to the frequency and scope established by this Order to
assure that:
(a) The program described in paragraph 9 is being implemented.
(b) Effective action is being taken to correct deficiencies identified
from previous appraisals, including prioritization, tracking, and
implementation of interim compensatory measures.
(c) Losses, impairments, and unusual fire-related incidents have been
investigated and analyzed to identify causes, corrective action(s),
and preventive methods. ●
Section 7
Submit an annual summary to Office of Safety and Quality Assurance
(EH-30) through the PSO covering the fire protection program and loss
experience of the previous year, as required by DOE 5484.1.
Forward requests for fire protection exemptions prepared by the
contractor to the PSO. Submit a recommendation for approval for these
conditions to the PSO for those issues where, in the judgment of the
Head of the Field Organization, compliance with specific program
elements is not attainable and where an acceptable level of safety has
been provided. The cognizant Headquarters fire protection engineer
should be consulted on these issues as appropriate.
Maintain or have access to an adequate fire protection staff, including
one or more qualified fire protection engineers, to accomplish the ●
above objectives. Continuing education and training should be provided
to maintain and enhance the level of competency of the fire protection
staff.
Establish and maintain a method to disseminate fire protection
information from Headquarters to the contractors and vice versa.
DOE 5480.7A
2-17-93
11
.- .
(11) Where there is no PSO, the Head of the Field Organization shall
assume the responsibilities as delineated in paragraph 8a. Where
there is no contractor, the Head of the Field Organization shall
assume the responsibilities as delineated in paragraph 8h.
h. Heads of Headquarters Elements and Heads of Field Organizations.
The senior ranking DOE official at a DOE office location shall include
the following in a procurement request package for each procurement
requiring the application of this directive: (1) identification of the
Directive, (2) identification of the specific requirements with which a
contractor or other awardee is to comply, or, if this is not
practicable, identification of the specific paragraphs or other portions
of this Directive with which a contractor or other awardee is to comply,
and (3) requirements for the flowdown of provisions of this directive to
any subcontract or subaward. For application to awarded management and
operating contracts, Heads of Headquarters Elements and heads of field
organizations may set forth this information in a written communication
to the contracting officer rather than in a procurement request package.
i. Contractor Organizations.
As required by the PSO or the Heads of Field Organizations and directed
by the Contracting Officer, contractors shall be required to:
(1)
(2)
(3)
(4)
(5)
(6)
Provide and maintain a level of fire protection to meet the
objectives of paragraph 4, and the criteria of paragraph 9.
Provide and maintain a system to ensure that the requirements of
the DOE fire protection program are documented and incorporated in
the plans and specifications for all new facilities and for major
modifications of existing facilities. This includes review and
comment by a qualified fire protection engineer of plans,
specifications and test procedures and results for fire protection
features.
Assist DOE in coordinating fire safety assessments at those
facilities included in the survey program, establish action plans
for compliance with recommendations resulting from the assessments,
and forward compliance plans, exemption requests, and other
requested data to DOE field organizations.
Establish and maintain a list of facilities for which the
contractor has fire protection assessment responsibility.
Conduct fire protection assessments of facilities according to the
scope and frequency established by this Order.
Section 8
Provide fire protection technical assistance to DOE.
12 ;0;75;:0 . 7A
. -
9.
(7) Submit requests for exemptions and fire safety equivalences to –
the Head of the Field Organization for those facilities where
compliance with specific program elements is not attainable and
where an acceptable level of safety has been achieved.
(8) Maintain or have access to an adequate fire protection staff,
including a qualified fire protection engineer(s). Continuing
education and training should be provided to maintain and enhance
the level of competency of the fire protection staff.
.
DOE FIRE PROTECTION PROGRAM REQUIREMENTS.
A DOE facility shall be characterized by a level of fire protection sufficient “
to fulfill the requirements for the best protected class of industrial risks
(Highly Protected Risk/Improved Risk). This program is characterized by the
inclusion of a continuing, sincere interest on the part of management and
employees in minimizing losses from fire and related perils and the inclusion
of preventive features necessary to ensure the satisfaction of objectives
related to safety.
Based upon the above paragraph, the DOE Fire Protection Program shall meet or
exceed the minimum requirements established by the National Fire Protection
Association as directed by the PSO. Basic requirements shall include: a
reliable water supply of acceptable capacity for fire suppression;
noncombustible construction of an acceptable nature for the occupancy of the ●
facility; automatic fire extinguishing systems; a fully staffed, trained, and
equipped emergency response force; a means to summon the emergency response
force in the event of a fire; and a means to notify and evacuate building
occupants in the event of a fire. For areas subject to significant life safety
risks, serious property damage, program interruption, or loss of safety class
equipment as defined in the relevant facility SAR, additional protection
measures may be deemed necessary as determined by the AHJ.
This level of protection also includes: administrative procedures encompassing
controls for hazardous substances/processes; inspection, maintenance, and
testing of fire protection features; and other programmatic fire safety
activities as defined below.
a. Procwammatic Elements. .
Fire protection programs shall incorporate the following elements to assure
that the objectives of paragraph 4 are met:
(1) Fire Protection Criteria. A documented “Fire Protection Program” which
includes:
(a) A statement of management commitment to achieve the above stated
objectives.
(b) A policy statement that implements this Order and other DOE fire ●
protection related mandatory codes and standards.
all
.
.
0
DOE 5480.7A 13
2-17-93
(c) Fire protection criteria that reflect site-specific aspects of
the fire protection program, including: the organization and
responsibilities of the fire protection staff, administrative
aspects of the fire protection program, and requirements for
physical fire protection features.
(2) Assessments. Documented evaluations of the fire protection program,
including field walkdowns of facilities, shall be performed as follows:
(a) Facil ities/ccmtractors shall be assessed to establish that they
conform with DOE fire protection criteria.
(b) Minimum Freauency
Headquarters:
o PSO assessment
. . .
of field offices . . . . . . . . . . . . . . . . . . . . . . . . .
0 EH assessment of program offices . . . . . . . . . . . . . . . . . . . . . . . .
Field Office:
Section 9
o Field office assessment of the fire
protection program of each contractor . . . . . . . . . . . . . . . . . . .
Contractors/Facility Managers:
o
0
0
0
0
Annual fire protection assessments shall be made of fac
valued in excess of $50 million; where considered to be
3 years
3 years
. 2 years
lities
moderate (Category 2“Hazard) or-high hazard (Category 1 ~azard)
as defined in DOE 5481.lB. SAFETY ANALYSIS AND REVIEW SYSTEM. for
nonnuclear facilities and’in DOE 5480.23, NUCLEAR SAFETY ANALYSIS
REPORTS, for nuclear facilities; or in which vital programs are
involved.
Fire protection assessments shall be made at least every
two years of facilities plus equipment valued at $10
million to $50 million.
Remaining facilities shall be assessed at least every three years
or at frequencies determined by the AHJ.
Comprehensive
shall be made
Copies of the
file.
assessments of fire protection program elements
every two years.
two most recent assessment reports shall be kept on
r–
14 D) EJ4$$I .7A
. -
(c) Nature and ScoDe. Assessments shall include an evaluation of the
following elements of the fire protection program:
Program-related:
o
0
0
0
0
0
0
0
Comprehensiveness of the fire protection program.
Procedures for engineering design and review.
Procedures for maintenance, testing, and inspection.
Fire protection engineering staff (number,
qualifications, training).
Fire suppression organization (personnel
and training).
Fire suppression mutual aid agreements.
Management support.
Exemptions and documented equivalences.
Facility-related:
o Fire protection of safety class equipment.
o Life safety considerations.
o Fire protection of vital programs.
o Fire protection of high value property.
o Fire suppression equipment.
o Water runoff.
o Pre-fire plans.
o Fire apparatus accessibility.
o Completeness of fire hazards analyses.
o Fire barrier integrity.
o Completeness of fire loss potential
(MPFL/MCFL) determinations.
o Fire safety training.
Combined Aspects (Program & Facility):
o Inspection, testing, and maintenance reports.
o Adequacy of facility appraisal reports.
o Tests of fire suppression systems, water supplies,
and procedures for maintaining these in working order.
o Administrative controls.
o Temporary protection and compensatory measures.
o Status of findings from previous assessments.
o Conformance with applicable Orders, codes and standards.
DOE 5480.7A
2-17-93
15
(3) Fire Hazards Analvses. The purpose of a fire hazards analysis (FHA)
is to comprehensively assess the risk from fire within individual
fire areas in a DOE facility in relation to existing or proposed fire
protection so as to ascertain whether the objectives of paragraph 4,
are met. A graded FHA, that reflects the risks from fire in a
facility, shal 1 be performed for new facilities as directed by DOE
6430.1A, for nuclear facilities where safety analyses are required by
DOE 5480.23, and as directed by the PSO. A Safety Analysis Report
(SAR) that addresses the following elements will satisfy the
requirement for an FHA. A graded FHA shall contain, but not be
limited to, the following elements:
(a)
(b)
(c)
(d)
(e)
(f)
(9)
(h)
(i)
(j)
(1)
(m)
(n)
(o)
(P)
Section 10
Description of construction.
Protection of essential safety class equipment.
Fire protection features.
Description of fire hazards.
Life safety considerations.
Critical process equipment.
High value property.
Damage potential: Maximum Credible Fire Loss (MCFL) and Maximum
Possible Fire Loss (MPFL).
Fire Department/Brigade response.
Recovery potential.
Potential for a toxic, biological and/or radiation incident due
to a fire.
Emergency planning.
Security considerations related to fire protection.
Natural hazards (earthquake, flood, wind) impact on fire safety.
Exposure fire potential, including the potential for fire spread-.
between fire areas.
An FHA shall be performed under the direction of a qualified fire
protection engineer.
b. Phvsical Features of the Proqram.
DOE facilities shall incorporate the following elements to assure that
the objectives of paragraph 4, are met:
8
(1) Safet.v Class Equipment. In areas where a fire could cause damage to
safety class equipment and where no redundant safety capability
exists, a redundant fire protection system shall be provided for the
safety class equipment. For new facilities, redundant Safety Class
Equipment shall located be in separate fire areas. Fire suppression
systems shall be designed such that their actuation will not damage
safety class equipment or cause a criticality incident.
16 DOE 5480.7A
2-17-93
(2) Life Safetv. Life safety provisions shall be provided for all
facilities in accordance with the Life Safety Code (LSC), NFPA
Standard 101. The methods outlined in NFPA 101M may be used to obtain
an equivalent level of life safety where strict compliance is not
possible. Exit requirements for toxic and explosive environments shall
be as determined by the AHJ. In addition, for explosives environments,
exits shall reflect the criteria contained in the DOE Explosives Safety
Manual, (DOE/EV 06194). Where noncompliance with some Life Safety Code
provisions may be required for public safety, as in some containment
structures, additional protective systems and personnel limits should
be maintained. Compliance with the Life Safety Code shall be
considered to satisfy the exit requirements of the applicable building
code and OSHA 29 CFR 1910.
(3) Automa tic Fire Protection. Complete automatic fire suppression systems
designed in accordance with applicable NFPA standards shall be provided
as follows:
(a) In all new structures over 5,000 square feet.
(b) In all structures having an MPFL in excess of $1,000,000. or where
the maximum credible fire will result in the loss of use of a vital
structures for a period longer than that specified as acceptable by
the applicable PSO. ●
(4) Redundant Fire Protection.
(a) When the MPFL exceeds $50 mill ion, a redundant fire protection
system is provided that, despite the failure of the primary fire
protection system, will limit the loss to $50 million.
(b) When the MPFL exceeds $150 mill ion, a redundant fire protection
system and a 3-hour fire barrier are required to limit the maximum
possible fire loss to $150 million.
(5) Testinq and Maintenance. Fire protection systems shall be tested and .
maintained in accordance with the applicable NFPA standards and as
supplemented by criteria in the DOE Fire Protection Resource Manual.
(6) Qua1 itv Construction. New permanent structures in excess of 5,000
●
square feet of area shall be of noncombustible or fire resistive
construction.
I
DOE 5480.7A 17
2-17-93
Section 11
(7) Fire Department. A fully staffed, trained, and equipped fire
department/brigade shall service all DOE facilities, except as
determined by the PSO. (Refer to the fire protection positions on
minimal staffing levels in the DOE Fire Protection Resource Manual.)
DOE or Contractor-operated organizations with the responsibility for
providing fire protection for DOE property may enter into mutual aid
agreements with other fire departments in accordance with Public Law
46 (Title 42 U!SC Section 1856).
.
(8) Fire Protection Water SUDD IY An automatic water supply for fire
protection having a minimum two hours stored water capacity shall be
. maintained. Municipal supplies having the same capability are
acceptable. Facilities having a MPFL in excess of $50 million shall
be provided with an additional, independent source of fire protection
water.
A water supply dedicated for fire protection may be necessary as
determined by the PSO. A dedicated system shall be able to meet hose
stream and sprinkler system demands.
A combined fire and process/domestic system shall be able to deliver
the fire demand plus the maximum daily domestic demand for the
required duration.
(9) Underground Pip_Jg. Mains shall be sized for the largest fire flows
anticipated but in no case shall be less than 8-inch diameter.
Supply piping to individual fire sprinkler systems shall be at least
as large as the fire sprinkler system riser.
(10) Liauid Run-off Control. Natural or artificial means of controlling
liquid run offs from a maximum credible fire shall be provided so
that contaminated or polluting liquids will not escape the site,
including potentially contaminated water resulting from fire fighting
operations. The amount of fire water that must be controlled and the
design of the containment system shall be determined based on
. consultations with the cognizant DOE fire protection engineer.
(11) Fire Alarm SYSW. Where fire suppression or fire alarm systems are
b provided, local alarms in the protected area and alarm transmission
to an acceptable remote attended location shall be provided.
(12) Containment Svstems for Ventilation. Facilities which require
ventilation containment systems shall be protected from the effects
from fire to preclude release of radioactive, toxic, or other
hazardous materials.
18 DOE 5480.7A
2-17-93
●
(13)
(14)
(15)
(16)
(17)
Sr)ecial Hazard Protection. Hazards unique to DOE and not addressed by
the mandatory codes and standards listed in Paragraph 5 shall be
protected by isolation, segregation or use of special fire control
systems (inert gas, explosion suppression, etc.) as determined by the
AHJ. In addition devices for limiting or controlling the effects of a
fire (relief valves, filters, blast walls, emergency shutdown systems,
scuppers, etc.) shall be provided.
Jialon Usaqe. Future use of Halon will be governed under the conditions ,
set forth in the DOE memorandum “Interim Position on the Installation
of New Halon 1301 Fixed Fire Suppression Systems and Halon 1211
Portable Fire Extinguishers,” dated September 27, 1990, and superseding .
documents.
Se ismic Criteri4. The design of fire protection systems to withstand
seismic events shall be in-accordance- with the criteria developed by
the National Fire Protection Associat
DOE criteria.
~MD airment Control. A fire protection
be provided for control of operations
during periods when fire protection s!stems are out of service.
on, except as required by other
Section 12
system impairment program shall
and tracking of impairments
~iciher Standard of Protection. A higher standard of protection, which
includes fire protection features beyond those stimulated above, may be
warranted uncle; certain circumstance~. These featu;es shall be - “
determined by the PSO. The following factors shall be considered:
(a) importance
(b) effect on production
(c) costs versus benefits
(d) future conditions *
c. Adm inistrative Features of the Procram.
(1) Fire Prevention Procedures. Facilities shall have procedures governing ‘
the use and storage of combustible, flammable, radioactive and
hazardous materials so as to minimize the risk from fire. Such
procedures shall also exist for activities, such as smoking
limitations, isolation of hot work, and other fire prevention measures,
which contribute to the decrease in fire risk.
DOE 5480.7A
2-17-93
19 (and 20)
(2)
(3)
i
(4)
(5)
(6)
BY ORDER
Assessment Results Trackinq Proqram. There shall be a program to
identify, prioritize and monitor the status of fire protection
related assessment findings/recommendations until resolution is
achieved. Resolution could be achieved by either: plant
modification, procedure change, fire safety equivalency, or
exemption.
Interim Comr)ensatorv Measures. When final resolution of a
finding/recomm~ndation will be significantly delayed because of
funding, scheduling, or other considerations, appropriate interim
compensatory measures (e.g., fire watches, fire patrols, enhanced
hazards control procedures, temporary fire protection features) shall
be implemented to minimize the fire risk.
ODerabilitv S~ecifications. Minimum requirements to establish
“operability” shall be developed for fire protection features such
as: fire doors, fire dampers, fire detection and suppression systems,
fire protection water supplies, etc. Periodic tests, conducted to
satisfy the applicable NFPA codes and standards or other DOE criteria
shall confirm that these features are operable. If fire protection
will be inoperable for a significant period of time, interim
compensatory measures shall be implemented until operability is
restored.
EmerqencY Plann~. Information from the fire protection program
shall be incorporated in the Emergency Plan. The facility fire
protection organization shall be involved in the development of the
Emergency Plan and in all related training and drills.
Traininq. Training shall be provided for the individuals within the
fire protection organization, the fire department/brigade, and any
other person with responsibilities for fire safety. Training programs
shall reflect the criteria contained in the mandatory codes and
standards listed in paragraph 5, and shall reflect site-specific
considerations.
Communications. Emergency communications shall be outlined in the
emergency plan. The communications capability among potential
responders to an emergency shall be coordinated to avoid confusion
and interference. This capability shall be tested on a frequency
established by the authority having jurisdiction in accordance with
DOE criteria.
OF THE SECRETARY OF ENERGY:
@
T
. LINDA G. SYE
A:t Acting Director of Organization